Inspections for the day of: Thursday, October 25, 2018.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR18-00718 INSP-Sprinkler Rough-in10/25/201810/25/201810/25/2018 2:18:17 PMPPASS
Core and shell fire sprinkler protection rough in inspection complete, overhead fire sprinkler piping above hardlid areas approved for cover.
FIR18-00718 INSP-Sprinkler Rough-in/Hydro10/24/201810/25/201810/25/2018 1:55:11 PMPDONE
Hydrostatic test for overhead fire sprinkler piping, remote FDC and undergorund supply complete, no pressure loss observed.

Phone #: ###-#### Inspection requested via web by Jessia Maxwell
BLD18-00923 FIRE-Final Inspection10/25/201810/25/201810/25/2018 12:18:30 PMPFAIL
Fire alarm inspection did not pass, FIR permit for associate fire alarm work needs to be completed before life fire safety can be finaled.

Ken Phone #: ###-####
FIR18-00159 INSP-Final Inspection10/24/201810/25/201810/25/2018 12:14:58 PMPCANC
Leon Taylor is point of contact. Phone #: ###-#### >> Inspection requested via web by Randy Knutson Inspection cancelled from web by: Randy Knutson
FIR18-00655 INSP-Final Inspection10/25/201810/25/201810/25/2018 10:32:51 AMAPASS
Final fire sprinkler inspection for area of work complete.
FIR18-00802 INSP-Final Inspection10/24/201810/25/201810/25/2018 10:32:02 AMAPASS
Rough in inspection and final inspection complete for overhead fire sprinkler piping in area of work.
FIR18-00774 INSP-Final Inspection10/25/201810/25/201810/25/2018 10:18:51 AMPFAIL
Troubleshoot HVAC unit for shutdown, HVAC unit did not shutdown with un-duct detector activation. Need city approved drawings, drawings provided did not have city stamp, plans did not show hood suppression system monitoring.

Shaine Phone #: ###-####
FIR18-00816 INSP-Final Inspection10/24/201810/25/201810/25/2018 10:16:15 AMAPASS
Final hood suppression system inspection complete.

Call Zach Phone #: ###-#### Inspection requested via web by Don Kartchner
FIR18-00703 INSP-Sprinkler Rough-in10/24/201810/25/201810/25/2018 8:45:25 AMAPASS
All tenting in place at time of inspection, rough to cover inspection for overhead fire sprinkler piping complete, all piping approved for cover.

John Phone #: ###-####
FIR18-00718 INSP-Final Inspection10/23/201810/25/201810/23/2018 9:04:24 PMACANC
Phone #: ###-#### >> Inspection requested via web by Jessia Maxwell Inspection cancelled from web by: Jessia Maxwell