Inspections for the day of: Friday, October 25, 2019.
Number of inspections: 20
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR19-00221 INSP-Sprinkler Rough-in10/25/201910/25/201910/25/2019 2:56:26 PMPPART
Rough in inspection for parking garage piping complete.

Tom Phone #: ###-####
BLD19-00775 FIRE-Final Inspection10/25/201910/25/201910/25/2019 1:45:52 PMPPASS
Previously noted items have been corrected, fire sprinkler inspection is complete, fire alarm inspection is complete, fire extinguishers are placed with current inspection tags. Final life fire safety inspection for area of work complete, signatures provide for associated trades on signature card.

Phone #: ###-#### Inspection requested via web by Korey Hall
BLD17-03168 FIRE-Final Inspection10/22/201910/25/201910/25/2019 1:35:42 PMPPASS
Previously noted items have been corrected, final life fire safety inspection is complete, signature card not provided at time of inspection.

jEREMY Phone #: ###-####
NAF19-00070 INSP-Final10/25/201910/25/201910/25/2019 12:46:08 PMPDONE
Previously noted items have been corrected, final fire sprinkler inspection for area of work complete.

Will be done by3:30pm Phone #: ###-#### Inspection requested via web by Sam Ball
FIR19-00526 INSP-Sprinkler Rough-in10/24/201910/25/201910/25/2019 12:43:37 PMAPASS
Rough to cover inspection for overhead fire sprinkler piping in area of work complete, approved for cover.

Jon Olmstead Phone #: ###-#### Inspection requested via web by Brodie Stenquist
BLD18-04076 FIRE-Final Inspection10/24/201910/25/201910/25/2019 12:43:04 PMAPASS
No fire sprinklers, no fire alarms, fire extinguishers are placed with current inspection tags. Final life fire safety inspection for area of work complete, signature provided on signature card.

Larry Phone #: ###-####
FIR18-00957 INSP-Sprinkler Rough-in/Hydro10/25/201910/25/201910/25/2019 12:42:04 PMADONE
Hydrostatic test for wet systems complete, no pressure loss observed.

KERRY IS OUR FOREMAN. THIS IS A HYDRO AND COVER INSPECTION. Phone #: ###-#### Inspection requested via web by Brad Bettencourt
FIR18-00957 INSP-Sprinkler Rough-in10/25/201910/25/201910/25/2019 12:41:20 PMPPASS
Rough to cover inspection for remaining overhead fire sprinkler piping above grid ceiling complete, approved for cover.
NAF19-00070 INSP-Sprinkler Rough-in/Hydro10/25/201910/25/201910/25/2019 12:39:54 PMPDONE
Hydrostatic for overhead fire sprinkler piping modifications complete, no pressure loss observed.

FIR19-00111 INSP-Final Inspection10/24/201910/25/201910/25/2019 10:29:58 AMACANC
Contact Noemi Carrero - ###-#### 30 min prior to Final Insp start please

Thank YOU Phone #: ###-#### >> Inspection requested via web by Teri Cruickshank Inspection cancelled from web by: Teri Cruickshank
FIR19-00490 INSP-Sprinkler Rough-in/Hydro10/24/201910/25/201910/25/2019 9:30:55 AMADONE
24 hour air test is complete.

Please call Roy for inspection time.24 hour test Phone #: ###-#### Inspection requested via web by Daniel Buccino
FIR19-00768 INSP-Sprinkler Rough-in10/24/201910/25/201910/25/2019 9:01:58 AMAPART
Rough to cover inspection for area 2A overhead fire sprinkler piping complete, area 2A approved for cover.

Call James before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
FIR19-00610 INSP-Final Inspection10/24/201910/25/201910/25/2019 8:59:50 AMAPASS
Previously noted items have been corrected, final fire alarm inspection is complete.

Phone #: 208831311 >> Inspection requested via mobile web by Nathan Price
FIR18-00503 INSP-Final Inspection10/24/201910/25/201910/25/2019 8:21:05 AMPCANC
Contact is Dirk. Phone #: ###-#### >> Inspection requested via web by Morgan Ahten Inspection cancelled from web by: Morgan Ahten
FIR19-00418 INSP-Final Inspection10/24/201910/25/201910/25/2019 8:20:20 AMAPASS
Previously noted items have benn corrected, final fire sprinkler inspection complete.

Backflow replaced with a double check valve as designed. Please call James before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
BLD19-03142 FIRE-Final Inspection10/22/201910/25/201910/25/2019 7:10:39 AMAFAIL
Fire alarm failed inspection, no life fire safety inspection performed, fire alarm inspection must pass before life fire safety inspection will be performed.

FL/S inspection with FIRE Permit #FIR19-00578 Phone #: ###-#### Inspection requested via web by Kirsten Dallmann
FIR19-00522 INSP-Alarm Testing10/23/201910/25/201910/25/2019 7:09:37 AMAFAIL
Relocate 2 smoke detectors that are overspaced. Relocate smoke detector that is to close to HVAC register or relocate HVAC register to get minimum of 36 inches away. Sync sounder base to A/V devices in space, sound did not sync.

Needs done at 7:00 am Phone #: ###-#### Inspection requested via web by Sam Ball
FIR19-00578 INSP-Final Inspection10/23/201910/25/201910/25/2019 7:07:59 AMAPASS
Final fire sprinkler inspection for area of work complete.

Inspection needs done at 7:00am Phone #: ###-#### Inspection requested via web by Sam Ball
FIR17-00186 INSP-Final Inspection10/23/201910/25/201910/24/2019 12:00:00 AMPCANC
Mark Phone #: ###-####

Kristen from Johnson Controls called to cancel this inspection.
FIR19-00614 INSP-Supply line flush10/21/201910/25/201910/21/2019 9:30:00 AMPCANC
Contact Tanner Loomis ###-#### 30 min prior to UG Flush Insp start please... Phoenix to call SUEZ for water turn on.

Thx Phone #: ###-#### >> Inspection requested via web by Teri Cruickshank Inspection cancelled from web by: Teri Cruickshank