Inspections for the day of: Friday, October 26, 2018.
Number of inspections: 19
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD18-01760 FIRE-Final Inspection10/26/201810/26/201810/26/2018 3:56:13 PMAPART
Partial final inspection for life fire safety inspection complete. TCO authorized for life safety pending fire alarm completion associated with project. Permit for life fire safety can be finaled when remaining noted items on fire alarm are complete.

Dereck-wants temp c of o Phone #: ###-####wants temp c of o
FIR18-00737 INSP-Final Inspection10/26/201810/26/201810/26/2018 3:53:57 PMPPART
Partial final inspectin complete for fire alarms system in area of work. Door release mags were not installed at time of inspection, a follow up inspection will be required for door release to final permit.

Phone #: ###-#### Inspection requested via web by Rick Groom
FIR18-00736 INSP-Final Inspection10/26/201810/26/201810/26/2018 3:53:39 PMPPART
Partial final inspectin complete for fire alarms system in area of work. Door release mags were not installed at time of inspection, a follow up inspection will be required for door release to final permit.

Phone #: ###-#### Inspection requested via web by Rick Groom
BLD18-01760 FIRE-Conference10/25/201810/26/201810/26/2018 3:52:09 PMADONE
Fire conference complete

Zack Phone #: ###-####
FIR18-00159 INSP-Final Inspection10/25/201810/26/201810/26/2018 2:33:20 PMAFAIL
Repair all noted items mentioned through inpsection on level 3 and 4. Contractor needs to walk remaining floors and fix any deficiencies found.

Leon is point of contact. Phone #: ###-#### Inspection requested via web by Randy Knutson
FIR18-00628 INSP-Sprinkler Rough-in10/25/201810/26/201810/26/2018 2:24:24 PMAPASS
Rough to cover inspection for overhead fire sprinkler piping in area of work complete, approved for cover.

RANDY Phone #: ###-#### Inspection requested via web by Nathan Stenquist
BLD17-02261 FIRE-Conference10/25/201810/26/201810/26/2018 2:23:40 PMACANC
Phone number provided is not in service, conference will need to be rescheduled with correct point of contact information, this conference request is cancelled.

Mike Phone #: ###-####
FIR18-00420 INSP-Sprinkler Rough-in/Hydro10/26/201810/26/201810/26/2018 2:21:01 PMPPART
Hydrostatic test for stairwell standpipes, underground supply and basement system witnessed, no pressure loss observed. Levels 1 through 5 to be completed when heat can be maintained at 40 degrees or above on mentioned floors.

Hydro on the basement feed and Underground coming into the basement.
Hydro on both standpipes.
Call Patrick @ ###-#### Phone #: ###-#### Inspection requested via web by Sheldon Gray
BLD18-02561 FIRE-Final Inspection10/25/201810/26/201810/26/2018 2:16:14 PMAPART
Previously noted items have been corrected, life fire safety inspection for this permit is complete. Racking permit (BLD18-03747) is issued to the tenant, life fire safety can be finaled once racking permit is completed.

Tim Phone #: ###-####-racking is in and will be anchored on Friday
FIR18-00567 INSP-Final Inspection10/25/201810/26/201810/26/2018 2:10:54 PMAPASS
Final fire sprinkler inspection for area of work complete.

RANDY Phone #: ###-#### Inspection requested via web by Nathan Stenquist
FIR18-00481 INSP-Sprinkler Rough-in10/25/201810/26/201810/26/2018 12:53:10 PMAPASS
Rough-in passed
BLD18-01269 FIRE-Final Inspection10/26/201810/26/201810/26/2018 12:46:30 PMAPASS
GFinal life fire sfatey inspection for area of work complete.

Zach Phone #: ###-####
BLD18-01055 FIRE-Final Inspection10/26/201810/26/201810/26/2018 12:42:12 PMPPASS
Life fire sfatey inspection for vanilla space associated with this permit complete.

Dereck Phone #: ###-####
FIR18-00610 INSP-Conference10/26/201810/26/201810/26/2018 12:01:21 PMPDONE
Temporary FDC is installed on the southside of building.

Temp FDC is Installed Phone #: ###-#### Inspection requested via web by Christophe Wilson
FIR18-00481 INSP-Final Inspection10/25/201810/26/201810/26/2018 12:00:18 PMAPASS
Final fire sprinkler inspection for area of work complete.

Pls call 30 mins in advance Phone #: ###-#### Inspection requested via web by Teri Cruickshank
BLD17-02377 FIRE-Final Inspection10/25/201810/26/201810/26/2018 11:48:17 AMAFAIL
Project not ready for life fire safety inspection. Associated FIR permits need to be finaled before life fire safety inspection can be completed.

Todd Phone #: ###-####
FIR18-00574 INSP-Final Inspection10/25/201810/26/201810/26/2018 11:48:17 AMAPART
Fire alarm inspection for flowswitches, tamper switches and A/V devices complete for levels 3 and 4.

Phone #: ###-#### Inspection requested via web by Matt Casey
BLD18-03009 FIRE-Final Inspection10/26/201810/26/201810/26/2018 10:17:48 AMPCANC
Please call 30 mons a head of time so I can meet you there. Phone #: ###-#### >> Inspection requested via web by Gerome Fries Inspection cancelled from web by: Gerome Fries
FIR18-00483 INSP-Final Inspection10/25/201810/26/201810/26/2018 9:14:07 AMAPASS
Final fire alarm inspection for area of work complete.

7am Phone #: ###-#### Inspection requested via web by Rick Groom