Inspections for the day of: Monday, October 28, 2019.
Number of inspections: 6
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR19-00558 INSP-Sprinkler Rough-in10/28/201910/28/201910/28/2019 2:57:00 PMPPASS
Rough to cover inspection for remaining overhead fire sprinkler piping in area of work complete, approved for cover.

Phone #: ###-#### Inspection requested via web by Matthew Lewis
FIR19-00269 INSP-Final Inspection10/28/201910/28/201910/28/2019 9:31:19 AMPPASS
Previouly noted items have bee corrected, head box not required per NFPA 13D, section 5.1.1.2, final fire sprinkler inspection is complete.

Please call Troy Nelson for inspection time. Currently the bell is working. Phone #: ###-#### Inspection requested via web by Daniel Buccino
BLD19-04155 FIRE-Final Inspection10/24/201910/28/201910/28/2019 9:29:53 AMAPASS
No fire sprinkler mdifications, no fire aalrm modifications, fire extinguisher is placed with a current inspection tag (Inspection tag expires in November). Final life fire safety inspection for area of work complete.

Christine Simon Phone #: ###-####
BLD19-04178 FIRE-Final Inspection10/25/201910/28/201910/28/2019 9:05:06 AMAFAIL
Provide signage on west door reading door to remain unlocked while building is occupied. Provide exit signage as shown on the city approved documents in the northside of the space. Door that needs to change direction of travel is going to be removed.

Call ahead to meet there // Tamara Phone #: ###-####
BLD19-03142 FIRE-Final Inspection10/27/201910/28/201910/28/2019 7:35:52 AMAFAIL
Fire alarm inspection for area of work needs to be completed before l;ife fire safety inspection can be signed off. Provide emergency lighting for exterior discharge landing as discuused on the north added doors, north east door has lighting provided.

In conjunction with Sprinkler and Alarm inspection. Phone #: ###-#### Inspection requested via web by Kirsten Dallmann
FIR19-00522 INSP-Alarm Testing10/25/201910/28/201910/28/2019 7:34:31 AMAFAIL
Sounder base and A/V devices do not sync during operation. Pull station in 180 tenant space did not operate when activated.

Needs to be done at 7:00am Phone #: ###-#### Inspection requested via web by Sam Ball