FIR19-00558
| INSP-Sprinkler Rough-in | 10/28/2019 | 10/28/2019 | 10/28/2019 2:57:00 PM | P | PASS |
|
|
Rough to cover inspection for remaining overhead fire sprinkler piping in area of work complete, approved for cover.
Phone #: ###-#### Inspection requested via web by Matthew Lewis
|
FIR19-00269
| INSP-Final Inspection | 10/28/2019 | 10/28/2019 | 10/28/2019 9:31:19 AM | P | PASS |
|
|
Previouly noted items have bee corrected, head box not required per NFPA 13D, section 5.1.1.2, final fire sprinkler inspection is complete.
Please call Troy Nelson for inspection time. Currently the bell is working. Phone #: ###-#### Inspection requested via web by Daniel Buccino
|
BLD19-04155
| FIRE-Final Inspection | 10/24/2019 | 10/28/2019 | 10/28/2019 9:29:53 AM | A | PASS |
|
|
No fire sprinkler mdifications, no fire aalrm modifications, fire extinguisher is placed with a current inspection tag (Inspection tag expires in November). Final life fire safety inspection for area of work complete.
Christine Simon Phone #: ###-####
|
BLD19-04178
| FIRE-Final Inspection | 10/25/2019 | 10/28/2019 | 10/28/2019 9:05:06 AM | A | FAIL |
|
|
Provide signage on west door reading door to remain unlocked while building is occupied. Provide exit signage as shown on the city approved documents in the northside of the space. Door that needs to change direction of travel is going to be removed.
Call ahead to meet there // Tamara Phone #: ###-####
|
BLD19-03142
| FIRE-Final Inspection | 10/27/2019 | 10/28/2019 | 10/28/2019 7:35:52 AM | A | FAIL |
|
|
Fire alarm inspection for area of work needs to be completed before l;ife fire safety inspection can be signed off. Provide emergency lighting for exterior discharge landing as discuused on the north added doors, north east door has lighting provided.
In conjunction with Sprinkler and Alarm inspection. Phone #: ###-#### Inspection requested via web by Kirsten Dallmann
|
FIR19-00522
| INSP-Alarm Testing | 10/25/2019 | 10/28/2019 | 10/28/2019 7:34:31 AM | A | FAIL |
|
|
Sounder base and A/V devices do not sync during operation. Pull station in 180 tenant space did not operate when activated.
Needs to be done at 7:00am Phone #: ###-#### Inspection requested via web by Sam Ball
|