BLD18-03009
| FIRE-Final Inspection | 10/29/2018 | 10/29/2018 | 10/29/2018 2:56:48 PM | P | PASS |
|
|
No fire sprinklers, smoke detector is stand-alone and not monitored, fire exitnguisher is placed with current inspection tag. Final life fire safety inspection for area of work complete.
Please call 30 mins ahead of time so I can meet you there. Phone #: ###-#### Inspection requested via web by Gerome Fries
|
BLD18-01760
| FIRE-Final Inspection | 10/29/2018 | 10/29/2018 | 10/29/2018 2:23:53 PM | P | PASS |
|
|
Final life fire safety inspection for area of work complete.
Derek Phone #: ###-####
|
BLD18-01760
| FIRE-Final Inspection | 10/26/2018 | 10/29/2018 | 10/29/2018 2:23:15 PM | A | CANC |
|
|
zack Phone #: ###-####
|
FIR18-00512
| INSP-Sprinkler Rough-in/Hydro | 10/29/2018 | 10/29/2018 | 10/29/2018 1:47:31 PM | P | DONE |
|
|
Hydrostatic test for undergorund supply witnessed, no pressure loss observed.
this is a underground hydro test. troy is our contact Phone #: ###-#### Inspection requested via web by Brad Bettencourt
|
BLD17-04365
| FIRE-Final Inspection | 10/29/2018 | 10/29/2018 | 10/29/2018 1:46:47 PM | P | FAIL |
|
|
City approved drawings and small documentation not on site, city approved drawings and associated small documents are required for the inspection process. Performed courtesy inspection for basic life safety items, no emergency lighting in shower/restroom area. Fire alarm modifications are required for area of work as noted in the fire conference notes entered in on 9JULY2018 under this BLD permit.
Fire alarm panel was showing a trouble at time of inspection, fire alarm panel needs to show a normal panel before life fire safety inspection.
John or ###-#### Breanna Phone #: ###-####
|
BLD18-00923
| FIRE-Final Inspection | 10/29/2018 | 10/29/2018 | 10/29/2018 11:46:03 AM | P | PASS |
|
|
Fire sprinkler inspection complete, fire alarm inspection complete, fire extinguishers are placed with current inspection tags, commercial hood fire suppression system inspection complete. Final life fire safety inspection for area of work complete.
|
FIR18-00774
| INSP-Final Inspection | 10/29/2018 | 10/29/2018 | 10/29/2018 11:44:44 AM | P | PASS |
|
|
Final fire alarm inspection for area of work complete.
Shyann Phone #: ###-####
|
FIR18-00819
| INSP-Sprinkler Rough-in | 10/29/2018 | 10/29/2018 | 10/29/2018 11:27:20 AM | P | PASS |
|
|
Rough to cover ispection for overhead fire sprinkler piping in area of work complete, approved for cover.
rick Phone #: ###-####
|
FIR18-00736
| INSP-Final Inspection | 10/29/2018 | 10/29/2018 | 10/29/2018 11:12:47 AM | A | PASS |
|
|
Final fire alarm inspection for area of work complete.
Phone #: ###-#### Inspection requested via web by Rick Groom
|
FIR18-00459
| INSP-Final Inspection | 10/29/2018 | 10/29/2018 | 10/29/2018 11:09:35 AM | P | PASS |
|
|
Final fire sprinkler inspection for scope of work complete.
rick Phone #: ###-####
|
FIR18-00636
| INSP-Sprinkler Rough-in | 10/29/2018 | 10/29/2018 | 10/29/2018 11:07:42 AM | A | PASS |
|
|
All tenting in place at time of inspection, overehad fire sprinkler piping rough in complete, overhead fire sprinkler piping approved for cover.
|
FIR18-00636
| INSP-Sprinkler Rough-in/Hydro | 10/26/2018 | 10/29/2018 | 10/29/2018 11:06:53 AM | A | DONE |
|
|
Hydrostatic test for overhead fire sprinkler piping on levels 1, 2 and 3 witnessed, no pressure loss observed at riser provided gauges. Noted that glycerin anti-freeze was used to complete hydrostatic test.
Phone #: ###-#### Inspection requested via web by Stan Beus
|
BLD18-02561
| FIRE-Final Inspection | 10/29/2018 | 10/29/2018 | 10/29/2018 11:02:41 AM | P | PASS |
|
|
Life fire safety inspection for racking permit associated with tenant complete. Final life fire safety inspection for area of work complete.
|
FIR18-00716
| INSP-Sprinkler Rough-in | 10/26/2018 | 10/29/2018 | 10/29/2018 11:01:46 AM | A | PART |
|
|
Rough to cover inspection for overhead fire sprinkler piping on levels 1 and 2 complete, levels 1 and 2 approvbed for cover. Rough in inspection for level 3 complete, tenting still needs to be installed, level 3 not approved for cover.
Phone #: ###-#### Inspection requested via web by Stan Beus
|
BLD18-03747
| FIRE-Final Inspection | 10/23/2018 | 10/29/2018 | 10/29/2018 10:04:04 AM | A | PASS |
|
|
Life fire safety inspection for racking permit complete.
brandon Phone #: ###-####
|
FIR18-00737
| INSP-Final Inspection | 10/29/2018 | 10/29/2018 | 10/29/2018 8:54:22 AM | A | PASS |
|
|
Final fire alarm inspection for area of work complete.
Phone #: ###-#### Inspection requested via web by Rick Groom
|
FIR18-00774
| INSP-Final Inspection | 10/26/2018 | 10/29/2018 | 10/29/2018 8:53:44 AM | A | FAIL |
|
|
Called phone number provided two times between 0820 and 0845, received a messgae stated it was outside of normal business hours. Inspection request will need to be rescheduled.
Shyann Phone #: ###-####
|
BLD18-01325
| FIRE-Final Inspection | 10/26/2018 | 10/29/2018 | 10/29/2018 7:42:58 AM | A | PASS |
|
|
Final life fire safety inspection for area of work complete.
Rick Phone #: ###-####
|