FIR18-00067
| INSP-Final Inspection | 10/28/2019 | 10/29/2019 | 10/29/2019 3:29:15 PM | P | PASS |
|
|
Final inspection for scope of work is complete.
We would like to discuss the final for this work. Please call Cameron with questions. Phone #: ###-#### Inspection requested via web by Jeff Packham
|
BLD19-03060
| FIRE-Final Inspection | 10/28/2019 | 10/29/2019 | 10/29/2019 3:06:39 PM | P | FAIL |
|
|
Emergency lighting does not match the city approved drawings. FIR permit for fire sprinkler in office remodel area needs to be finaled before TCO.
Final inspection for TCO, fire life inspection Phone #: ###-#### Inspection requested via web by Mark Coiner
|
BLD19-02167
| FIRE-Final Inspection | 10/28/2019 | 10/29/2019 | 10/29/2019 10:54:04 AM | A | PASS |
|
|
No fire sprinklers, no fire alarms, fire extinguisher is placed with a current inspection tag. Final life fire safety inspection for area of work complete.
call when on the way // An Phone #: ###-####
|
FIR19-00111
| INSP-Final Inspection | 10/28/2019 | 10/29/2019 | 10/29/2019 10:46:23 AM | A | FAIL |
|
|
Install missing head in entry room 101, heads in kitchen area overspaced off of wall room 101. head painted in room 102, sprinkler head to close to ceiling fan room 102. Missing escutcheon on balcony, room 103. Sprinkler head to close to ceiling fan room 104. sidewall deflector above wood beam room 202 balcony, head sticking to far down through ceiling room 202. Inspection stopped due to defecincies.
Contact Noemi Carrero ###-#### 30 min prior to Final Insp start please.
Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
|
BLD19-04183
| FIRE-Final Inspection | 10/29/2019 | 10/29/2019 | 10/29/2019 9:45:01 AM | A | PASS |
|
|
No fire sprinkler modifications, no fire alarm modifications, fire extinguisher is placed with a current inspection tag. Final life fire safety inspection complete.
|
BLD18-03655
| FIRE-Final Inspection | 10/28/2019 | 10/29/2019 | 10/29/2019 9:29:40 AM | A | PASS |
|
|
No fire sprinklers, no fire alarms, fire extinguishers are placed with current inspection tags. Final life fire safety inspection for scope of work complete, permenant addressing to be installed when received.
Phone #: ###-#### Inspection requested via web by Jimmy Martin
|
BLD18-03640
| FIRE-Final Inspection | 10/28/2019 | 10/29/2019 | 10/29/2019 9:29:14 AM | A | PASS |
|
|
No fire sprinklers, no fire alarms, fire extinguishers are placed with current inspection tags. Final life fire safety inspection for scope of work complete, permenant addressing to be installed when received.
Phone #: ###-#### Inspection requested via web by Jimmy Martin
|
BLD18-03654
| FIRE-Final Inspection | 10/28/2019 | 10/29/2019 | 10/29/2019 9:28:54 AM | A | PASS |
|
|
No fire sprinklers, no fire alarms, fire extinguishers are placed with current inspection tags. Final life fire safety inspection for scope of work complete, permenant addressing to be installed when received.
Phone #: ###-#### Inspection requested via web by Jimmy Martin
|
BLD18-03649
| FIRE-Final Inspection | 10/28/2019 | 10/29/2019 | 10/29/2019 9:28:31 AM | A | PASS |
|
|
No fire sprinklers, no fire alarms, fire extinguishers are placed with current inspection tags. Final life fire safety inspection for scope of work complete, permenant addressing to be installed when received.
Phone #: ###-#### Inspection requested via web by Jimmy Martin
|
BLD19-04183
| FIRE-Final Inspection | 10/22/2019 | 10/29/2019 | 10/29/2019 9:15:12 AM | A | FAIL |
|
|
Called point of contact provided at 8:57AM, left a message stating that if I did not hear back from point of contact by 9:15 then I will procceed to next inspection, no return call was received by 9:15, a reschedule for life fire safety inspection will need to be requested.
TAMMI Phone #: ###-####
|
FIR19-00751
| INSP-Sprinkler Rough-in | 10/28/2019 | 10/29/2019 | 10/29/2019 8:57:05 AM | A | PART |
|
|
Rough to cover inspection for overhead fire sprinkler piping above hardlids complete, hardlids approved for cover, areas approved for cover have been notated with red ink on city approved drawings on site.
Rick Phone #: ###-####
|
BLD19-04177
| FIRE-Final Inspection | 10/28/2019 | 10/29/2019 | 10/29/2019 8:33:35 AM | A | FAIL |
|
|
Cooler has been removed, dry pendant sprinkler head is still in place, fire sprinkler head needs to be removed, a seperate FIR permit is required for fire sprinkler modifications. Provide annual inspection for fire extinguisher, current tag expires in 3 days from day of life fire safety inspection. Provide signage on the main entry with correct wording reading "Door to remain unlocked while building is occupied".
call ahead - Kelly Phone #: ###-####
|
FIR19-00522
| INSP-Alarm Testing | 10/28/2019 | 10/29/2019 | 10/28/2019 2:29:54 PM | A | CANC |
|
|
Needs to be done at 7:00am Phone #: ###-#### >> Inspection requested via web by Sam Ball Inspection cancelled from web by: Sam Ball
|