Inspections for the day of: Tuesday, October 29, 2019.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR18-00067 INSP-Final Inspection10/28/201910/29/201910/29/2019 3:29:15 PMPPASS
Final inspection for scope of work is complete.

We would like to discuss the final for this work. Please call Cameron with questions. Phone #: ###-#### Inspection requested via web by Jeff Packham
BLD19-03060 FIRE-Final Inspection10/28/201910/29/201910/29/2019 3:06:39 PMPFAIL
Emergency lighting does not match the city approved drawings. FIR permit for fire sprinkler in office remodel area needs to be finaled before TCO.

Final inspection for TCO, fire life inspection Phone #: ###-#### Inspection requested via web by Mark Coiner
BLD19-02167 FIRE-Final Inspection10/28/201910/29/201910/29/2019 10:54:04 AMAPASS
No fire sprinklers, no fire alarms, fire extinguisher is placed with a current inspection tag. Final life fire safety inspection for area of work complete.

call when on the way // An Phone #: ###-####
FIR19-00111 INSP-Final Inspection10/28/201910/29/201910/29/2019 10:46:23 AMAFAIL
Install missing head in entry room 101, heads in kitchen area overspaced off of wall room 101. head painted in room 102, sprinkler head to close to ceiling fan room 102. Missing escutcheon on balcony, room 103. Sprinkler head to close to ceiling fan room 104. sidewall deflector above wood beam room 202 balcony, head sticking to far down through ceiling room 202. Inspection stopped due to defecincies.

Contact Noemi Carrero ###-#### 30 min prior to Final Insp start please.

Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
BLD19-04183 FIRE-Final Inspection10/29/201910/29/201910/29/2019 9:45:01 AMAPASS
No fire sprinkler modifications, no fire alarm modifications, fire extinguisher is placed with a current inspection tag. Final life fire safety inspection complete.
BLD18-03655 FIRE-Final Inspection10/28/201910/29/201910/29/2019 9:29:40 AMAPASS
No fire sprinklers, no fire alarms, fire extinguishers are placed with current inspection tags. Final life fire safety inspection for scope of work complete, permenant addressing to be installed when received.

Phone #: ###-#### Inspection requested via web by Jimmy Martin
BLD18-03640 FIRE-Final Inspection10/28/201910/29/201910/29/2019 9:29:14 AMAPASS
No fire sprinklers, no fire alarms, fire extinguishers are placed with current inspection tags. Final life fire safety inspection for scope of work complete, permenant addressing to be installed when received.

Phone #: ###-#### Inspection requested via web by Jimmy Martin
BLD18-03654 FIRE-Final Inspection10/28/201910/29/201910/29/2019 9:28:54 AMAPASS
No fire sprinklers, no fire alarms, fire extinguishers are placed with current inspection tags. Final life fire safety inspection for scope of work complete, permenant addressing to be installed when received.

Phone #: ###-#### Inspection requested via web by Jimmy Martin
BLD18-03649 FIRE-Final Inspection10/28/201910/29/201910/29/2019 9:28:31 AMAPASS
No fire sprinklers, no fire alarms, fire extinguishers are placed with current inspection tags. Final life fire safety inspection for scope of work complete, permenant addressing to be installed when received.

Phone #: ###-#### Inspection requested via web by Jimmy Martin
BLD19-04183 FIRE-Final Inspection10/22/201910/29/201910/29/2019 9:15:12 AMAFAIL
Called point of contact provided at 8:57AM, left a message stating that if I did not hear back from point of contact by 9:15 then I will procceed to next inspection, no return call was received by 9:15, a reschedule for life fire safety inspection will need to be requested.

TAMMI Phone #: ###-####
FIR19-00751 INSP-Sprinkler Rough-in10/28/201910/29/201910/29/2019 8:57:05 AMAPART
Rough to cover inspection for overhead fire sprinkler piping above hardlids complete, hardlids approved for cover, areas approved for cover have been notated with red ink on city approved drawings on site.

Rick Phone #: ###-####
BLD19-04177 FIRE-Final Inspection10/28/201910/29/201910/29/2019 8:33:35 AMAFAIL
Cooler has been removed, dry pendant sprinkler head is still in place, fire sprinkler head needs to be removed, a seperate FIR permit is required for fire sprinkler modifications. Provide annual inspection for fire extinguisher, current tag expires in 3 days from day of life fire safety inspection. Provide signage on the main entry with correct wording reading "Door to remain unlocked while building is occupied".

call ahead - Kelly Phone #: ###-####
FIR19-00522 INSP-Alarm Testing10/28/201910/29/201910/28/2019 2:29:54 PMACANC
Needs to be done at 7:00am Phone #: ###-#### >> Inspection requested via web by Sam Ball Inspection cancelled from web by: Sam Ball