Inspections for the day of: Tuesday, November 12, 2019.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD19-03560 FIRE-Final Inspection11/8/201911/12/201911/12/2019 11:11:21 AMAPASS
No fire sprinklers, no fire alarms, hood suppression system inspection is current with no modifications, fire exitnguishers are placed with current inspection tags. Final life fire safety inspection complete, signature provided on signature card.

Elena Phone #: ###-####
FIR19-00419 INSP-Sprinkler Rough-in11/8/201911/12/201911/12/2019 10:47:36 AMAPASS
Rough to cover inspection for overhead fire sprinkler piping in area of work complete, approved for cover.

Phone #: ###-#### Inspection requested via web by Sam Ball
BLD19-04294 FIRE-Final Inspection11/8/201911/12/201911/12/2019 10:36:35 AMAPASS
Previously noted items have been corrected, no fire sprinkler, no fire alarms, fire exitnguishers are placed with current inspection tags. Final life fire safety inspection for area of work complete.

Salam Phone #: ###-####
FIR19-00679 INSP-Sprinkler Rough-in11/11/201911/12/201911/12/2019 10:24:16 AMPCANC
Per conversation with installing contractor, this is a duplicate inspection request, this request is cancelled.

Phone #: ###-#### Inspection requested via web by Sam Ball
FIR19-00679 INSP-Sprinkler Rough-in11/8/201911/12/201911/12/2019 10:22:10 AMAPART
Rough to cover inspection for overhead fire sprinkler piping in area of work is complete, approved for cover. City approved drawings points out a room that does not have a ceiling, no ceiling was installed at time of inspection. As stated on the city approved draiwngs if walls do not go all the way to the deck then that area will need to comply with 2016 NFPA 13 section 18.15.23.

If sprinkler heads are added due to the walls not going all the way to the deck then ceiling tiles will need to be removed to verify upright fire sprinkler addition to comply with NFPA 13.

Phone #: ###-#### Inspection requested via web by Sam Ball
BLD19-01638 FIRE-Final Inspection11/8/201911/12/201911/12/2019 9:38:48 AMAFAIL
Provided fire alarm modifications as discussed, a seperate per it is required for fire aalrm modifications.

TJ Phone #: ###-####
FIR19-00826 INSP-Final Inspection11/8/201911/12/201911/12/2019 9:17:13 AMAPASS
Final fire sprinkler inspection for scope of work complete.

Jeff Phone #: ###-####
FIR19-00826 INSP-Sprinkler Rough-in11/8/201911/12/201911/12/2019 9:16:27 AMAPASS
Rough to cover inspection for area of work complete, approved for cover.

Jeff Phone #: ###-####
FIR19-00634 INSP-Final Inspection11/7/201911/12/201911/12/2019 9:14:49 AMPCANC
We would like this inspection performed after 1:30 pm per the occupant''s request. Please call Nate at ###-#### with inspection time. Phone #: ###-#### >> Inspection requested via web by Lori Brungardt Inspection cancelled from web by: Lori Brungardt