BLD18-01550
| FIRE-Final Inspection | 11/16/2018 | 11/19/2018 | 11/19/2018 2:01:44 PM | P | FAIL |
|
|
Fire sprinkler permit is required for modifications to the fire sprinklers system, fire sprinklers are overspaced in area of work.
Rick Phone #: ###-####
|
BLD18-01933
| FIRE-Final Inspection | 11/19/2018 | 11/19/2018 | 11/19/2018 12:54:59 PM | P | PASS |
|
|
Previously noted items have been corrected, final life fire safety inspection complete.
Clinton Phone #: ###-####
|
BLD18-01746
| FIRE-Final Inspection | 11/19/2018 | 11/19/2018 | 11/19/2018 12:36:10 PM | P | FAIL |
|
|
Fire sprinkler heads by island/sink in breakroom ltchen area are less tha 6 feet abart, a minimum of 6 feet betwwen heads is required by code. Escutcheons need to be installed on the heads in the entry way to include cover of piping and holes for the fire sprinkler heads.
Larren Phone #: ###-####
|
BLD18-00803
| FIRE-Final Inspection | 11/16/2018 | 11/19/2018 | 11/19/2018 12:22:32 PM | P | FAIL |
|
|
No fire alarm inspection or testings has been completed for area of work, an inspection for FIR18-00740 needs to be scheduled and passed before life fire safety inspection can be completed.
Kevin Phone #: ###-####
|
FIR18-00673
| INSP-Sprinkler Rough-in/Hydro | 11/16/2018 | 11/19/2018 | 11/19/2018 11:08:14 AM | A | FAIL |
|
|
Sway bracing attachments need to be a minimum of a 4X, attachments for attic mains are attached to 2X4, not a 4X4 or larger. Fix blocked head as noted. Move hangers that are to close to the attic heads.
Phone #: ###-#### Inspection requested via web by Shane Lesteberg
|
FIR18-00868
| INSP-Final Inspection | 11/19/2018 | 11/19/2018 | 11/19/2018 10:35:46 AM | P | PASS |
|
|
Final fire sprinkler inspection for area of work complete.
Adam Phone #: ###-#### Inspection requested via web by Nathan Stenquist
|
BLD18-03972
| FIRE-Final Inspection | 11/16/2018 | 11/19/2018 | 11/19/2018 9:31:40 AM | A | PASS |
|
|
No fire sprinkler modifications (fire sprinkler annual inspection is current), no fire alarm modifications, fire extinguishers are placed with current ins[pection tags. Addressing needs to be installed before BLD permit final. Final life fire safety inspection for area of work complete.
Scott-please call 30 minutes prior to meet Phone #: ###-####
|
BLD17-04686
| FIRE-Conference | 11/19/2018 | 11/19/2018 | 11/19/2018 9:01:33 AM | A | DONE |
|
|
Signage discussed for pruposed TCO, temporary signage can be used if a TCO is aggress upon, permenant signage needs to be in place for final C of O.
|
BLD17-04686
| FIRE-Final Inspection | 11/16/2018 | 11/19/2018 | 11/19/2018 8:59:16 AM | A | CANC |
|
|
Request is for a conference, not a final. This request is cancelled.
Tyler Phone #: ###-####
|