Inspections for the day of: Monday, November 19, 2018.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD18-01550 FIRE-Final Inspection11/16/201811/19/201811/19/2018 2:01:44 PMPFAIL
Fire sprinkler permit is required for modifications to the fire sprinklers system, fire sprinklers are overspaced in area of work.



Rick Phone #: ###-####
BLD18-01933 FIRE-Final Inspection11/19/201811/19/201811/19/2018 12:54:59 PMPPASS
Previously noted items have been corrected, final life fire safety inspection complete.

Clinton Phone #: ###-####
BLD18-01746 FIRE-Final Inspection11/19/201811/19/201811/19/2018 12:36:10 PMPFAIL
Fire sprinkler heads by island/sink in breakroom ltchen area are less tha 6 feet abart, a minimum of 6 feet betwwen heads is required by code. Escutcheons need to be installed on the heads in the entry way to include cover of piping and holes for the fire sprinkler heads.

Larren Phone #: ###-####
BLD18-00803 FIRE-Final Inspection11/16/201811/19/201811/19/2018 12:22:32 PMPFAIL
No fire alarm inspection or testings has been completed for area of work, an inspection for FIR18-00740 needs to be scheduled and passed before life fire safety inspection can be completed.

Kevin Phone #: ###-####
FIR18-00673 INSP-Sprinkler Rough-in/Hydro11/16/201811/19/201811/19/2018 11:08:14 AMAFAIL
Sway bracing attachments need to be a minimum of a 4X, attachments for attic mains are attached to 2X4, not a 4X4 or larger. Fix blocked head as noted. Move hangers that are to close to the attic heads.

Phone #: ###-#### Inspection requested via web by Shane Lesteberg
FIR18-00868 INSP-Final Inspection11/19/201811/19/201811/19/2018 10:35:46 AMPPASS
Final fire sprinkler inspection for area of work complete.

Adam Phone #: ###-#### Inspection requested via web by Nathan Stenquist
BLD18-03972 FIRE-Final Inspection11/16/201811/19/201811/19/2018 9:31:40 AMAPASS
No fire sprinkler modifications (fire sprinkler annual inspection is current), no fire alarm modifications, fire extinguishers are placed with current ins[pection tags. Addressing needs to be installed before BLD permit final. Final life fire safety inspection for area of work complete.

Scott-please call 30 minutes prior to meet Phone #: ###-####
BLD17-04686 FIRE-Conference11/19/201811/19/201811/19/2018 9:01:33 AMADONE
Signage discussed for pruposed TCO, temporary signage can be used if a TCO is aggress upon, permenant signage needs to be in place for final C of O.
BLD17-04686 FIRE-Final Inspection11/16/201811/19/201811/19/2018 8:59:16 AMACANC
Request is for a conference, not a final. This request is cancelled.

Tyler Phone #: ###-####