BLD19-04311
| FIRE-Final Inspection | 11/18/2019 | 11/19/2019 | 11/19/2019 2:39:05 PM | P | PASS |
|
|
No fire sprinklers, no fire alarms, fire extinguishers are placed and will be inspected as discussed. Final life fire safety inspection complete, signature provided on permit sign off card.
Shannon Phone #: ###-####
|
BLD19-00314
| FIRE-Final Inspection | 11/18/2019 | 11/19/2019 | 11/19/2019 2:11:40 PM | P | PASS |
|
|
No fire sprinklers, no fire alarms, fire extinguishers are placed with current inspection tags. Final life fire safety inspection for this scope of work complete, signature provided on permit sign off card.
Phone #: ###-#### Inspection requested via web by chad stradley
|
FIR19-00703
| INSP-Sprinkler Rough-in | 11/19/2019 | 11/19/2019 | 11/19/2019 1:48:22 PM | P | PART |
|
|
Rough to cover inspection for overhead fire sprinkler piping above hardlids in scope of work complete, hardlids approved for cover.
Mike Phone #: ###-####
|
BLD19-01329
| FIRE-Final Inspection | 11/19/2019 | 11/19/2019 | 11/19/2019 1:14:18 PM | P | PASS |
|
|
no fire sprinkler modifications, fire alarm inspection is complete, fire extinguishers are placed with current inspection tags. Final life fire safety inspection for area of work complete.
Alex Phone #: ###-####
|
BLD19-04493
| FIRE-Final Inspection | 11/18/2019 | 11/19/2019 | 11/19/2019 12:36:07 PM | A | FAIL |
|
|
Service exit lights as dicussed. Provide and place fire extinguisher with a current inspection tag as discussed.
call for access code // Tara Phone #: ###-####
|
FIR19-00766
| INSP-Sprinkler Rough-in | 11/18/2019 | 11/19/2019 | 11/19/2019 11:32:41 AM | A | FAIL |
|
|
Tenting not installed correctly in numerous places, blow in insulation will get inot required pocket between sheetrock and piping. Sidewall heads in the in-law suite are more than 36 inches down from the peak. Freeze protection for vertical pipe in attic spaces is not adequate, relocate piping for correct freeze protection as discussed or provide heat calculations for install to meet the minimum requirement. No cover is approved.
Contact Perly Daniel ###-#### 30 min prior to RTC insp start please.
Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
|
FIR19-00810
| INSP-Sprinkler Rough-in | 11/18/2019 | 11/19/2019 | 11/19/2019 10:58:00 AM | A | PASS |
|
|
Rough to cover inspection for overhead fire sprinkler piping in area of work complete, approved for cover.
Phone #: ###-#### Inspection requested via web by Sam Ball
|
FIR19-00611
| INSP-Final Inspection | 11/18/2019 | 11/19/2019 | 11/19/2019 10:34:18 AM | A | PASS |
|
|
Final fire alarm inspection for scope of work comlpete.
Phone #: 2088990672 >> Inspection requested via mobile web by Josiah
|
BLD18-01491
| FIRE-Final Inspection | 11/19/2019 | 11/19/2019 | 11/19/2019 9:59:49 AM | P | FAIL |
|
|
Site work for fire truck access is not complete, fire truck access must be complete before life fire safety can be signed off per note number 1 of building permit fire code review. Provide signage for fire sprinkler riser room as well as fire alarm control panel per note number 14. Provide address numbers on both east and south sides per boise municipal code 505.3. Fire sprinkler system requires a re-hydro due to the amount of corrections that were made.
Mark - Fire/Life Safety. Working with sprinkler contractor to get inspection for FIR19-00111 this afternoon as well. Phone #: ###-####
|
FIR19-00593
| INSP-Final Inspection | 11/19/2019 | 11/19/2019 | 11/19/2019 9:39:28 AM | A | FAIL |
|
|
Provide sigange for fire bell. Wiring for irrigation shutdown not installed correctly, irrigation will not shut down during waterflow.
Call before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
BLD18-01031
| FIRE-Final Inspection | 11/18/2019 | 11/19/2019 | 11/19/2019 9:23:26 AM | P | PASS |
|
|
Previously noted items have been corrected, final life fire safety inspection for area of work complete.
Randy Phone #: ###-####
|
FIR19-00601
| INSP-Sprinkler Rough-in | 11/19/2019 | 11/19/2019 | 11/19/2019 9:22:29 AM | A | FAIL |
|
|
Install on level 1 does not match city approved drawings, inspection was stopped half way through level 1.
Call before heading out, rough and tenting. Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
FIR19-00808
| INSP-Final Inspection | 11/19/2019 | 11/19/2019 | 11/19/2019 8:56:41 AM | A | PASS |
|
|
Final fire sprinkler inspection for area of work complete.
|
FIR19-00808
| INSP-Sprinkler Rough-in | 11/18/2019 | 11/19/2019 | 11/19/2019 8:55:33 AM | A | PASS |
|
|
Rough to cover inspection for overhead fire sprinkler piping in area of work complete, approved for cover, flex drops were used in original install, flex drops are in place.
Please Call Rick Fouts 1 hour prior to heading to the job site at Phone #: ###-#### Inspection requested via web by Matt Barnard
|
FIR19-00843
| INSP-Final Inspection | 11/18/2019 | 11/19/2019 | 11/19/2019 8:21:10 AM | A | PASS |
|
|
Final fire sprinkler inspection for area of work complete.
Contact Tanner Loomis ###-#### 30 min prior to Fire Final Insp Start please.
Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
|
FIR19-00066
| INSP-Final Inspection | 11/18/2019 | 11/19/2019 | 11/18/2019 12:19:28 PM | A | CANC |
|
|
Please contact Buck for Inspection. Phone #: ###-#### >> Inspection requested via web by Ken Webster Inspection cancelled from web by: Ken Webster
|