FIR19-00634
| INSP-Final Inspection | 11/19/2019 | 11/21/2019 | 11/21/2019 4:09:20 PM | P | FAIL |
|
|
Corridor spacing for smoke detection as well as audio visual notification for this project does not apply to most areas, numerous office walls shown on city approved drawings are half walls, smoke detection and audio visual notification will need to corrected, a plan mod will be required beofre next inspection. Notated city approved drawings with red ink areas where smoke detection is overspaced, a smoke detector is not installed that is city approved drawings as well as A/V notification that is overspaced, all areas of building fire alarm system were inspected. Inspection was stopped due to deficiencies noted. No initiating devices or A/V devices were tested.
We would like this inspection to be performed at 2:00 PM per the occupant''s request. Please call Nate at ###-#### with inspection time. Phone #: ###-#### Inspection requested via web by Lori Brungardt
|
BLD19-02841
| FIRE-Final Inspection | 11/20/2019 | 11/21/2019 | 11/21/2019 1:48:57 PM | P | PASS |
|
|
Fire sprinkler inspection for area of work complete, fire aalrm inspection for area of work is complete, fire extinguishers are placed with current inspection tags. Final life fire safety inspection for area of work complete, signature card not availabe at time of inspection.
Later in the afternoon if possible. Please call me ahead of time so I am available, tenant is moving in furniture. This is for Temp Occupancy only - Inspection was done with previous permit BLD19-03142. Phone #: ###-#### Inspection requested via web by Kirsten Dallmann
|
BLD19-03468
| FIRE-Final Inspection | 11/19/2019 | 11/21/2019 | 11/21/2019 1:45:27 PM | A | PASS |
|
|
Fire sprinkler inspection is complete, no fire alarm modifications, fire extinguishers are placed with current inspection tags. Final life fire safety inspection for area of work complete, signatures provided on permit card for associated trades.
David Phone #: ###-####
|
BLD18-00005
| FIRE-Final Inspection | 11/20/2019 | 11/21/2019 | 11/21/2019 1:27:51 PM | P | PASS |
|
|
No fire sprinklers, smoke detectors placed and are not monitored stand-alone type, fire extinguishers are placed under kitchen sinks and will be inspected as discussed. Final life fire safety inspection for scope of work complete.
Stan Phone #: ###-####
|
FIR19-00694
| INSP-Final Inspection | 11/21/2019 | 11/21/2019 | 11/21/2019 1:27:51 PM | P | PASS |
|
|
Final fire aalrm inspection complete.
Call prior to going Phone #: 2086810381 >> Inspection requested via mobile web by Doug Lessa
|
FIR19-00536
| INSP-Final Inspection | 11/20/2019 | 11/21/2019 | 11/21/2019 1:27:50 PM | P | PASS |
|
|
Final fire sprinkler inspection is complete.
Cameron Phone #: ###-#### Inspection requested via web by Jeanine Halbesleben
|
BLD19-00727
| FIRE-Final Inspection | 11/21/2019 | 11/21/2019 | 11/21/2019 11:02:40 AM | P | FAIL |
|
|
Mag lock interface with fire alarm system has not been completed, as stated in past inspection on 13SEPT2019, mag locks on egress doors need to release during general fire per international fire code.
Travis Phone #: ###-####
|
BLD19-04012
| FIRE-Final Inspection | 11/21/2019 | 11/21/2019 | 11/21/2019 10:57:13 AM | P | FAIL |
|
|
Provide code compliant door hardware throughout space, current door hardware thoughout space is round type door hardware. Area of work requires fire alarm modifications, a seperate fire alarm permit will be required for area of work.
Zach Phone #: ###-####
|
BLD18-01083
| FIRE-Final Inspection | 11/21/2019 | 11/21/2019 | 11/21/2019 10:49:35 AM | P | FAIL |
|
|
Door 111 is designated as an exit door with path of travel going from cooler to office area, door 111 needs to swing with the path of travel, door swing needs to be changed, no other items inspected for life fire safety.
call 30 mins ahead please- Mike Phone #: ###-####
|
FIR19-00794
| INSP-Sprinkler Rough-in | 11/20/2019 | 11/21/2019 | 11/21/2019 10:37:26 AM | A | PASS |
|
|
Rough to cover inspection for overhead fire sprinkler piping in area of work complete, approved for cover.
Patin Phone #: ###-####
|
FIR19-00795
| INSP-Final Inspection | 11/19/2019 | 11/21/2019 | 11/21/2019 10:19:56 AM | A | PASS |
|
|
Final fire sprinkler inspection for scope of work complete.
Rick Fry to coincide with the fire/life safety final Phone #: ###-#### Inspection requested via web by Brodie Stenquist
|
FIR19-00066
| INSP-Final Inspection | 11/21/2019 | 11/21/2019 | 11/21/2019 9:51:29 AM | A | PART |
|
|
Partial final complete for fire alarm inspection. Initiating devices and audio visual devices tested, last item to test will be FDC bell after install.
Phone #: ###-#### Inspection requested via web by Ken Webster
|
BLD19-04493
| FIRE-Final Inspection | 11/20/2019 | 11/21/2019 | 11/21/2019 9:49:53 AM | A | PASS |
|
|
Previously noted items have been corrected, no fire sprinklers, no fire nalarms, fire extinguisher is placed with a current inspection tag. Final life fire safety inspection for temp occupancy complete.
call for code for access- Tara Phone #: ###-####
|