Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD19-02562 FIRE-Final Inspection11/25/201911/25/201911/25/2019 3:36:44 PMPPASS
Previously noted items have been corrected, final life fire safety inspection for area of work complete.

Rob Phone #: ###-####
BLD19-04620 FIRE-Final Inspection11/25/201911/25/201911/25/2019 12:51:55 PMPPASS
No fire sprinkler modificaitons, no fire alarm modifications, fire extinguisher is placed with a current inspection tag, signage to be placed at main entry reading "Door to remain unlocked while building is occupied" as discussed. Final life fire safety inspection for area of work complete, signatures provided for associated trades on permit sign off card.

Matt Phone #: ###-####
FIR19-00766 INSP-Sprinkler Rough-in11/25/201911/25/201911/25/2019 12:28:56 PMPFAIL
Areas of concern for tenting were shown to the point of contact during last inspection, tenting still is not correct, no cover is approved.

Contact Perly Daniel ###-#### 30 min prior to RTC Insp start please,

Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
FIR19-00721 INSP-Final Inspection11/25/201911/25/201911/25/2019 9:26:03 AMPCANC
Cancelled per conversation with point of contact, inspection will be rescheduled for a later date.

Rick Phone #: ###-####
FIR19-00394 INSP-Final Inspection11/22/201911/25/201911/25/2019 8:57:52 AMACANC
Permit has been finaled in 22NOV2019.

UG inspections are complete. Flush completed on overhead permit. Please call Jeff with questions.

Thanks Phone #: ###-#### Inspection requested via web by Jeff Packham
FIR19-00867 INSP-Sprinkler Rough-in11/25/201911/25/201911/25/2019 8:57:17 AMAFAIL
Underground not installed at timne of inspection.

Call before heading out, underground rough to bury (hydro in warm weather or closer to final) Phone #: ###-#### Inspection requested via web by Anthony Minichiello
FIR19-00869 INSP-Sprinkler Rough-in11/25/201911/25/201911/25/2019 8:56:45 AMAFAIL
Bury depth of 54 inches to top of pipe not met. Attach bury wire to pipe, cover is not approved.

Call before heading out, underground rough to bury (hydro in warm weather or closer to final) Phone #: ###-#### Inspection requested via web by Anthony Minichiello
FIR19-00870 INSP-Sprinkler Rough-in11/25/201911/25/201911/25/2019 8:56:25 AMAFAIL
Bury depth of 54 inches to top of pipe not met. Attach bury wire to pipe, cover is not approved.

Call before heading out, underground rough to bury (hydro in warm weather or closer to final) Phone #: ###-#### Inspection requested via web by Anthony Minichiello
FIR19-00864 INSP-Sprinkler Rough-in11/25/201911/25/201911/25/2019 8:56:05 AMAFAIL
Underground not installed at time of inspection.

Call before heading out, underground rough to bury (hydro in warm weather or closer to final) Phone #: ###-#### Inspection requested via web by Anthony Minichiello
FIR19-00871 INSP-Sprinkler Rough-in11/25/201911/25/201911/25/2019 8:54:51 AMAFAIL
Bury depth of 54 inches to top of pipe not met. Attach bury wire to pipe, cover is not approved.

Call before heading out, underground rough to bury (hydro in warm weather or closer to final) Phone #: ###-#### Inspection requested via web by Anthony Minichiello
FIR19-00872 INSP-Sprinkler Rough-in11/25/201911/25/201911/25/2019 8:54:28 AMAFAIL
Bury depth of 54 inches to top of pipe not met. Attach bury wire to pipe, cover is not approved.

Call before heading out, underground rough to bury (hydro in warm weather or closer to final) Phone #: ###-#### Inspection requested via web by Anthony Minichiello