Inspections for the day of: Friday, November 8, 2019.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR19-00712 INSP-Sprinkler Rough-in/Hydro11/8/201911/8/201911/8/2019 3:52:50 PMPPASS
Hydrostatic test for overhead fire sprinkler piping witnessed, no pressure loss observed.

Phone #: ###-#### Inspection requested via web by Sam Ball
FIR19-00712 INSP-Sprinkler Rough-in/Hydro11/8/201911/8/201911/8/2019 3:52:16 PMPPASS
Rough to cover/rough in inspection for overhead fire sprinkler piping in scope of work complete, approved for cover.

Phone #: ###-#### Inspection requested via web by Sam Ball
FIR19-00829 INSP-Sprinkler Rough-in11/8/201911/8/201911/8/2019 3:45:57 PMPPASS
Rough to cover inspection for overhead fire sprinkler piping in area of work complete, approved for cover.

Phone #: ###-#### Inspection requested via web by Sam Ball
BLD19-04379 FIRE-Final Inspection11/8/201911/8/201911/8/2019 2:27:34 PMPPASS
Previously noted items have been corrected, exit sign has been removed as discussed. No fire sprinklers, no fire alarms, fire extinguisher is mounted with current inspection tag. Final life fire safety inspection for area of work complete.

kyle Phone #: ###-####
BLD19-03314 FIRE-Final Inspection11/6/201911/8/201911/8/2019 2:11:07 PMAFAIL
Provide fire extinguisher for level 2 residential area, extinguisher can be placed under kitchen sink as discussed. A monitored smoke detector is installed on the B occupancy side of the building, per conversation with Lee Meridith, Fire Alarm Plan Reviewer, the fire alarm system is not required due to type of occupancy, if fire alarm system stays in place then a seperate FIR permit and fire alarm review is required.

dUSTY-if possible call 30 min ahead (WAS INFROM THAT THIS IS NOT GUARANTEED) Phone #: ###-####
FIR19-00536 INSP-Sprinkler Rough-in11/8/201911/8/201911/8/2019 2:04:45 PMPPASS
Rough to cover inspection for east and west corridors and kitchen area complete, heads have been added in the combustible concealed spaces as discussed, approved for cover.
FIR19-00536 INSP-Sprinkler Rough-in/Hydro11/8/201911/8/201911/8/2019 2:03:23 PMPDONE
Hydrostatic test for overhead fire sprinkler piping witnessed, no pressure loss observed.

John Phone #: ###-####
FIR19-00396 INSP-Sprinkler Rough-in11/7/201911/8/201911/8/2019 1:18:41 PMPPASS
Rough to cover inspection for overhead fire sprinkler piping in area of work complete, approved for cover.

Phone #: ###-#### Inspection requested via web by Sam Ball
BLD19-01312 FIRE-Final Inspection11/7/201911/8/201911/8/2019 12:04:57 PMAFAIL
Architectural feature at bottom of escalator is not installed, fire sprinkler head is to far down from deck, feature needs to be in place for final sign off. Need a fire alarm vendor available to test fire alarm system as discussed as verbally discussed, audio visual devices were removed and re-installed during project, need to verify operation.

Tom Phone #: ###-####
FIR19-00562 INSP-Final Inspection11/7/201911/8/201911/8/2019 12:01:01 PMANR
Area of work is not complete, finish item at bottom of escalator not in place, sprinkler head is to far down from deck without finsh material installed, project not ready for final inspection.

Rick Phone #: ###-####
FIR19-00812 INSP-Final Inspection11/8/201911/8/201911/8/2019 10:13:50 AMPPASS
Final fire alarm inspection for area of work complete.

Phone #: ###-#### Inspection requested via web by Kristin Dolan
FIR19-00551 INSP-Sprinkler Rough-in11/7/201911/8/201911/8/2019 9:47:13 AMAPASS
All tenting in place at time of inspection, cover approved for overhead fire sprinkler piping.

Robert Chambers is the field contact. Thanks for all you do! Phone #: ###-#### Inspection requested via web by Stan Beus