FIR18-00832
| INSP-Final Inspection | 12/10/2018 | 12/11/2018 | 12/11/2018 3:55:35 PM | P | PASS |
|
|
Final fire sprinkler inspection for area of work complete.
Rick Phone #: ###-####
|
FIR18-00836
| INSP-Final Inspection | 12/6/2018 | 12/11/2018 | 12/11/2018 3:05:20 PM | P | PASS |
|
|
Final fire alarm inspection for scope of work complete.
Final Inspection of New Portable addition to existing system. Phone #: 208- ###-#### matt Inspection requested via web by jason petty
|
FIR18-00510
| INSP-Conference | 12/11/2018 | 12/11/2018 | 12/11/2018 3:04:46 PM | P | CANC |
|
|
Phone #: ###-#### Inspection requested via web by Sam Ball
|
BLD18-04295
| FIRE-Final Inspection | 12/5/2018 | 12/11/2018 | 12/11/2018 2:15:36 PM | P | FAIL |
|
|
Numerous exit lights/emergency lights did not work on battery power, lights will need to be sreviced or replaced to be code compliant.
call for access- Ketih Phone #: ###-####
|
FIR18-00479
| INSP-Sprinkler Rough-in | 12/11/2018 | 12/11/2018 | 12/11/2018 1:51:58 PM | P | PASS |
|
|
Rough to cover inspection for overhead fire sprinkler piping in area of work complete, approved for cover.
Call to meet there // Tom Phone #: ###-####
|
FIR18-00583
| INSP-Sprinkler Rough-in | 12/11/2018 | 12/11/2018 | 12/11/2018 1:10:39 PM | P | CANC |
|
|
Rescheduled for 12DEC18 per conversation with POC, this request is cancelled.
Tony Cetani is the contact. Phone #: ###-#### Inspection requested via web by Stan Beus
|
FIR18-00592
| INSP-Sprinkler Rough-in/Hydro | 12/11/2018 | 12/11/2018 | 12/11/2018 12:58:40 PM | P | DONE |
|
|
Hydrostatic test for overhead fire sprinkler piping witnessed, no pressure loss observed.
Contact Ken Orahood ###-#### 30 min prior to Hydro Insp start please.
Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
|
BLD18-04364
| FIRE-Final Inspection | 12/4/2018 | 12/11/2018 | 12/11/2018 12:06:18 PM | A | PASS |
|
|
No fire sprinklers, no fire alarms, fire exitnguisher will be mounted in discussed location. Final life fire safety inspection complete.
Call for Access- Chet Phone #: ###-####
|
FIR18-00428
| INSP-Final Inspection | 12/11/2018 | 12/11/2018 | 12/11/2018 11:42:32 AM | P | CANC |
|
|
Tony Cetani is the contact. Phone #: ###-#### Inspection requested via web by Stan Beus
|
BLD18-03324
| FIRE-Final Inspection | 12/7/2018 | 12/11/2018 | 12/11/2018 11:28:37 AM | A | PASS |
|
|
Space is now back to a vanilla TI space with no occupancy, modifications will be required for the fire alarm system with future occupants, no modifications required for the fire sprinkler system in vanilla TI section for this permit. Life fire safety inspection for vanilla TI complete. As stated, no occupancy allowed under this permit. John Phone #: ###-####252
|
FIR18-00502
| INSP-Final Inspection | 12/10/2018 | 12/11/2018 | 12/11/2018 10:46:32 AM | A | PASS |
|
|
Final fire sprinkler inspection complete.
Please call Anthony before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
BLD18-02751
| FIRE-Final Inspection | 12/10/2018 | 12/11/2018 | 12/11/2018 9:31:40 AM | A | PASS |
|
|
Previously noted items have been corrected, fire sprinkler inspection complete, fire alarm inspection complete, fire extinguishers are in place with current inspection tags. Final life fire safety inspection for area of work complete.
Tim Phone #: ###-####
|
FIR18-00897
| INSP-Final Inspection | 12/10/2018 | 12/11/2018 | 12/11/2018 9:30:35 AM | A | PASS |
|
|
Final fire alarm inspection for area of work complete.
Phone #: 2088990672 >> Inspection requested via mobile web by Josiah Froese
|
BLD18-02834
| FIRE-Final Inspection | 12/10/2018 | 12/11/2018 | 12/11/2018 9:22:49 AM | A | FAIL |
|
|
Reference Troys notes entered on 06DEC2018, as of this inspection no upgrade aggreement has been made.
Tony Phone #: ###-####
|
BLD18-01271
| FIRE-Final Inspection | 12/11/2018 | 12/11/2018 | 12/11/2018 8:50:24 AM | A | PASS |
|
|
Fire sprinkler inspection complete, fire alarm inspection complete, fire extinguishers are placed with current inspection tags. Final life fire safety inspection for area of work complete.
|
FIR18-00888
| INSP-Final Inspection | 12/7/2018 | 12/11/2018 | 12/11/2018 8:49:35 AM | A | PASS |
|
|
Final fire alarm inspection for area of work complete.
Stan-early am if possible Phone #: ###-####
|
BLD18-04333
| FIRE-Final Inspection | 12/10/2018 | 12/11/2018 | 12/11/2018 8:25:40 AM | A | FAIL |
|
|
Fire extinguishers need to be inspected and tagged accordingly. Mount fire extinguishers as discussed, maximum of 75 foot walking distance for each extinguisher as per code. Service or replace exit signs that are inoperable. Provide signage on main entry doors reading "Door to remain unlocked while building is occupied".
Rebecca Phone #: 208-###-####-please call a few minutes prior to meet for access
|
BLD18-02794
| FIRE-Final Inspection | 12/10/2018 | 12/11/2018 | 12/11/2018 7:53:22 AM | A | PASS |
|
|
Previously noted items have been corrected, escutcheons will be installed when received, final life fire safety inspection for area of work complete.
Parker. Requesting TCO Phone #: ###-####
|
FIR18-00455
| INSP-Conference | 12/10/2018 | 12/11/2018 | 12/11/2018 12:00:00 AM | A | DONE |
|
|
Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price.
On site to review 2nd and 3rd floor strobe placement changes. No problems found. No tests performed.
|