FIR18-00455
| INSP-Final Inspection | 12/12/2018 | 12/12/2018 | 12/12/2018 3:50:16 PM | P | PART |
|
|
RTU shutdown testing complete, in-duct detectors tested on levels 2 and 3. Still need to test A/V devices and initiating devices for phase 1 TCO requested areas.
Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price
|
FIR18-00153
| INSP-Final Inspection | 12/11/2018 | 12/12/2018 | 12/12/2018 3:46:38 PM | P | PART |
|
|
Partial final inspection for overhead fire sprinkler piping complete, plumbers still need to hook water closet to fire sprinkler system as shown on the city approved drawings. Flow test will be completed during next inspection.
Colton Cox is the Contact Phone #: ###-#### Inspection requested via web by Stan Beus
|
FIR18-00686
| INSP-Sprinkler Rough-in/Hydro | 12/11/2018 | 12/12/2018 | 12/12/2018 1:31:07 PM | P | DONE |
|
|
Hydrostatic test for remaining overhead wet system fire sprinkler piping witnessed, no pressure loss observed, hydrostatic test for all of wet system complete.
Ron Phone #: ###-####
|
FIR18-00686
| INSP-Sprinkler Rough-in | 12/11/2018 | 12/12/2018 | 12/12/2018 1:31:07 PM | P | PASS |
|
|
Rough in inspection for dry system complete.
dry system Ron Phone #: ###-####
|
FIR18-00766
| INSP-Final Inspection | 12/11/2018 | 12/12/2018 | 12/12/2018 1:31:06 PM | P | FAIL |
|
|
Repair visual device in back hallway that was INOP during inspection.
Phone #: ###-#### Inspection requested via web by Gary Gambino
|
FIR18-00819
| INSP-Final Inspection | 12/12/2018 | 12/12/2018 | 12/12/2018 10:36:17 AM | P | PASS |
|
|
Final fire sprinkler inspection for area of work compolete.
Rick Phone #: ###-####
|
FIR18-00267
| INSP-Sprinkler Rough-in | 12/11/2018 | 12/12/2018 | 12/12/2018 10:35:37 AM | A | PART |
|
|
Partial rough to cover inspection for overhead fire sprinkler piping complete, notated city approved drawings on level 1 with yellow highlighter/red ink areas approved for cover.
Justin Phone #: ###-####
|
FIR18-00716
| INSP-Sprinkler Rough-in/Hydro | 12/11/2018 | 12/12/2018 | 12/12/2018 9:59:46 AM | A | DONE |
|
|
Hydrostatic test for level 2 completed with anit-freeze, no pressure loss observed.
Gerarrdo is the contact and he would like a hydro on the 2nd floor. please. Phone #: ###-#### Inspection requested via web by Stan Beus
|
FIR18-00021
| INSP-Sprinkler Rough-in | 12/11/2018 | 12/12/2018 | 12/12/2018 9:17:32 AM | A | PART |
|
|
Partial rough to cover inspection for overhead fire sprinkler piping on level 2 complete, notated city approved drawings with yellow highlighter/red ink areas inspected and approved for cover. Temporary FDC will be installed by fire sprinkler riser room due to access, permenant location currently has portable buildings that will be removed in the future so a temp FDC will be required for occupancy until permenant location can be accessed by fire truck.
George Jess is the contact for this rough to cover inspection on the 2nd floor. Thank you for your help. Have a nice day. Phone #: ###-#### Inspection requested via web by Stan Beus
|
FIR18-00510
| INSP-Sprinkler Rough-in | 12/11/2018 | 12/12/2018 | 12/12/2018 8:41:21 AM | A | PART |
|
|
No fire sprinklers required under garage exhaust ducting.
Phone #: ###-#### Inspection requested via web by Sam Ball
|
FIR17-00474
| INSP-Sprinkler Rough-in | 12/11/2018 | 12/12/2018 | 12/12/2018 7:44:19 AM | A | CANC |
|
|
Rescheduled per conversation with POC, inspection scheduled for 13DEC2018.
Mark Jensen is the contact. Phone #: ###-#### Inspection requested via web by Stan Beus
|
FIR18-00565
| INSP-Sprinkler Rough-in | 12/11/2018 | 12/12/2018 | 12/12/2018 7:38:57 AM | A | PART |
|
|
Rough to cover inspection for overhead fire sprinkler piping/insulation for unti 119 complete, approved for cover.
Nate Phone #: ###-####
|
FIR18-00775
| INSP-Supply line flush | 12/11/2018 | 12/12/2018 | 12/11/2018 3:43:17 PM | A | CANC |
|
|
Phone #: ###-#### >> Inspection requested via web by Sam Ball Inspection cancelled from web by: Sam Ball
|
FIR18-00776
| INSP-Supply line flush | 12/11/2018 | 12/12/2018 | 12/11/2018 3:43:06 PM | A | CANC |
|
|
Phone #: ###-#### >> Inspection requested via web by Sam Ball Inspection cancelled from web by: Sam Ball
|