Inspections for the day of: Thursday, December 12, 2019.
Number of inspections: 28
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR19-00896 INSP-Final Inspection12/11/201912/12/201912/12/2019 4:01:25 PMPPASS
Previously noted items have been corrected, final inspection for hood suppression system complete.

Please Call Brian Lockwood (YMC) at ###-#### one hour prior to inspection Phone #: ###-#### Inspection requested via web by JJ Wallace
FIR19-00897 INSP-Final Inspection12/11/201912/12/201912/12/2019 4:01:03 PMPPASS
Previously noted items have been corrected, final inspection for hood suppression system complete.

Please Call Brian Lockwood (YMC) at ###-#### one hour prior to inspection Phone #: ###-#### Inspection requested via web by JJ Wallace
FIR19-00898 INSP-Final Inspection12/11/201912/12/201912/12/2019 4:00:34 PMPPASS
Previously noted items have been corrected, final inspection for hood suppression system complete.

Please Call Brian Lockwood (YMC) at ###-#### one hour prior to inspection Phone #: ###-#### Inspection requested via web by JJ Wallace
FIR19-00899 INSP-Final Inspection12/11/201912/12/201912/12/2019 4:00:12 PMPPASS
Previously noted items have been corrected, final inspection for hood suppression system complete.

Please Call Brian Lockwood (YMC) at ###-#### one hour prior to inspection Phone #: ###-#### Inspection requested via web by JJ Wallace
FIR19-00900 INSP-Final Inspection12/11/201912/12/201912/12/2019 3:59:42 PMPPASS
Previously noted items have been corrected, final inspection for hood suppression system complete.

Please Call Brian Lockwood (YMC) at ###-#### one hour prior to inspection Phone #: ###-#### Inspection requested via web by JJ Wallace
FIR19-00901 INSP-Final Inspection12/11/201912/12/201912/12/2019 3:59:42 PMPPASS
Previously noted items have been corrected, final inspection for hood suppression system complete.

Please Call Brian Lockwood (YMC) at ###-#### one hour prior to inspection Phone #: ###-#### Inspection requested via web by JJ Wallace
FIR19-00318 INSP-Alarm Testing12/12/201912/12/201912/12/2019 3:56:18 PMPPART
Fire alarm test for hood monitoring complete.

Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price
FIR18-00858 INSP-Final Inspection12/12/201912/12/201912/12/2019 1:50:33 PMPPART
Northside of level 2 walkthrough complete, approved plans are notated for areas of correction.
FIR18-00858 INSP-Final Inspection12/10/201912/12/201912/12/2019 1:49:49 PMPFAIL
Level 3 floor plan does not match what was provided to the fire alarm designer, corrections need to be made for proper coverage..

Call prior to going Phone #: 2086810381 >> Inspection requested via mobile web by Doug Lessa
FIR19-00170 INSP-Final Inspection12/11/201912/12/201912/12/2019 1:15:43 PMPPASS
Previously noted items have been corrected, storage area that did not have fire sprinkler head located under the stairs was blocked off and not accessible at time of inspection. No sprinkler timer or irrigation solenoids have been installed at time of inspection and I could not confirm with the homeowner when the landscaping will be installed. Any and all irrigation that is part of the domestic water system (treated metered water) needs to isolate and shut off during water flow switch activation, as noted this was not installed at time of inspection and will be required when landscaping irrigation is installed. Final fire sprinkler inspection complete.

Please call Chris ford Phone #: ###-#### Inspection requested via web by Jessia Maxwell
FIR19-00766 INSP-Sprinkler Rough-in12/11/201912/12/201912/12/2019 12:44:47 PMPFAIL
Insulation above fire sprinkler piping in walls not installed at time of inspection.

Contact Ken Orahood ###-#### 30 min prior to RTC Insp start please, Ken would like to schedule this for late, late afternoon if possible.

Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
FIR19-00263 INSP-Sprinkler Rough-in12/11/201912/12/201912/12/2019 12:10:48 PMADONE
Hydrostatic test for dry system complete, no pressure loss observed.

Rob Chambers is the contact. Need a 24 HR Air Test on the dry system. Thanks for all you do! Phone #: ###-#### Inspection requested via web by Stan Beus
FIR19-00263 INSP-Sprinkler Rough-in/Hydro12/11/201912/12/201912/12/2019 12:10:14 PMADONE
24 hour air test witnessed for dry system, no pressure loss observed.

Rob Chambers is the contact. this is a hydro on the dry system. Thanks for all you do! Phone #: ###-#### Inspection requested via web by Stan Beus
FIR19-00891 INSP-Sprinkler Rough-in12/11/201912/12/201912/12/2019 9:52:20 AMAPART
Rough to cover inspection for overhead fire sprinkler piping in area of work complete, area of work approved for cover. Quick response heads were used for the new install, remaining open area around scope of work has standard response heads, heads will need to all be standard response or quick response, a resubmittal will be required for approval on type of head to be installed. Will verify head change during final inspection.

Contact: Steve Vaughn Phone #: ###-#### Inspection requested via web by Hunter Fillmore
FIR19-00838 INSP-Sprinkler Rough-in12/10/201912/12/201912/12/2019 9:31:32 AMAFAIL
Walls do not go all the way to deck, sprinkler system needs to comply with 8.15.23 of the 2016 NFPA 13.

Contact: Steven Vaughn Phone #: ###-#### Inspection requested via web by Hunter Fillmore
BLD19-03060 FIRE-Final Inspection12/12/201912/12/201912/12/2019 8:06:45 AMAPASS
Fire sprinkler inspection for scope of work complete, fire alarm inspection for scope of work is complete, fire extinguishers are placed with current inspection tags. Final life fire safety inspection for scope of work is complete, signatures provided on permit signature card.
FIR19-00708 INSP-Final Inspection12/11/201912/12/201912/12/2019 7:39:21 AMPPASS
Per email from Romeo Gervias Boise City Deputy Chief FIre Marshal and Lee Meridith Fire Alarm Plans Examiner, RTU units can shut down individually instead of all together, final fire alarm inspection for scope of work is complete.

Call prior to going Phone #: 2086810381 >> Inspection requested via mobile web by Doug Lessa
BLD19-01787 FIRE-Final Inspection12/11/201912/12/201912/12/2019 7:27:55 AMAPASS
Fire sprinkler inspection is complete, fire alarm inspection is complete, fire extinguishers are placed with current inspection tags. Final life fire safety inspection for area of work complete, signatures provided on permit signature card.

Mark Phone #: ###-####
FIR19-00396 INSP-Final Inspection12/11/201912/12/201912/12/2019 7:26:31 AMAPASS
Final fire sprinkler inspection for area of work complete.

Phone #: ###-#### Inspection requested via web by Sam Ball
FIR19-00407 INSP-Final Inspection12/11/201912/12/201912/12/2019 7:25:44 AMAPASS
Final fire aalrm inspection for area of work complete.

Phone #: ###-#### Inspection requested via web by Rick Groom
FIR19-00901 INSP-Final Inspection12/11/201912/12/201912/11/2019 2:30:14 PMPCANC
Please call one hour prior to inspection Phone #: ###-#### >> Inspection requested via web by JJ Wallace Inspection cancelled from web by: JJ Wallace
FIR19-00900 INSP-Final Inspection12/11/201912/12/201912/11/2019 2:30:10 PMPCANC
please call one hour prior to inspection >> Inspection requested via web by JJ Wallace Inspection cancelled from web by: JJ Wallace
FIR19-00899 INSP-Final Inspection12/11/201912/12/201912/11/2019 2:30:07 PMPCANC
please call one hour prior to inspection >> Inspection requested via web by JJ Wallace Inspection cancelled from web by: JJ Wallace
FIR19-00898 INSP-Final Inspection12/11/201912/12/201912/11/2019 2:30:05 PMPCANC
please call one hour prior to inspection Phone #: ###-#### >> Inspection requested via web by JJ Wallace Inspection cancelled from web by: JJ Wallace
FIR19-00897 INSP-Final Inspection12/11/201912/12/201912/11/2019 2:30:02 PMPCANC
please call one hour prior to inspection Phone #: ###-#### >> Inspection requested via web by JJ Wallace Inspection cancelled from web by: JJ Wallace
FIR19-00896 INSP-Final Inspection12/11/201912/12/201912/11/2019 2:30:00 PMPCANC
please call one hour prior to inspection Phone #: ###-#### >> Inspection requested via web by JJ Wallace Inspection cancelled from web by: JJ Wallace
FIR19-00321 INSP-Final Inspection12/11/201912/12/201912/11/2019 2:07:02 PMAPASS
Final fire sprinkler inspection is complete.

Phone #: ###-#### Inspection requested via web by Jessia Maxwell
FIR19-00321 INSP-Final Inspection12/11/201912/12/201912/11/2019 12:48:35 PMPCANC
Phone #: ###-#### >> Inspection requested via web by Jessia Maxwell Inspection cancelled from web by: Jessia Maxwell