BLD19-00248
| FIRE-Conference | 12/13/2019 | 12/13/2019 | 12/13/2019 3:08:46 PM | P | DONE |
|
|
Fire conference complete, discussed items required for life fire safety for phase 1 occupancy.
Review phase 1 occupancy / egress plan. Please call Chris when in route. Thank you, Phone #: ###-#### Inspection requested via web by Chris Fuhrman
|
BLD19-00278
| FIRE-Conference | 12/13/2019 | 12/13/2019 | 12/13/2019 2:21:22 PM | P | DONE |
|
|
Fire sprinkler systems are active and monitored, set up of unit furniture/office furniture is approved, no occupancy allowed as of this entry.
|
BLD19-02706
| FIRE-Final Inspection | 12/13/2019 | 12/13/2019 | 12/13/2019 12:46:47 PM | P | FAIL |
|
|
Smoke detector in main lobby of tenant space, next to conference room is overspaced. Conference room requires notification. Modifications have been made without a fire alarm permit. FIR permit for fire sprinkler needs to be finaled before life fire safety inspection can be completed. No occupancy allowed until inspection process is complete and finaled.
Bill- Phone #: ###-####
|
BLD19-02692
| FIRE-Final Inspection | 12/12/2019 | 12/13/2019 | 12/13/2019 12:09:43 PM | A | CANC |
|
|
Cancelled per conversation with point of contact, fire sprinklers will need to adjusted due to ceiling changes, inspection will be rescheduled for a later date.
Scott Phone #: ###-####
|
FIR19-00722
| INSP-Final Inspection | 12/12/2019 | 12/13/2019 | 12/13/2019 12:08:51 PM | A | CANC |
|
|
Cancelled per conversation with Robert, ceiling elevation was changed which affected sidewall positioning, will be requested for a later date.
Contact is Nick Phone #: ###-#### Inspection requested via web by Chris Green
|
FIR19-00727
| INSP-Final Inspection | 12/10/2019 | 12/13/2019 | 12/13/2019 12:03:58 PM | A | CANC |
|
|
Cancelled per conversation with point of contact, wall was added which effected sprinkler coverage, will be rescheduled for a later date.
Kenny is the contact. Thanks for all you do! Phone #: ###-#### Inspection requested via web by Stan Beus
|
FIR19-00727
| INSP-Sprinkler Rough-in | 12/10/2019 | 12/13/2019 | 12/13/2019 12:03:41 PM | A | CANC |
|
|
Cancelled per conversation with point of contact, wall was added which effected sprinkler coverage, will be rescheduled for a later date.
Kenny is the contact. Thanks for all you do! Phone #: ###-#### Inspection requested via web by Stan Beus
|
FIR19-00067
| INSP-Final Inspection | 12/13/2019 | 12/13/2019 | 12/13/2019 12:02:29 PM | P | PASS |
|
|
Final underground supply inspection is complete.
|
FIR19-00263
| INSP-Final Inspection | 12/12/2019 | 12/13/2019 | 12/13/2019 11:59:21 AM | A | PASS |
|
|
Final fire sprinkler inspection complete.
Rob Chambers is the contact. Thanks for all yo do! Phone #: ###-#### Inspection requested via web by Stan Beus
|
FIR19-00318
| INSP-Final Inspection | 12/11/2019 | 12/13/2019 | 12/13/2019 11:57:39 AM | A | PART |
|
|
Fire sprinkler system monitoring is complete. Remaining items to test, full notification throughout and initiating devices in common areas.
Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price
|
FIR19-00846
| INSP-Final Inspection | 12/12/2019 | 12/13/2019 | 12/13/2019 8:44:57 AM | A | FAIL |
|
|
2 pendant heads to close to registers, lees than 12 inches and 155 degree heads are placed. Head that was aded in juicer area is 3 5/8 inches off of wall, a minimum of 4 inches is required. Upright heads next to vetstibule entrance, northside are overspaced, upright heads are 10 on center, upright is 7 foot off of new wall and upright that was added is more than 5 foor off edge of new wall corner.
Contact Hunter Anderson ###-#### 30 min prior to Final Insp. start please, Hunter would like to sched. for early AM as possible.
Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
|
BLD19-03260
| FIRE-Final Inspection | 12/12/2019 | 12/13/2019 | 12/12/2019 9:03:33 PM | A | CANC |
|
|
Daryl Phone #: ###-#### Inspection cancelled via mobile web on Thursday, December 12, 2019.
|