BLD18-04417
| FIRE-Final Inspection | 12/14/2018 | 12/14/2018 | 12/14/2018 3:55:23 PM | P | FAIL |
|
|
Attempted to call point of contact with phone number that was provided at 2:53PM, left a voicemail with my contact information, waited until 4PM with no call back. Inspection will need to be rescheduled.
Leticia Phone #: ###-####
|
FIR18-00856
| INSP-Sprinkler Rough-in/Hydro | 12/13/2018 | 12/14/2018 | 12/14/2018 2:53:08 PM | P | CANC |
|
|
Inspection rescheduled for 17DEC2018 per conversation with point of contact. This request is cancelled.
Please call chris felty Phone #: ###-#### Inspection requested via web by Jessia Maxwell
|
BLD18-01064
| FIRE-Final Inspection | 12/14/2018 | 12/14/2018 | 12/14/2018 2:51:48 PM | P | FAIL |
|
|
Need signage leading from exterior to fire sprinkler riser room. Install fire lane signage as discussed. Provide notification over fire department connection, currently no bell or A/V device is installed. Stairwells need to be 100% complete before TCO can be authorized for life fire safety. Elevator smoke detectors report as a supervisor, detectors need to report as general alarm.
dave Phone #: ###-####
|
BLD18-01593
| FIRE-Final Inspection | 12/14/2018 | 12/14/2018 | 12/14/2018 2:48:13 PM | P | FAIL |
|
|
Pedestrian link between 36 and 37 not ready for inspection.
Dave Phone #: ###-####
|
FIR18-00455
| INSP-Final Inspection | 12/14/2018 | 12/14/2018 | 12/14/2018 2:47:17 PM | A | PART |
|
|
Fire alarm inspection for level 3 and level 1 lobby complete, fire sprinkker monitoring complete to include standpipe valve supervision. Still need to inspect levels 1 and 2 including pedestrian link.
Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price
|
BLD18-01261
| FIRE-Final Inspection | 12/13/2018 | 12/14/2018 | 12/14/2018 11:45:40 AM | A | PASS |
|
|
Final life fire safety inspection for area of work complete.
Dale Phone #: ###-####
|
FIR18-00491
| INSP-Final Inspection | 12/13/2018 | 12/14/2018 | 12/14/2018 11:07:30 AM | A | FAIL |
|
|
Provide fire sprinklers in areas on level 2 that are part of the bedroom compartments. Could not flow water due to plumbers not being complete. Install missing escutcheon in office to right of main entry. Appears irrigation timer is not in place.
Please call Anthony before heading out, thank you! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
FIR18-00489
| INSP-Final Inspection | 12/13/2018 | 12/14/2018 | 12/14/2018 10:46:58 AM | A | PASS |
|
|
Final fire sprinkler inspection complete.
Please call before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
FIR18-00356
| INSP-Final Inspection | 12/12/2018 | 12/14/2018 | 12/14/2018 10:46:06 AM | A | PASS |
|
|
Final fire sprinkler inspection for area of work complete.
Rick Phone #: ###-####
|
FIR18-00766
| INSP-Final Inspection | 12/13/2018 | 12/14/2018 | 12/14/2018 10:13:30 AM | A | PASS |
|
|
Final fire alarm inspection for area of work complete.
Phone #: ###-#### Inspection requested via web by Rafe Barrett
|
FIR18-00153
| INSP-Final Inspection | 12/13/2018 | 12/14/2018 | 12/14/2018 10:10:03 AM | A | PASS |
|
|
Final fire sprinkler inspection complete.
Marcus Smith is the contact for this final inspection. Thank you for your help. Phone #: ###-#### Inspection requested via web by Stan Beus
|
FIR18-00910
| INSP-Final Inspection | 12/13/2018 | 12/14/2018 | 12/14/2018 8:32:49 AM | A | PASS |
|
|
Final fire sprinkler inspection for area of work complete.
Meet with Eric the superintendent for Dauby construction to access the space. Phone #: ###-#### Inspection requested via web by Sam Ball
|
FIR18-00910
| INSP-Sprinkler Rough-in | 12/14/2018 | 12/14/2018 | 12/14/2018 8:32:16 AM | A | PASS |
|
|
Rough to cover inspection for overhead fire sprinkler piping in area of work complete, approved for cover.
|
BLD18-01250
| FIRE-Final Inspection | 12/13/2018 | 12/14/2018 | 12/14/2018 8:05:50 AM | A | PASS |
|
|
Fire sprinkler inspection complete, no fire alarm modifications. Final life fire safety inspection for scope of work complete.Dale Phone #: ###-####
|