Inspections for the day of: Tuesday, December 17, 2019.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR19-00274 INSP-Final Inspection12/16/201912/17/201912/17/2019 2:58:41 PMPFAIL
Chute room on level 3 is also a furnace closet, sprinkler head must be provided in mechanical closets. 4 sprinkler heads are less than 24 inches from heat registers, sprinklers must be 24 inches or greater away from heat registers per 2016 NFPA 13D. Repair holes around sprinkler heads where escutcheon does not cover entire penetration. Install escutcheons that are missing as discussed and replaced escutcheon in master bathroom.

Please call before heading to job site. We will be coming from the office and will need about 30 to 45 minutes to get to the job site. Phone #: ###-#### Inspection requested via web by Matt Barnard
BLD19-02586 FIRE-Final Inspection12/16/201912/17/201912/17/2019 12:16:40 PMAPASS
Final life fire safety inspection for scope of work is complete.

Final inspection request for new precast stairs installed on exiting columns. Phone #: ###-#### Inspection requested via web by Brian Hetmer
FIR19-00390 INSP-Sprinkler Rough-in12/16/201912/17/201912/17/2019 12:16:12 PMAPART
Due to this being a steep hiilside project, undergorund supply approved for partial cover, fittings to be left exposed and will be inspected following day.

UG Phone #: ###-#### Inspection requested via web by Matthew Lewis
BLD19-02053 BLD-Conference12/16/201912/17/201912/17/2019 11:19:16 AMADONE
Fire conference complete.

Ron Phone #: ###-####
FIR19-00666 INSP-Final Inspection12/16/201912/17/201912/17/2019 10:13:39 AMAPASS
Final fire sprinkler inspection for area of work complete.

Phone #: ###-#### Inspection requested via web by Jonathan LaFond
BLD19-04783 FIRE-Final Inspection12/16/201912/17/201912/17/2019 9:53:06 AMAPASS
No fire sprinklers, no fire alarms, fire exitnguisher is placed and will be inspected as discussed. Final life fire safety inspection complete, signature provided on permit sign off card.

JANA Phone #: ###-####/
BLD19-01829 FIRE-Final Inspection12/16/201912/17/201912/17/2019 9:35:24 AMAPASS
Fire sprinkler inspection is complete, no fire alarm modificaitons required, fire extinguishers are in common areas with current inspection tags. Final life fire safety inspection for area of work is complete, no signature card provided at time of inspection.

Adam Phone #: ###-####
BLD19-01829 FIRE-Supply Line Hydro12/16/201912/17/201912/17/2019 9:33:50 AMACANC
Adam Phone #: ###-####
BLD19-03260 FIRE-Final Inspection12/16/201912/17/201912/17/2019 8:37:32 AMAPASS
Fire sprinkler inspection is complete, no fire alarm modifications required, fire extinguishers are placed and will be tagged with current inspection tags. Final life fire safety inspection for area of work is complete.

Daryl Phone #: ###-####
FIR19-00846 INSP-Final Inspection12/16/201912/17/201912/17/2019 8:36:36 AMAPASS
Previously noted items have been corrected, final fire sprinkler inspection for area of work complete.

Contact Hunter Anderson - ###-#### Final Insp - Phone #: ###-#### Inspection requested via web by Teri Cruickshank
FIR19-00846 INSP-Final Inspection12/16/201912/17/201912/16/2019 12:02:56 PMPCANC
Contact Hunter Anderson ###-#### 30 min prior to Final Insp start please.

Thank YOU Phone #: ###-#### >> Inspection requested via web by Teri Cruickshank Inspection cancelled from web by: Teri Cruickshank