Inspections for the day of: Tuesday, December 18, 2018.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR14-00118 FIR-Aging Inspection12/18/201812/18/201812/24/2018 11:04:40 AM CANC
Project is still under construction.
BLD18-03929 FIRE-Final Inspection12/18/201812/18/201812/18/2018 1:58:44 PMPPASS
Final life fire safety inspection for scope of work complete.

call 10 mins ahead- Christy Phone #: ###-####
FIR17-00612 INSP-Sprinkler Rough-in12/18/201812/18/201812/18/2018 1:39:42 PMPPASS
Rough to cover inspection for remaining sprinkler piping in Rite Aid canopy complete, approved for cover.

Jeff Chaney is the contact for this RTC inspection. Thank you for your help and have a nice day. Phone #: ###-#### Inspection requested via web by Stan Beus
FIR18-00912 INSP-Final Inspection12/18/201812/18/201812/18/2018 1:38:14 PMPPASS
Final fire sprinker inspection for scope of work complete.

jeremy Phone #: ###-####
FIR18-00871 INSP-Alarm Testing12/17/201812/18/201812/18/2018 1:38:13 PMPDONE
Fire alarm testing complete.

Chris Siewert, technician Phone #: ###-#### Inspection requested via web by John Siewert
BLD18-01334 FIRE-Final Inspection12/18/201812/18/201812/18/2018 10:59:03 AMPPASS
Final life fire safety inspection for area of work complete.

Zach Phone #: ###-####
BLD18-03669 FIRE-Final Inspection12/17/201812/18/201812/18/2018 10:55:22 AMAPASS
Final life fire safety inspection for racking permit complete.

Joe Phone #: ###-####
BLD18-01906 FIRE-Final Inspection12/18/201812/18/201812/18/2018 9:01:33 AMPPART
Fire sprinkler inspection for area of work complete, fire alarm inspection for area of work complete, fire extinguishers are placed with current inspection tags in area of work. Fire alarm panel for building had troubles at time of inspection, troubles need to be repaired and fire panel needs to show normal before life fire safety can be finaled, all other items for life fire safety inspection is complete.

Phone #: ###-#### Inspection requested via web by Jason Ginn
BLD18-01906 FIRE-Alarm Testing12/18/201812/18/201812/18/2018 8:59:24 AMPCANC
Phone #: ###-#### Inspection requested via web by Jason Ginn
FIR18-00750 INSP-Final Inspection12/17/201812/18/201812/18/2018 7:41:06 AMAPART
Final fire alarm inspection for area of work complete, panel was showing troubles outside the scope of work that need to be repaired, permit will not be finaled until troubles are resloved and panel is showing normal.

7 am owner request Phone #: ###-#### Inspection requested via web by Shane Lesteberg
FIR18-00479 INSP-Final Inspection12/17/201812/18/201812/18/2018 7:39:55 AMAPASS
Final fire sprinkler inspection for area of work complete.

The General Contractor informed us they were attempting to complete their Fire Life Safety for the BLD at 7 AM Tuesday 12-18. We would like to perform our inspection in conjunction. Please let Tom know if there are any questions. Phone #: ###-#### Inspection requested via web by Jeff Packham
FIR18-00750 INSP-Final Inspection12/17/201812/18/201812/17/2018 4:02:02 PMACANC
7am inspection requested by building owner Phone #: ###-#### >> Inspection requested via web by Shane Lesteberg Inspection cancelled from web by: Shane Lesteberg