FIR19-00489
| INSP-Sprinkler Rough-in/Hydro | 12/18/2019 | 12/18/2019 | 12/18/2019 4:12:01 PM | P | PART |
|
|
Initial walk through for rough in inspection for overhead fire sprinkler piping complete, a seperate inspection will need to be requested for a cover inspection after finsh heads are cut in.
Todd Ketterling is the contact. Thanks for all you do! Phone #: ###-#### Inspection requested via web by Stan Beus
|
BLD19-02692
| FIRE-Final Inspection | 12/18/2019 | 12/18/2019 | 12/18/2019 2:41:30 PM | P | PASS |
|
|
Fire sprinkler inspection is complete, no fire alarm modifications, fire extinguisher is placed with a current inspection tag. Final life fire safety inspection for area of work complete.
|
FIR19-00722
| INSP-Final Inspection | 12/18/2019 | 12/18/2019 | 12/18/2019 2:40:36 PM | P | PASS |
|
|
Final fire sprinkler inspection for area of work complete.
Contact is Roy Fouts Phone #: ###-#### Inspection requested via web by Chris Green
|
FIR19-00722
| INSP-Sprinkler Rough-in | 12/18/2019 | 12/18/2019 | 12/18/2019 2:40:06 PM | P | PASS |
|
|
Rough to cover inspection for remaining fire sprinkker piping in scope of work complete, approved for cover.
Contact is Roy Fouts Phone #: ###-#### Inspection requested via web by Chris Green
|
FIR19-00634
| INSP-Final Inspection | 12/12/2019 | 12/18/2019 | 12/18/2019 11:45:25 AM | A | FAIL |
|
|
Elevator pit has fire sprinkler installed, provide smoke and heat detection in for shunt and recall as discussed. Notated city approved drawings where audio visual notification was overspaced. Verified monitoring, tested basement initiating devices, tested fire sprinkler tampers and flow switch, items tested all worked as required.
We would like this inspection to be done at 9:00 am. Please call Nate at ###-#### with inspection time. Phone #: ###-#### Inspection requested via web by Lori Brungardt
|
FIR19-00860
| INSP-Sprinkler Rough-in | 12/17/2019 | 12/18/2019 | 12/18/2019 10:43:15 AM | A | PASS |
|
|
Rough to cover inspection for overhead fire sprinkler piping in scope of work complete, scope of work approved for cover.
Peyton Phone #: ###-####
|
BLD19-04417
| FIRE-Final Inspection | 12/17/2019 | 12/18/2019 | 12/18/2019 10:26:51 AM | A | PASS |
|
|
No fire sprinkler modifications, no fire aalrm modifications, fire extinguisher is placed with a current inspection tag. Final life fire safety inspection for area of work is complete, signatures provided on permit sign off card.
Phone #: 2088415809 >> Inspection requested via mobile web by Mike
|
BLD18-02007
| FIRE-Final Inspection | 12/17/2019 | 12/18/2019 | 12/18/2019 10:09:00 AM | A | PASS |
|
|
Previously noted iems have been corrected, final life fire safety inspection is complete, signature provided on permit sign off card.
|
FIR19-00390
| INSP-Sprinkler Rough-in | 12/17/2019 | 12/18/2019 | 12/18/2019 9:57:51 AM | A | PASS |
|
|
Rough to cover inspection for underground supply complete, approved for cover.
UG Phone #: ###-#### Inspection requested via web by Matthew Lewis
|
BLD19-04602
| FIRE-Final Inspection | 12/17/2019 | 12/18/2019 | 12/18/2019 7:18:06 AM | A | CANC |
|
|
Fire alarm inspection failed, FIR permits associated with space must be finaled before l;ife fire safety can be completed, this request is cancelled..
Tom Phone #: ###-####
|
FIR19-00910
| INSP-Final Inspection | 12/12/2019 | 12/18/2019 | 12/18/2019 7:17:13 AM | A | FAIL |
|
|
Four different flash patterns seen on the east side of tenant space, visual notification needs to sync to be code compliant.
Needs to be done at 7:00am Phone #: ###-#### Inspection requested via web by Sam Ball
|
FIR19-00892
| INSP-Final Inspection | 12/12/2019 | 12/18/2019 | 12/18/2019 7:16:15 AM | A | PASS |
|
|
Final fire sprinkler inspection for area of work complete.
Needs to be done at 7:00am Phone #: ###-#### Inspection requested via web by Sam Ball
|
FIR19-00693
| INSP-Final Inspection | 12/17/2019 | 12/18/2019 | 12/17/2019 12:12:29 PM | A | PASS |
|
|
Final fire aalrm inspection for area of work is complete.
Site inspection already complete per conv. with Jim Page. Contact John Siewert for further if needed. Phone #: ###-#### Inspection requested via web by John Siewert
|