Inspections for the day of: Friday, December 21, 2018.
Number of inspections: 21
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR18-00686 INSP-Sprinkler Rough-in/Hydro12/20/201812/21/201812/21/2018 3:42:24 PMPPART
Hydrostatic test for dry system witnessed, no pressure loss observed. 24 hour air test still needs to be performed.

Ron Phone #: ###-####
FIR18-00860 INSP-Final Inspection12/20/201812/21/201812/21/2018 3:29:16 PMPPASS
Final fire alarm inspection for area of work complete.

Phone #: ###-#### Inspection requested via web by John Lopez
BLD17-00374 FIRE-Final Inspection12/20/201812/21/201812/21/2018 1:17:05 PMPPASS
Previously noted iyems have been corrected, final life fire safety inspection for area of work complete.

Have scheduled door company for a 1:00pm drop test on coil door if any questions please call Dutch @ 208 249 6313 Thank you Phone #: ###-#### Inspection requested via web by Dennis Harmon
FIR18-00869 INSP-Sprinkler Rough-in12/20/201812/21/201812/21/2018 12:24:02 PMPCANC
Contact Hunter Anderson - ###-#### 30 Min prior to RTC Insp start please

Thank YOU Phone #: ###-#### >> Inspection requested via web by Teri Cruickshank Inspection cancelled from web by: Teri Cruickshank
BLD16-02008 FIRE-Final Inspection12/21/201812/21/201812/21/2018 12:11:10 PMPPART
Final life fire safety inspection for phase 4 TCO complete. Phase 3 of TCO aggreement still needs to be completed for life fire safety.

Phase 4 TCO, Plaza Park. Call Adam with any questions. ###-####. Thanks. AKJ Phone #: ###-#### Inspection requested via web by Adam Johnson
FIR18-00759 INSP-Sprinkler Rough-in12/21/201812/21/201812/21/2018 12:09:14 PMPPASS
Rough to cover inspection for overhead fire sprinkler piping in remainder of scope of work complete, approved for cover.

tom Phone #: ###-####
FIR18-00021 INSP-Sprinkler Rough-in12/20/201812/21/201812/21/2018 11:16:48 AMAPART
Rough to cover inspection for overhead fire sprinkler piping in kitchen complete, kitchen area approved for cover. Fire sprinkler heads around kitchen cooking hood will be changed to 200 degree heads before final inspection.

George is the contact. He asked for an inspection for a RTC in the Kitchen area. Thank you for your help! Phone #: ###-#### Inspection requested via web by Stan Beus
FIR18-00917 INSP-Final Inspection12/20/201812/21/201812/21/2018 10:51:38 AMACANC
Building manager was not on-site during inspection request, point of contact notified me before inspection was performed, this inspection is cancelled per conversation with point of contact.

Contact is Derrick Kamper. Phone #: ###-#### Inspection requested via web by Morgan Ahten
FIR18-00725 INSP-Final Inspection12/20/201812/21/201812/21/2018 10:48:35 AMAFAIL
Ceiling tiles were installed before cover inspection was performed, only inspection for cover was on the hardlids, cover material for areas that have not been inspected needs to be removed for cover inspection to be performed.

Please call Lonnie with questions. Phone #: ###-#### Inspection requested via web by Jeff Packham
BLD18-02662 FIRE-Final Inspection12/20/201812/21/201812/21/2018 10:36:16 AMAPASS
Fire sprinkler inspection complete, fire alarm inspection complete, fire extinguishers are placed with current inspection tags. Final life fire safety inspection for area of work complete.

fire life safety for chase bank to e done same time as TVFP.. thank you Steve Dwyer ###-#### Phone #: ###-#### Inspection requested via web by Steve Dwyer
FIR18-00713 INSP-Final Inspection12/20/201812/21/201812/21/2018 10:34:03 AMAPASS
Final fire sprinkler inspection for area of work complete.

Access is limited and we would like to perform this in conjunction with the fire life safety for the BLD. Please call Terry with a time frame to ensure access. Phone #: ###-#### Inspection requested via web by Jeff Packham
BLD18-03632 FIRE-Final Inspection12/20/201812/21/201812/21/2018 10:11:33 AMAFAIL
Fire sprinkler permit for fire alarm modifications still in issued status, need associated fire sprinkler permit competed and finaled before life fire safety can be completed.

Please call ahead of arrival. Thanks. Phone #: ###-#### Inspection requested via web by Kirsten Dallmann
FIR18-00852 INSP-Sprinkler Rough-in/Hydro12/20/201812/21/201812/21/2018 9:45:51 AMACANC
Cancelled per conversation with point of contact.

5th floor Phone #: ###-#### Inspection requested via web by Matthew Lewis
BLD18-04417 FIRE-Final Inspection12/20/201812/21/201812/21/2018 9:44:46 AMAFAIL
Fire spribkler head next to center bar area has head within 12 inches of air diffuser, needs to be an intermediate temperature head to be code compliant, current temp for sprinkler is 155 degree. Numerous escutcheons are missing throughout, all escutcheons need to be in place on fire sprinklers. New cooking epuipment has been installed as well as exisitng cooking equipment has been moved, modification to the hood fire suppression system may be required, contact a licensed commercial hood contractor for corrections (A permit will be required for ANY modifications to the hood system).

Leticia Phone #: ###-####
BLD17-04571 FIRE-Final Inspection12/20/201812/21/201812/21/2018 9:19:21 AMAFAIL
Provide fire extinguisher with current inspection tag. Provide sticker on front door reading "Door to remain unlocked while building is occupied. Need city approved drawings/documents for final inspection.

Stuart Phone #: ###-####
FIR18-00609 INSP-Final Inspection12/19/201812/21/201812/21/2018 8:46:36 AMAFAIL
Flow switch did not activate with water flow.

Rough in and Final inspection. POC is Jeff Jeager Phone #: ###-#### Inspection requested via web by Brett Lawatch
FIR18-00630 INSP-Final Inspection12/20/201812/21/201812/21/2018 8:45:58 AMAFAIL
Flow switch did not operate with water flow, FDC bell stopped when panel was silenced, did not continue to ring with flow switch being held, FDC bell needs to ring during water flow.

John Howard, Technician Phone #: ###-#### Inspection requested via web by John Siewert
FIR18-00609 INSP-Sprinkler Rough-in12/19/201812/21/201812/21/2018 8:44:02 AMAPASS
Rough in inspection for overhead fire sprinkler piping complete.

Rough in and Final inspection. POC is Jeff Jeager Phone #: ###-#### Inspection requested via web by Brett Lawatch
BLD11-02634 FIRE-Final Inspection12/20/201812/21/201812/21/2018 8:17:19 AMAFAIL
Numerous escutcheons are missing throughout on the fire sprinkler heads. Fire sprinkler coverage needs to be corrected in womens locker room basement level. Fire sprinklers were added to a closet without a permit. Head coverage issues throughout building, fire sprinkler coverage will need to be corrected under an issued permit, any modifications to the fire sprinkler system requires a p[ermit. Exit signs need serviced throughout. Provide fire sprinkler under HVAC unit in tennis court area. Overhead door on tennis court needs to be measured when open, if door exyends back more than 48 inches then a fire sprinkler will be required.

Ray Phone #: ###-####
BLD18-02662 FIRE-Final Inspection12/20/201812/21/201812/20/2018 2:22:35 PMACANC
fire life safety inspection Phone #: ###-#### >> Inspection requested via web by Steve Dwyer Inspection cancelled from web by: Steve Dwyer
FIR18-00852 INSP-Sprinkler Rough-in/Hydro12/20/201812/21/201812/20/2018 1:46:33 PMACANC
Phone #: ###-#### >> Inspection requested via web by Matthew Lewis Inspection cancelled from web by: Matthew Lewis