BLD19-00278
| FIRE-Conference | 12/23/2019 | 12/23/2019 | 12/23/2019 2:45:55 PM | P | DONE |
|
|
Fire conference complete.
Fire life/safety walk Phone #: ###-#### Inspection requested via web by Corey Hockersmith
|
BLD19-04245
| FIRE-Final Inspection | 12/23/2019 | 12/23/2019 | 12/23/2019 2:45:25 PM | A | PASS |
|
|
Previously noted items have been corrected, no fire sprinkler modifications, fire aalrm inspection is complete, fire extinguishers are placed with current inspection tags, no modifications to hood suppression system. Final life fire safety inspection for area of work complete.
|
FIR19-00855
| INSP-Sprinkler Rough-in | 12/23/2019 | 12/23/2019 | 12/23/2019 10:47:10 AM | P | FAIL |
|
|
Could not locate city approved drawings at time of inspection. Tenting needs corrected in numerous places before cover can be approved.
Ready any time, call James before heading out. Overhead rough and tenting inspection. Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
BLD19-00727
| FIRE-Final Inspection | 12/20/2019 | 12/23/2019 | 12/23/2019 10:41:45 AM | A | FAIL |
|
|
Mag lock interface with fire alarm system has not been completed, as stated in past inspections on 13SEPT2019 and 21NOV2019, mag locks on egress doors need to release during general fire per international fire code. A seperate permit is required for any and all fire alarm system modifications.
Peter Phone #: ###-####
|
FIR19-00274
| INSP-Final Inspection | 12/22/2019 | 12/23/2019 | 12/23/2019 10:39:34 AM | A | PASS |
|
|
Previously noted items have been corrected, final fire sprinkler inspection is complete.
All comments from the failed final have been corrected. Rick Fouts will be coming from the office, if possible, please contact him 1 hour prior to heading to the job site to allow for time to get to the site at Phone #: ###-#### Inspection requested via web by Matt Barnard
|
FIR19-00751
| INSP-Sprinkler Rough-in | 12/20/2019 | 12/23/2019 | 12/23/2019 8:54:38 AM | A | PART |
|
|
Notated city approved drawings areas approved for cover.
Adam Phone #: ###-####
|
FIR19-00893
| INSP-Final Inspection | 12/23/2019 | 12/23/2019 | 12/23/2019 7:51:35 AM | A | PASS |
|
|
Audio shutdown verified, final fire alarm inspection for scope of work is complete.
|
FIR19-00893
| INSP-Alarm Testing | 12/20/2019 | 12/23/2019 | 12/23/2019 7:51:03 AM | A | DONE |
|
|
Fire alarm testing for scope of work is complete.
Pre-arranged testing time with Jim Page and Joe Hobbs of ATS Facility Systems for 7:00am Phone #: ###-#### Inspection requested via web by Joseph ATS Facility Systems
|
FIR19-00846
| INSP-Final Inspection | 12/16/2019 | 12/23/2019 | 12/16/2019 12:02:59 PM | P | CANC |
|
|
Contact Hunter Anderson ###-#### 30 min prior to Final Insp Phone #: ###-#### >> Inspection requested via web by Teri Cruickshank Inspection cancelled from web by: Teri Cruickshank
|