Inspections for the day of: Monday, December 23, 2019.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD19-00278 FIRE-Conference12/23/201912/23/201912/23/2019 2:45:55 PMPDONE
Fire conference complete.

Fire life/safety walk Phone #: ###-#### Inspection requested via web by Corey Hockersmith
BLD19-04245 FIRE-Final Inspection12/23/201912/23/201912/23/2019 2:45:25 PMAPASS
Previously noted items have been corrected, no fire sprinkler modifications, fire aalrm inspection is complete, fire extinguishers are placed with current inspection tags, no modifications to hood suppression system. Final life fire safety inspection for area of work complete.

FIR19-00855 INSP-Sprinkler Rough-in12/23/201912/23/201912/23/2019 10:47:10 AMPFAIL
Could not locate city approved drawings at time of inspection. Tenting needs corrected in numerous places before cover can be approved.

Ready any time, call James before heading out. Overhead rough and tenting inspection. Phone #: ###-#### Inspection requested via web by Anthony Minichiello
BLD19-00727 FIRE-Final Inspection12/20/201912/23/201912/23/2019 10:41:45 AMAFAIL
Mag lock interface with fire alarm system has not been completed, as stated in past inspections on 13SEPT2019 and 21NOV2019, mag locks on egress doors need to release during general fire per international fire code. A seperate permit is required for any and all fire alarm system modifications.

Peter Phone #: ###-####
FIR19-00274 INSP-Final Inspection12/22/201912/23/201912/23/2019 10:39:34 AMAPASS
Previously noted items have been corrected, final fire sprinkler inspection is complete.

All comments from the failed final have been corrected. Rick Fouts will be coming from the office, if possible, please contact him 1 hour prior to heading to the job site to allow for time to get to the site at Phone #: ###-#### Inspection requested via web by Matt Barnard
FIR19-00751 INSP-Sprinkler Rough-in12/20/201912/23/201912/23/2019 8:54:38 AMAPART
Notated city approved drawings areas approved for cover.

Adam Phone #: ###-####
FIR19-00893 INSP-Final Inspection12/23/201912/23/201912/23/2019 7:51:35 AMAPASS
Audio shutdown verified, final fire alarm inspection for scope of work is complete.

FIR19-00893 INSP-Alarm Testing12/20/201912/23/201912/23/2019 7:51:03 AMADONE
Fire alarm testing for scope of work is complete.

Pre-arranged testing time with Jim Page and Joe Hobbs of ATS Facility Systems for 7:00am Phone #: ###-#### Inspection requested via web by Joseph ATS Facility Systems
FIR19-00846 INSP-Final Inspection12/16/201912/23/201912/16/2019 12:02:59 PMPCANC
Contact Hunter Anderson ###-#### 30 min prior to Final Insp Phone #: ###-#### >> Inspection requested via web by Teri Cruickshank Inspection cancelled from web by: Teri Cruickshank