FIR19-00956
| INSP-Final Inspection | 12/26/2019 | 12/27/2019 | 12/27/2019 3:15:31 PM | P | PASS |
|
|
Final fire sprinkler inspection for scope of work complete.
Phone #: ###-#### Inspection requested via web by Sam Ball
|
FIR19-00956
| INSP-Sprinkler Rough-in | 12/26/2019 | 12/27/2019 | 12/27/2019 3:15:00 PM | P | PASS |
|
|
Rough to cover inspection for overhead fire sprinkler piping in scope of work complete, approved for cover.
Phone #: ###-#### Inspection requested via web by Sam Ball
|
BLD19-03758
| FIRE-Final Inspection | 12/27/2019 | 12/27/2019 | 12/27/2019 3:13:59 PM | P | PASS |
|
|
Fire alarm inspection is complete, no fire sprinkler modifications, fire extinguishers are placed with current inspection tags. Final life fire safety inspection for area of work complete.
Please call Jerry Jones 30 minutes before arrival Phone #: ###-#### Inspection requested via web by Jerry Jones
|
BLD19-02410
| FIRE-Final Inspection | 12/27/2019 | 12/27/2019 | 12/27/2019 2:58:22 PM | P | PASS |
|
|
No fire sprinkler modifications in scope of work, no fire alarm modifications in scope of work, fire extinguisher is in common area with a current inspection tag. Final life fire safety inspection for scope of work complete, signatures provided on permit sign off card.
Sorry we missed you this morning. The ban doesn''t open until 9 a.m. and with work being done we don''t have a super onsite. If you can call Patrick at the number above he should be able to be onsite in 10-15 minutes from when you want to arrive. Phone #: ###-#### Inspection requested via web by Dustin Keyes
|
BLD19-04107
| FIRE-Final Inspection | 12/27/2019 | 12/27/2019 | 12/27/2019 2:57:00 PM | P | PASS |
|
|
Previously noted items have been corrected, no fire sprinklers, no fire alarms, fire extinguishers are placed with current inspection yags. Final life fire safety inspection complete, signature provided on permit sign off card.
Justin Phone #: ###-####
|
FIR19-00799
| INSP-Sprinkler Rough-in | 12/25/2019 | 12/27/2019 | 12/27/2019 1:36:00 PM | P | FAIL |
|
|
Tenting not installed correctly in numerous areas, cover is not approved.
Overhead rough and tenting. Call James before heading out. Thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
FIR19-00906
| INSP-Sprinkler Rough-in/Hydro | 12/26/2019 | 12/27/2019 | 12/27/2019 11:14:05 AM | P | PASS |
|
|
Rough to cover inspection for underground supply complete, approved for cover.
Underground fire line. Call James before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
FIR19-00855
| INSP-Sprinkler Rough-in | 12/26/2019 | 12/27/2019 | 12/27/2019 10:37:41 AM | P | PASS |
|
|
Previously noted items have been corrected, rough to cover inspection for overhead fire sprinkler piping is complete, all tenting in place at time of inspection, cover is approved.
Overhead rough and tenting, call James before heading out - problem areas should be fixed by noon. Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
BLD19-04107
| FIRE-Final Inspection | 12/24/2019 | 12/27/2019 | 12/27/2019 10:14:20 AM | A | FAIL |
|
|
Exterior emergency light above north exit door did not operate when AC power was isolate. Provide exit sign above door leading from warehouse to office area as shown on city approved drawings. Remove slide bolt lock that is installed on the northeast door of office area.
Justin Phone #: ###-####
|
FIR19-00838
| INSP-Final Inspection | 12/26/2019 | 12/27/2019 | 12/27/2019 9:58:05 AM | A | PASS |
|
|
Final fire sprinkler inspection for area of work complete.
Contact: Steven Vaughn Phone #: ###-#### Inspection requested via web by Hunter Fillmore
|
NAF19-00084
| INSP-Final | 12/26/2019 | 12/27/2019 | 12/27/2019 9:57:39 AM | A | FAIL |
|
|
Tenant needs to get seperate permit for occupancy, this permit is for vanilla shell only, no occpancy for this permit is stated in project description. East area of tenant (rear storage area) space has 2 sprinkler heads that are less than 6 foot apart, a minimum of 6 feet between heads is required per NFPA 13, verify sprinkler head spacing in storage area as well, possible overspaced sprinkler head. Insulation barrier paper is blocking/resting on numerous upright heads, insulation barrier needs adjusted for proper coverage of fire sprinkler heads as well as providing the minimum 1 inch clearance above head as required by NFPA 13. Area next to main entry, northside of door has a pocket created by plywood, fire sprinkler addition required to be code compliant, any and all modifications to fire sprinkler system will require a seperate permit. Provide annual inspection for fire extinguisher as discussed.
Call for access Phone #: 7025055936 >> Inspection requested via mobile web by Inis Smith
|
BLD19-02410
| FIRE-Final Inspection | 12/26/2019 | 12/27/2019 | 12/27/2019 8:36:07 AM | A | FAIL |
|
|
Called point of cotact listed with no answer, left a message, went to project and doors were locked, inspection was not performed, life fire safety inspection will need to be rescheduled, proceeded to next inspection.
Fire life safety final Phone #: ###-#### Inspection requested via web by Dustin Keyes
|
BLD18-02176
| FIRE-Final Inspection | 12/26/2019 | 12/27/2019 | 12/27/2019 8:21:01 AM | A | PART |
|
|
Previously noted items have been corrected with exception to the door that was notated by Troy, opticon sensors not in place for access gates but gates are left open for fire truck access until opticon is operational. Fire alarm inspection has been completed, fire sprinkler inspections have been completed, fire extinguishers are placed with current inspection tags. A partial final inspection for life fire safety is complete, per conversation with Ron Johnson, a 90 TCO is authorized for life fire safety.
Nacho Phone #: ###-####
|
FIR19-00353
| INSP-Sprinkler Rough-in | 12/26/2019 | 12/27/2019 | 12/27/2019 8:17:35 AM | A | FAIL |
|
|
Add thrust clips on hangers next to sprinkler heads or make all thread rod long enough to keep the sprinkler head from thrusting up during head activation as required for CPVC, inspection was stopped after multiple heads found without sprinkler head vertical restraint.
rough on 1st floor guest rooms. Thank you Sir have a great day Phone #: ###-#### Inspection requested via web by jeremiah robison
|