Inspections for the day of: Friday, December 28, 2018.
Number of inspections: 22
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD18-04417 FIRE-Final Inspection12/28/201812/28/201812/28/2018 4:17:46 PMPPART
Previously noted items for life fire safety inspection have been completed. Phone lines for fire panel monitoring were effected by Century Link failure so fire panel was showing a communication failure, per conversation with Ron Johnson a fire watch is recommended and a 15 day TCO is authorized contingent on phone lines being repaired and fire sprinkler monitoring is established.
BLD17-04686 FIRE-Final Inspection12/28/201812/28/201812/28/2018 4:11:23 PMPFAIL
Exposed combustible material in basement that is no covered by fire sprinklers. Need FIR permits for fire alarm and fire sprinkler finaled before life safety can be completed. Install sheetrock in level 1 elevator lobby, sprinkler head not installed because of no sheetrock. Provide signage for exterior showing which stairwell has roof top access and the one that does not. Still need to test emergency lighting.

Mop sink on level 4 leaked down to level 3 saturating the monitoring modules for the fire alarm system, leak needs to be fixed to prevent false alarms.

Pete Phone #: ###-####
FIR18-00420 INSP-Final Inspection12/27/201812/28/201812/28/2018 3:21:43 PMPFAIL
Multiple heads blocked in basement level. Could not test basement flow switch due to sump pump no keeping up with water flow. Exposed combustible material in basement level with no sprinkler protection.

Phone #: ###-#### Inspection requested via web by Matthew Lewis
FIR18-00162 INSP-Final Inspection12/27/201812/28/201812/28/2018 3:20:28 PMPFAIL
Did not have basement city approved drawings, horn strobe in basement was inoperable but couldn't tell if it was part of the TI system or part of core and shell.

derik Phone #: ###-####
FIR18-00741 INSP-Final Inspection12/28/201812/28/201812/28/2018 3:19:19 PMPPASS
Final fire sprinkler inspection for area of work complete.

Please call Lonnie before heading over to the project for the final inspection. Phone #: ###-#### Inspection requested via web by Daniel Buccino
BLD18-01913 FIRE-Final Inspection12/27/201812/28/201812/28/2018 12:16:38 PMAPASS
Smoke detector has been placed in bedroom, final life fire safety inspection for area of work complete.

Heidi Phone #: ###-####
BLD18-01064 FIRE-Final Inspection12/27/201812/28/201812/28/2018 12:03:35 PMPFAIL
Fire alarms are not complete, need fire alarms for phase 2 finaled. Phase 2 is not ready for life fire safety inspection.

Dave-2nd floor of phase 2 Phone #: ###-####
FIR18-00455 INSP-Alarm Testing12/28/201812/28/201812/28/2018 12:02:00 PMPFAIL
Provide3 notification in area between offices on southwest corner. Provide correct coverage in restrooms, currently restrooms have shadow issues. Clean up wiring on NAC panels, can't have wires hanging out of panel.

Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price
FIR18-00382 INSP-Sprinkler Rough-in12/27/201812/28/201812/28/2018 11:59:46 AMPPART
Rough to cover inspection for overhead fire sprinkler piping in phase 3 kitchen area and soffit in expansion area complete, approved for cover.

Rough to cover, server area - Zach Phone #: ###-####
FIR18-00684 INSP-Final Inspection12/27/201812/28/201812/28/2018 11:05:14 AMPPASS
Final fire sprinkler inspection for area of work complete.

Plans are on site Phone #: ###-#### Inspection requested via web by Sam Ball
FIR18-00708 INSP-Sprinkler Rough-in12/26/201812/28/201812/28/2018 11:04:25 AMAPART
Rough to cover inspection for overhead firte sprinkler piping on level 1 restroom/gym area complete. RTC for grid areas on level 1 complete, areas inspected approved for cover.

Contact is Mike Martin. Phone #: ###-#### Inspection requested via web by Stan Beus
FIR18-00708 INSP-Sprinkler Rough-in/Hydro12/27/201812/28/201812/28/2018 11:03:15 AMADONE
Hydrostatic test for level 1 witnessed, nio pressure loss observed.

Mike Phone #: ###-####
FIR18-00583 INSP-Final Inspection12/26/201812/28/201812/28/2018 11:01:34 AMAPASS
Final fire sprinkler inspection for level 2 complete.

Mike Martin is the contact. Phone #: ###-#### Inspection requested via web by Stan Beus
FIR18-00455 INSP-Alarm Testing12/27/201812/28/201812/28/2018 9:40:44 AMACANC
Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price Inspection cancelled via mobile web on Friday, December 28, 2018.
FIR18-00826 INSP-Sprinkler Rough-in12/28/201812/28/201812/28/2018 9:36:49 AMAPART
Rough to cover inspection for overehad fire sprinkler piping/tenting on north apartment units complete, approved for cover except unit B-HC on level 3, mentioned unit cannot be covered due to tenting issues.
FIR18-00826 INSP-Sprinkler Rough-in12/27/201812/28/201812/28/2018 9:33:40 AMAFAIL
Unit B-HC level 3 has exposed piping in the attis space where tenting was not installed correctly.

2nd half inspection. Gerarrdo is the contact. Phone #: ###-#### Inspection requested via web by Stan Beus
FIR18-00799 INSP-Final Inspection12/27/201812/28/201812/28/2018 9:02:08 AMAPASS
Final fire sprinkler inspection for area of work complete.

as per phone conversation
FIR18-00872 INSP-Sprinkler Rough-in12/28/201812/28/201812/28/2018 9:00:49 AMAPASS
Rouh to cover inspection for overehad fire sprinkler piping in area of work complete, area of work approved for cover.

FIR18-00872 INSP-Final Inspection12/27/201812/28/201812/28/2018 8:59:35 AMACANC
Project not ready for final inspection. This request is cancelled.

Jim Baker is the contact. Phone #: ###-#### Inspection requested via web by Stan Beus
BLD18-03965 FIRE-Final Inspection12/27/201812/28/201812/28/2018 8:47:16 AMAPART
Previously noted items have been completed except the fire alarm issue. 30 day TCO authorized by Ron Johnson for life fire safety contingent on fire alarm modification be completed.

Phone #: ###-#### Inspection requested via web by Tyson Jardine
BLD18-04372 FIRE-Final Inspection12/27/201812/28/201812/28/2018 8:35:36 AMAPASS
Final life fire safety inspection for area of work complete.

Zach Phone #: ###-####
FIR18-00420 INSP-Final Inspection12/27/201812/28/201812/27/2018 3:42:28 PMACANC
Phone #: ###-#### >> Inspection requested via web by Matthew Lewis Inspection cancelled from web by: Matthew Lewis