Inspections for the day of: Monday, December 30, 2019.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR19-00964 INSP-Final Inspection12/30/201912/30/201912/30/2019 3:55:50 PMPPASS
Final hood suppression system inspection is comlpete.

Phone #: ###-#### Inspection requested via web by Don Kartchner
FIR18-00858 INSP-Final Inspection12/27/201912/30/201912/30/2019 3:52:54 PMPPART
Walkthrough completed for remaining level 2 and basment level. Walkthrough not performed on level 1, base of A/V devices were masked for painting, could not see candella setting.

Call prior to going Phone #: 2086810381 >> Inspection requested via mobile web by Doug Lessa
BLD19-03277 FIRE-Final Inspection12/30/201912/30/201912/30/2019 3:31:59 PMPPASS
No fire sprinklers, no fire alarms, space is a vanilla finish so no fire extinguishers, final life fire safety inspection for vanilla TI complete, as stated in the project description, no occupancy allowed under this permit.

Matt Phone #: ###-####
BLD19-03521 FIRE-Final Inspection12/30/201912/30/201912/30/2019 2:52:39 PMPPASS
No fire sprinklers, no fire alarms, fire extinguishers are placed with current inspection tags. Final life fire safety inspection for area of work complete, signature provided on permit sign off card.

Sid Phone #: ###-####
BLD19-02869 FIRE-Final Inspection12/30/201912/30/201912/30/2019 2:36:36 PMPPASS
No fire sprinkler modifications, no fire alarm modificaitons, final life fire safety inspection for vanilla TI complete, signatures provided on permit sign off card. As noted it project description, no occupancy allowed under this permit.

Tom Phone #: ###-####
BLD19-04886 FIRE-Final Inspection12/30/201912/30/201912/30/2019 12:52:30 PMPPASS
No fire sprinklers, no fire alarms, fire extinguishers are placed with current inspection tags. Final life fire safety inspection complete, signature provided on permit sign off card.

Kim Phone #: ###-####
FIR19-00353 INSP-Sprinkler Rough-in12/30/201912/30/201912/30/2019 11:51:16 AMPFAIL
ADA room level 1 has open outlet above hard-lid, outlet is for sprinkler head in combustible concealed space behind bathtub, piping/head is not installed at time of inspection. Restraint clip for pendant fire sprinkler head in same ADA bathroom is not installed. Pipe size for electrical room (piping from double queen ext room, west of ADA room supplies electrical room) behind storage room shows 1 inch on city approved drawings, 1 1/2 pipe appears to be whats installed, not 1 inch as shown on drawings.

1st floor rooms drop ceilings. Thank you. Phone #: ###-#### Inspection requested via web by jeremiah robison
BLD19-04340 FIRE-Final Inspection12/27/201912/30/201912/30/2019 10:17:14 AMAPASS
Previously noted items have been corrected, fire sprinkler inspection is complete, no fire alarm modifications, fire extinguisher is placed with a current inspection tag. Final life fire safety inspection for scope of work complete.

Tom Phone #: ###-####
BLD19-03930 FIRE-Conference12/27/201912/30/201912/30/2019 9:50:23 AMADONE
Fire conference complete.

Rick Phone #: ###-####
BLD19-01927 FIRE-Conference12/24/201912/30/201912/30/2019 8:58:46 AMADONE
Fire conference complete.

Emergency light fixture layout, workstation furniture, additional signage requirements Phone #: ###-#### Inspection requested via web by Sam Reading
BLD19-03738 FIRE-Final Inspection12/27/201912/30/201912/30/2019 8:33:58 AMAPASS
No fire sprinklers, no fire alarms, fire extinguishers are placed with current inspection tags. Final life fire safety inspection for scope of work complete, signature provided on permit sign off card.

Tom Phone #: ###-####