Inspections for the day of: Thursday, December 5, 2019.
Number of inspections: 16
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR19-00896 INSP-Final Inspection12/3/201912/5/201912/5/2019 4:14:17 PMPFAIL
Manual pull station must comply with section 904.12.1 of the 2016 edition of the International Fire code.

Please call one hour prior to inspection.General has requested a 3:00 pm if possible to conform with other inspections Phone #: ###-#### Inspection requested via web by JJ Wallace
FIR19-00897 INSP-Final Inspection12/3/201912/5/201912/5/2019 4:14:02 PMPFAIL
Manual pull station must comply with section 904.12.1 of the 2016 edition of the International Fire code.

Please call one hour prior to inspection.General has requested a 3:00 pm if possible to conform with other inspections Phone #: ###-#### Inspection requested via web by JJ Wallace
FIR19-00898 INSP-Final Inspection12/3/201912/5/201912/5/2019 4:13:39 PMPFAIL
Manual pull station must comply with section 904.12.1 of the 2016 edition of the International Fire code.

Please call one hour prior to inspection.General has requested a 3:00 pm if possible to conform with other inspections Phone #: ###-#### Inspection requested via web by JJ Wallace
FIR19-00900 INSP-Final Inspection12/3/201912/5/201912/5/2019 4:13:23 PMPFAIL
Manual pull station must comply with section 904.12.1 of the 2016 edition of the International Fire code.

Please call one hour prior to inspection Phone #: ###-#### Inspection requested via web by JJ Wallace
FIR19-00901 INSP-Final Inspection12/3/201912/5/201912/5/2019 4:13:08 PMPFAIL
Manual pull station must comply with section 904.12.1 of the 2016 edition of the International Fire code.

Please call one hour prior to inspection. Phone #: ###-#### Inspection requested via web by JJ Wallace
FIR19-00899 INSP-Final Inspection12/4/201912/5/201912/5/2019 4:12:50 PMAFAIL
Manual pull station must comply with section 904.12.1 of the 2016 edition of the International Fire code.

Please call one hour prior to inspection Phone #: ###-#### Inspection requested via web by JJ Wallace
BLD19-03060 FIRE-Alarm Testing12/4/201912/5/201912/5/2019 1:18:04 PMPPART
All emergency lighting tested during this inspection, all fire exitnguishers are in place. Life fire safety cannot be signed off until FIR permit for fire alarms is finaled.

smoke test on 4 exterior RTU''s, ,life safety , EM lite test for full CO Phone #: ###-#### Inspection requested via web by Mark Coiner
FIR19-00708 INSP-Final Inspection12/4/201912/5/201912/5/2019 1:17:03 PMPPART
Fan shutdown on water flow verified. Will verify if all 4 RTU units need to shutdown during in duct smoke detector activation or if individual unti shutdown is approved.

Call prior to going Phone #: 2089546009 >> Inspection requested via mobile web by Kenny Leslie
FIR19-00580 INSP-Final Inspection12/5/201912/5/201912/5/2019 1:15:44 PMPNR
Charles Lamb is the contact. Thanks for all you do! Phone #: ###-#### Inspection requested via web by Stan Beus
BLD19-00294 FIRE-Final Inspection12/4/201912/5/201912/5/2019 12:20:08 PMPNR
Not ready for final life fire safety inspection, FIR19-00913 is for the in duct smoke detectors, FIR permit needs to scheduled, inspected and finaled before life fire safety will be completed.

Nate- after 2:30 please and call prior if possible Phone #: ###-####
FIR19-00868 INSP-Sprinkler Rough-in12/4/201912/5/201912/5/2019 10:34:56 AMAFAIL
Secire insulation that is resting on and blocking upright sprinkler heads above ceiling grid.

johnathon Phone #: ###-####
FIR19-00766 INSP-Sprinkler Rough-in12/3/201912/5/201912/5/2019 10:19:38 AMAFAIL
Inspection performed not knowing fees were due for pemit, tenting still not installed correctly, another re-inspection fee will be added.

Contact ken Orahood ###-#### 30 min prior to RTC Insp start please.

Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
FIR19-00658 INSP-Final Inspection12/4/201912/5/201912/5/2019 10:16:56 AMAFAIL
As per notes entered on 22NOV2019 conference, visual effects need to isolate during fire general fire alarm activation. Horn strobe by bar area is in different location than what is shown on the city approved drawings, A/V is a 75 candella, Horn strobe is oversapeced.

Phone #: ###-#### Inspection requested via web by Kristin Dolan
FIR19-00673 INSP-Final Inspection12/4/201912/5/201912/5/2019 10:14:29 AMAFAIL
Upright heads throughout space are painted, painted heads are not acceptable per NFPA13.

Damian Phone #: ###-####
BLD19-00278 FIRE-Conference12/3/201912/5/201912/5/2019 9:33:16 AMADONE
Fire conference complete.

Phone #: ###-#### Inspection requested via web by Corey Hockersmith
FIR19-00643 INSP-Sprinkler Rough-in/Hydro12/4/201912/5/201912/4/2019 12:54:46 PMACANC
Phone #: 2088990672 >> Inspection requested via mobile web by Josiah Inspection cancelled via mobile web on Wednesday, December 04, 2019.