Inspections for the day of: Friday, December 6, 2019.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR19-00892 INSP-Sprinkler Rough-in12/6/201912/6/201912/6/2019 2:28:15 PMPPASS
Rough to cover inspection for overhead fire sprinkler piping in scope of work complete, scope of work approved for cover.

Print on counter to left of entry lock box code 3266 Phone #: ###-#### Inspection requested via web by Sam Ball
BLD19-00294 FIRE-Final Inspection12/5/201912/6/201912/6/2019 1:26:26 PMANR
A stated in th 05DEC entry: Not ready for final life fire safety inspection, FIR19-00913 is for the in duct smoke detectors, FIR permit needs to scheduled, inspected and finaled before life fire safety will be completed. It is cooridnated to be completed the morning of 09DEC2019.

Nate Phone #: ###-####
BLD19-01312 FIRE-Final Inspection12/6/201912/6/201912/6/2019 1:24:47 PMPFAIL
Fire alarm panel has open circuit trouble on NAC circuit, panel needs to be normal for life fire safety inspection. A fire alarm vendor will need to be present for the life fire safety inspection, due to fire alarm devices being removed and re-installed during this scope of work a fire alarm test will be required to verify proper operation of fire alarm system in scope of work areas.

Tom Phone #: ###-####
FIR19-00562 INSP-Final Inspection12/6/201912/6/201912/6/2019 1:17:02 PMPPASS
Final fire sprinkler inspection for scope of work is complete.

Phone #: ###-#### Inspection requested via web by Matthew Lewis
FIR18-00152 INSP-Final Inspection12/6/201912/6/201912/6/2019 1:15:29 PMPPASS
Final inspection for AES communicator complete.
FIR18-00152 INSP-Alarm Testing12/6/201912/6/201912/6/2019 1:14:38 PMPPASS
AES testing complete.

Please call Kevin Brubaker Phone #: ###-#### Inspection requested via web by Jeff Gooch
FIR19-00672 INSP-Final Inspection12/5/201912/6/201912/6/2019 11:11:53 AMACANC
Point of contact not available when inspection could be completed, inspection request will need to be rescheduled, this request is cancelled.

Gabe is the contact. Thanks for all you do! Phone #: ###-#### Inspection requested via web by Stan Beus
FIR19-00846 INSP-Sprinkler Rough-in12/5/201912/6/201912/6/2019 10:34:12 AMAPASS
Rough to cover inspection for area of work complete, 3 hangers to be relocated due to incorrect install, hangers are in prep/employee only area, north side above ceiling grid. Will verify hanger correction during next inspection request, cover is approved.

Contact Fred Silva ###-#### 30 min prior to RTC Insp. start please.

Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
FIR19-00766 INSP-Conference12/5/201912/6/201912/6/2019 9:48:26 AMADONE
Fire conference is complete.

Contact Ken Orahood 08-###-#### 30 min prior to Conf Insp start please.

Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
BLD17-03344 FIRE-Final Inspection12/5/201912/6/201912/6/2019 9:18:16 AMAPASS
Final life fire safety inspection is complete.

Jason Phone #: ###-####
FIR18-00858 INSP-Final Inspection12/4/201912/6/201912/6/2019 9:17:24 AMAPART
Walk through complete for levels 4, 5 and 6, notated city approved plans with red ink for corrections.

Call prior to going Phone #: 2086810381 >> Inspection requested via mobile web by Doug Lessa