Inspections for the day of: Friday, December 7, 2018.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD18-01628 FIRE-Final Inspection12/7/201812/7/201812/7/2018 1:58:47 PMPFAIL
Install emergency egress lighting per city approved drawings, 7 emergency egress lights are missing. Install maximum occupancy placard.

vince Phone #: ###-####
FIR18-00770 INSP-Final Inspection12/7/201812/7/201812/7/2018 1:57:14 PMPPASS
Final fire sprinkler inspection for area of work complete.

Phone #: ###-#### Inspection requested via web by Sam Ball
FIR18-00878 INSP-Final Inspection12/7/201812/7/201812/7/2018 1:56:29 PMPPASS
Final fire alarm inspection for area of work complete.

This inspection could be scheduled the same time as today''s Life Safety inspection. Please call Mike at ###-#### with inspection time. Phone #: ###-#### Inspection requested via web by Lori Brungardt
FIR18-00455 INSP-Alarm Testing12/7/201812/7/201812/7/2018 1:00:50 PMAFAIL
Correct overspacing issues throughout level 3. Verify correct candela settings with city approved drawings. Numerous devices have the candele setting incorrect, candela settings need to match city approved drawings. A re-submittal will be required if devices are added to the fire alarm system that is not on the city approved drawings, to include candela adjustment outside of what is shown on city approved drawings. Correct shadowing issues that are throughout level 3. Correct overspacing issues with level 1 lobby A/V devices.



Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price
FIR18-00583 INSP-Sprinkler Rough-in12/7/201812/7/201812/7/2018 12:44:34 PMPPART
Rough to cover inspection for overhead fire sprinkler piping in sky-bridge link complete, approved for cover.

Tony Cetani is the contact. Phone #: ###-#### Inspection requested via web by Stan Beus
FIR18-00708 INSP-Sprinkler Rough-in12/6/201812/7/201812/7/2018 12:42:23 PMPPART
Rough to cover inspection for overehad fire sprinkler piping located above hardlids in restrooms complete, approved for cover.

to cover, 1st floor // Tony Phone #: ###-####
FIR18-00428 INSP-Final Inspection12/6/201812/7/201812/7/2018 12:41:35 PMPFAIL
TV monitors that are ceiling mounted are obstructing, correct obstruction issue.

Tony Phone #: ###-####
BLD18-02996 FIRE-Final Inspection12/6/201812/7/201812/7/2018 10:07:57 AMACANC
Chris Phone #: ###-####
BLD18-04395 FIRE-Final Inspection12/6/201812/7/201812/7/2018 9:21:43 AMAPASS
Final life fire safety inspection for area of work complete.

Sarah or Danielle Phone #: ###-####
FIR18-00686 INSP-Sprinkler Rough-in/Hydro12/6/201812/7/201812/7/2018 8:49:47 AMACANC
Inspextion request cancelled per conversation with Ron Larson.

Tony is point of contact, ###-####
FIR17-00612 INSP-Sprinkler Rough-in12/6/201812/7/201812/7/2018 8:48:47 AMAPART
Rough to cover inspection for overhead fire sprinkler piping in attic spaces on the east and west of high roof section on Rite Aid complete, approved for cover.

Jeff Chaney is the contact. Thank you for your help! Phone #: ###-#### Inspection requested via web by Stan Beus
BLD18-02751 FIRE-Final Inspection12/7/201812/7/201812/7/2018 12:00:00 AMPCANC
Tim Phone #: ###-####