Inspections for the day of: Friday, February 1, 2019.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD18-02909 FIRE-Final Inspection1/31/20192/1/20192/1/2019 3:41:32 PMPFAIL
Need to have tenant verify that the finishes in art exhibit rooms comply with chapter 7 of the International Fire Code. Fire sprinkler modifications are required for tenant space. Fire alarm modifications are required for tenant space. Any modifications to fire alarm and fire sprinkler system requires a permit. Provide fire extinguisher for proper coverage.

Jane Phone #: ###-####
BLD19-00339 FIRE-Final Inspection2/1/20192/1/20192/1/2019 3:03:48 PMPPASS
No fire sprinkler modifications, no fire alarm modifications, fire exitnguisher is placed with a current inspection tag (Fire extinguisher inspection will be required at the end of FEB2019), fire sprinkler inspection is current. Final life fire safety for area of work complete.

Call ahead // Amanda Phone #: ###-####
BLD19-00214 FIRE-Final Inspection2/1/20192/1/20192/1/2019 2:37:04 PMPPASS
No fire sprinkler mods, no firer alarm mods, fire exitnguishers are placed with current inspections tags, final life fire safety inspection complete.

Vicky-please go early if possible as the Bldg final is late pm today Phone #: ###-####
BLD18-00887 FIRE-Final Inspection1/31/20192/1/20192/1/2019 2:06:33 PMAFAIL
Exit signs have not been installed as discussed, provide exit signage as shown on city approved drawings.

request for final / TCO on Immanuel Lutheran Church.
Best access is usually off the alley.
Thank you. Phone #: ###-#### Inspection requested via web by Gary Band
FIR18-00852 INSP-Sprinkler Rough-in/Hydro1/30/20192/1/20192/1/2019 12:17:00 PMADONE
Hydrostatic test for overhead fire sprinkler piping on levels 3, 4 and 5 witnessed, no pressure loss observed.

Floors 3,4, and 5 Phone #: ###-#### Inspection requested via web by Matthew Lewis
FIR18-00495 INSP-Final Inspection1/31/20192/1/20192/1/2019 12:16:07 PMAPASS
Final inspection for clean agent system complete.

On Site Tech Jeremy Egbert - ###-#### Inspection requested via web by Eric Stanley
FIR18-00717 INSP-Final Inspection1/31/20192/1/20192/1/2019 11:15:22 AMAPASS
Previously noted items have been corrected, final fire alarm inspection complete.


Phone #: ###-#### Inspection requested via web by Ken Webster
FIR18-00686 INSP-Final Inspection1/31/20192/1/20192/1/2019 11:13:20 AMPPART
Partial final inspection for fire sprinkler system complete, flow switch currently reports in 7 seconds due to backflow issues, Backflow is going to be changed to allow a longer time frame for flow switch activation. Dry system trip will be completed after backflow is changed.

Gary Phone #: ###-####
FIR18-00955 INSP-Final Inspection1/31/20192/1/20192/1/2019 9:50:38 AMAPASS
Final fire alarm inspection for area of work complete.

Should be good to go. Neal ###-#### Phone #: ###-#### Inspection requested via web by Neal Timmerman