FIR19-00072
| INSP-Final Inspection | 2/11/2019 | 2/11/2019 | 2/11/2019 3:47:58 PM | P | PASS |
|
|
Final fire sprinkler inspection for area of work complete.
Adam Phone #: ###-####
|
FIR19-00072
| INSP-Sprinkler Rough-in | 2/11/2019 | 2/11/2019 | 2/11/2019 3:47:31 PM | P | PASS |
|
|
Rough to cover inspection for area of work complete, approved for cover.
Adam Phone #: ###-####
|
FIR19-00075
| INSP-Final Inspection | 2/8/2019 | 2/11/2019 | 2/11/2019 2:10:06 PM | P | FAIL |
|
|
Could not locate city approved drawings, need city approved drawings/documents to perform a correct inspection.
Dan Phone #: ###-####
|
FIR18-00336
| INSP-Sprinkler Rough-in/Hydro | 2/11/2019 | 2/11/2019 | 2/11/2019 12:05:19 PM | P | DONE |
|
|
Hydrostatic test for level 3 witnessed, no pressure loss observed.
Hydro on third floor Phone #: ###-#### Inspection requested via web by Sam Ball
|
BLD18-02909
| FIRE-Conference | 2/11/2019 | 2/11/2019 | 2/11/2019 10:52:33 AM | A | DONE |
|
|
Fire conference complete.
|
BLD18-02909
| FIRE-Final Inspection | 2/8/2019 | 2/11/2019 | 2/11/2019 10:52:05 AM | A | CANC |
|
|
Inspection request was for a conference, this request is cancelled.
Jane Phone #: ###-####
|
FIR19-00091
| INSP-Sprinkler Rough-in | 2/11/2019 | 2/11/2019 | 2/11/2019 9:47:23 AM | P | CANC |
|
|
UG Cover 2" Poly Troy Nelson Phone #: ###-#### >> Inspection requested via web by Nathan Stenquist Inspection cancelled from web by: Nathan Stenquist
|
BLD19-00382
| FIRE-Final Inspection | 2/8/2019 | 2/11/2019 | 2/11/2019 9:18:08 AM | A | FAIL |
|
|
Provide fire extinguishers in basement as well as level 1 as discussed, fire extinguishers are required to have an annual inspection tag with extinguisher to be code compliant.
Chris Phone #: ###-####
|
BLD19-00404
| FIRE-Final Inspection | 2/8/2019 | 2/11/2019 | 2/11/2019 8:45:53 AM | A | FAIL |
|
|
A wall has been added in area of tenant space that is not on the city approved drawings, need drawings updated with the city to show wall addition. Added wall has effected fire sprinkler coverage, fire sprinkler head is overspaced due to wall addition, any modifications to fire sprinkler system requires a permit.
Sharleen Phone #: ###-####
|