Inspections for the day of: Monday, February 11, 2019.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR19-00072 INSP-Final Inspection2/11/20192/11/20192/11/2019 3:47:58 PMPPASS
Final fire sprinkler inspection for area of work complete.

Adam Phone #: ###-####
FIR19-00072 INSP-Sprinkler Rough-in2/11/20192/11/20192/11/2019 3:47:31 PMPPASS
Rough to cover inspection for area of work complete, approved for cover.

Adam Phone #: ###-####
FIR19-00075 INSP-Final Inspection2/8/20192/11/20192/11/2019 2:10:06 PMPFAIL
Could not locate city approved drawings, need city approved drawings/documents to perform a correct inspection.

Dan Phone #: ###-####
FIR18-00336 INSP-Sprinkler Rough-in/Hydro2/11/20192/11/20192/11/2019 12:05:19 PMPDONE
Hydrostatic test for level 3 witnessed, no pressure loss observed.

Hydro on third floor Phone #: ###-#### Inspection requested via web by Sam Ball
BLD18-02909 FIRE-Conference2/11/20192/11/20192/11/2019 10:52:33 AMADONE
Fire conference complete.
BLD18-02909 FIRE-Final Inspection2/8/20192/11/20192/11/2019 10:52:05 AMACANC
Inspection request was for a conference, this request is cancelled.

Jane Phone #: ###-####
FIR19-00091 INSP-Sprinkler Rough-in2/11/20192/11/20192/11/2019 9:47:23 AMPCANC
UG Cover 2" Poly Troy Nelson Phone #: ###-#### >> Inspection requested via web by Nathan Stenquist Inspection cancelled from web by: Nathan Stenquist
BLD19-00382 FIRE-Final Inspection2/8/20192/11/20192/11/2019 9:18:08 AMAFAIL
Provide fire extinguishers in basement as well as level 1 as discussed, fire extinguishers are required to have an annual inspection tag with extinguisher to be code compliant.

Chris Phone #: ###-####
BLD19-00404 FIRE-Final Inspection2/8/20192/11/20192/11/2019 8:45:53 AMAFAIL
A wall has been added in area of tenant space that is not on the city approved drawings, need drawings updated with the city to show wall addition. Added wall has effected fire sprinkler coverage, fire sprinkler head is overspaced due to wall addition, any modifications to fire sprinkler system requires a permit.

Sharleen Phone #: ###-####