FIR18-00283
| INSP-Final Inspection | 2/11/2019 | 2/12/2019 | 2/12/2019 3:44:16 PM | P | PASS |
|
|
Final inspection for AES communicator complete.
Please call ahead of inspection so we can get alarm company on site for inspector. ###-#### Inspection requested via web by Bill Harmon
|
FIR18-00461
| INSP-Sprinkler Rough-in | 2/12/2019 | 2/12/2019 | 2/12/2019 3:32:14 PM | P | PART |
|
|
Blow in insulation for townhome attice spaces has been verified, attic spaces and under stair cavities have been filled with blow in, fire sprinkler pipng approved for cover. Rough to cover inspection for overhead fire sprinkler piping above hardlids in level 4 corridor complete, corridor hardlids with fire sprinkler piping above the sheetrock on level 4 approved for cover.
Town homes blow in insulation. Phone #: ###-#### Inspection requested via web by Sam Ball
|
FIR19-00091
| INSP-Sprinkler Rough-in | 2/12/2019 | 2/12/2019 | 2/12/2019 2:13:13 PM | P | PASS |
|
|
Rough to cover inspection for undergorund supply complete, approevd for cover.
UG Cover Troy Nelson Phone #: ###-#### Inspection requested via web by Nathan Stenquist
|
BLD18-04014
| FIRE-Final Inspection | 2/12/2019 | 2/12/2019 | 2/12/2019 1:57:25 PM | P | PASS |
|
|
Final life fire safety inspection for area of work complete.
|
FIR19-00078
| INSP-Conference | 2/8/2019 | 2/12/2019 | 2/12/2019 1:56:43 PM | P | DONE |
|
|
Fire conference complete.
Jim Phone #: ###-####
|
FIR19-00012
| INSP-Sprinkler Rough-in/Hydro | 2/11/2019 | 2/12/2019 | 2/12/2019 11:53:41 AM | A | CANC |
|
|
Temperature did not get above 40 degrees, hydro cancelled per conversarion with point of contact, inspection request will be rescheduled to coincide with allowable weather for hydrostatic test.
Phone #: ###-#### Inspection requested via web by jeremiah robison
|
BLD18-00887
| FIRE-Final Inspection | 2/12/2019 | 2/12/2019 | 2/12/2019 11:21:17 AM | A | FAIL |
|
|
No follow up inspection has been requested by the fire sprinkler contractor in regards to backflow/flow switch issue on the fire sprinkler system, FIR permits for the fire sprinkler system needs to be inspected and passed before life fire safety inspection. Life fire safety inspection will not be completed until FIR permits associated with this project are inspected, passed and the permits are finaled.
Missing exit lights installed per plan / request. F/L/S, re-inspection request, for final. best access off alley. Thank you Phone #: ###-#### Inspection requested via web by Gary Band
|
FIR19-00075
| INSP-Sprinkler Rough-in | 2/12/2019 | 2/12/2019 | 2/12/2019 11:02:28 AM | A | PASS |
|
|
Rough to cover inspection for overhead fire sprinkler piping in area of work complete, area of work approved for cover.
|
FIR19-00075
| INSP-Final Inspection | 2/12/2019 | 2/12/2019 | 2/12/2019 11:01:25 AM | P | CANC |
|
|
Tenant space is not ready for a final inspection, this request is cancelled.
Nick Phone #: ###-####
|
FIR18-00939
| INSP-Final Inspection | 2/12/2019 | 2/12/2019 | 2/12/2019 10:41:15 AM | A | PASS |
|
|
As-builts have been submitted and approved, final fire alarm inspection complete.
|
BLD18-01629
| FIRE-Final Inspection | 2/11/2019 | 2/12/2019 | 2/12/2019 10:33:53 AM | A | FAIL |
|
|
Access control door leading to space needs to comply with section 1010.1.9.8 of the 2015 IFC. Fire sprinkler head in space located by office is overspaced, fire sprinkler head needs to be added to be code compliant.
Larren Phone #: ###-####
|
BLD18-03429
| FIRE-Final Inspection | 2/11/2019 | 2/12/2019 | 2/12/2019 9:50:08 AM | A | PASS |
|
|
Fire sprinkler modifications are complete, no fire alarm modifications, fire extinguisher is placed with a current inspection tag. Final life fire safety inspection for vanilla TI complete, no occupancy under this permit.
Call 30 min befor for access Phone #: ###-#### Inspection requested via web by Tyson Jardine
|
FIR19-00043
| INSP-Final Inspection | 2/11/2019 | 2/12/2019 | 2/12/2019 9:48:50 AM | P | PASS |
|
|
Final fire sprinkler inspection for area of work complete.
Please call 30 minutes prior to arrival so we can let you into the space Phone #: ###-#### Inspection requested via web by Sam Ball
|
FIR19-00043
| INSP-Sprinkler Rough-in | 2/12/2019 | 2/12/2019 | 2/12/2019 9:48:20 AM | A | PASS |
|
|
Rough to cover inspection for overhead fire sprinkler piping in area of work complete, hard lid in restroom approved for cover.
|
FIR18-00891
| INSP-Sprinkler Rough-in | 2/11/2019 | 2/12/2019 | 2/12/2019 8:36:26 AM | A | FAIL |
|
|
Could not locate city approved drawings, piping is still covered, could not verify cover depth.
Cam Hess is the contact. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
|
FIR18-00889
| INSP-Sprinkler Rough-in | 2/11/2019 | 2/12/2019 | 2/12/2019 8:36:05 AM | A | FAIL |
|
|
Could not locate city approved drawings, piping is still covered, could not verify cover depth.
Cam Hess is the contact. Thank you! Phone #: ###-#### Inspection requested via web by Stan Beus
|
BLD18-03870
| FIRE-Final Inspection | 2/11/2019 | 2/12/2019 | 2/12/2019 8:08:42 AM | A | FAIL |
|
|
Need to have the fire sprinker issue resolved with fire department and plan review. Also need to test the fire alarm system in effected rooms due to possible issues with devices getting saturated.
Dave Phone #: ###-####
|
BLD18-04542
| FIRE-Final Inspection | 2/11/2019 | 2/12/2019 | 2/12/2019 8:03:20 AM | A | PASS |
|
|
No fire sprinkler modifications, no fire alarm modifications, fire extinguishers are placed with current inspection tags. Final life fire safety inspection for area of work complete.
Tom Phone #: ###-####
|
BLD18-04523
| FIRE-Final Inspection | 2/11/2019 | 2/12/2019 | 2/12/2019 8:03:00 AM | A | PASS |
|
|
No fire sprinkler modifications, no fire alarm modifications, fire extinguishers are placed with current inspection tags. Final life fire safety inspection for area of work complete.
Tom Phone #: ###-####
|
FIR18-00415
| INSP-Final Inspection | 2/12/2019 | 2/12/2019 | 2/12/2019 7:37:08 AM | A | PASS |
|
|
Final fire alarm inspection for area of work complete.
Please call 1/2 hour before arriving. Thanks Phone #: ###-#### Inspection requested via web by david davis
|
FIR18-00700
| INSP-Final Inspection | 2/12/2019 | 2/12/2019 | 2/12/2019 7:36:27 AM | A | PASS |
|
|
Final fire alarm inspection for area of work complete.
Please call 1/2 hour before arriving. Thanks Phone #: ###-#### Inspection requested via web by david davis
|
FIR19-00028
| INSP-Final Inspection | 2/11/2019 | 2/12/2019 | 2/12/2019 6:42:22 AM | A | PASS |
|
|
Previously noted items have been corrected, final fire alarm inspection for area of work complete.
As early as possible Phone #: 2085905075 >> Inspection requested via mobile web by Barney Sanders
|