Inspections for the day of: Thursday, February 14, 2019.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR18-00850 INSP-Final Inspection2/14/20192/14/20192/14/2019 2:38:41 PMPPASS
Final fire sprinkler inspection for area of work complete.

Phone #: ###-#### Inspection requested via web by jeremiah robison
BLD19-00336 FIRE-Final Inspection2/14/20192/14/20192/14/2019 1:22:02 PMPFAIL
Fire alarms in area of work are not code compliant, modifications to the fire alarm system will be required, any modification to the fire alarm system requires a permit. Provide exit lighting as well as emergency lighting per city approved drawings and notes number 15, 16 and 17 of building permit fire code review. Door hardware in area of work needs to comply with note number 5 of building permit fire code review comments. Smoke detectors are required per note number 7 of fire code review, smoke detectors in this building are monitored, a FIR permit will be required for fire alarm modifications. Provide electrical outlet covers per note number 4.

Sadi Phone #: ###-####
FIR19-00012 INSP-Sprinkler Rough-in/Hydro2/13/20192/14/20192/14/2019 12:39:46 PMPDONE
Hydrostatic test for newly installed overhead fire sprinkler piping witnessed, no pressure loss observed.

Phone #: ###-#### Inspection requested via web by jeremiah robison
FIR18-00850 INSP-Sprinkler Rough-in2/14/20192/14/20192/14/2019 10:50:17 AMAPASS
Rough to cover inspection for overhead fire sprinkler piping in area of work complete, approved for cover.
FIR18-00541 INSP-Sprinkler Rough-in2/13/20192/14/20192/14/2019 10:14:37 AMAPART
Rough to cover inspection for overhead fire sprinkler piping above hardlids complete, notated city approved drawings with red ink areas approved for cover.

Rick Phone #: ###-####
BLD18-02867 FIRE-Final Inspection2/13/20192/14/20192/14/2019 9:38:43 AMAPASS
Previously noted items have been corrected, final life fire safety inspection for area of work complete. In duct detectors are going to be removed during next remodel.

Rob Phone #: ###-####
FIR18-00956 INSP-Final Inspection2/13/20192/14/20192/14/2019 8:51:15 AMAPASS
Overspaced smoke detection has been corrected, final fire alarm inspection complete.

Phone #: ###-#### Inspection requested via web by Ken Webster