Inspections for the day of: Wednesday, February 20, 2019.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR18-00654 INSP-Supply line flush2/19/20192/20/20192/20/2019 2:40:42 PMPDONE
Undergournd main line flush complete.

Please call chris ford Phone #: ###-#### Inspection requested via web by Jessia Maxwell
BLD18-04312 FIRE-Final Inspection2/20/20192/20/20192/20/2019 2:40:10 PMPFAIL
Provide exit signage and emergency lighting on the southside enclosed patio. Provide emergency lighting in corridor between restrooms. Provide signage over the top of the main entry reading "Door to remain unlocked while building is occupied". South door swings the wrong direction for path of travel, need to correct door swing and install panic type door hardware per building fire code review comments. Place fire extinguishers in discussed locations.

Anthony Phone #: ###-####
FIR17-00508 INSP-Final Inspection2/20/20192/20/20192/20/2019 1:08:13 PMPCANC
Phone #: ###-#### >> Inspection requested via web by Gary Gambino Inspection cancelled from web by: Gary Gambino
BLD18-04113 FIRE-Final Inspection2/19/20192/20/20192/20/2019 11:08:38 AMAFAIL
FIR permit (FIR18-00963) for fire alarms is still in issued status during the time of entering these notes, FIR permit for fire alarms needs to be completed before life fire safety can be finaled.

Call 20 minutes before // Dan Phone #: ###-####
BLD19-00404 FIRE-Final Inspection2/20/20192/20/20192/20/2019 8:49:32 AMPPASS
Previously noted items have been corrected, final life fire safety inspection for area of work complete.

Paul Phone #: ###-####
FIR19-00075 INSP-Sprinkler Rough-in2/19/20192/20/20192/20/2019 8:48:55 AMPPASS
Final fire sprinkler inspection for area of work complete.

Raul Phone #: ###-####
FIR18-00930 INSP-Sprinkler Rough-in/Hydro2/19/20192/20/20192/20/2019 8:47:46 AMACANC
Hydrostatic test for overhead fire sprinkler piping in conapy has been cancelled, weather does not permit a hydrostatic test, temperature for hydrostaic tests needs to be maintained at 40 degrees or above for hydro to be accepted.

Zach Phone #: ###-####
FIR18-00930 INSP-Supply line flush2/19/20192/20/20192/20/2019 8:45:52 AMACANC
Inspection request was for a completion on the air test, not a main line flush, this request is cancelled.

air test // Zack Phone #: ###-####
FIR18-00930 INSP-Sprinkler Rough-in/Hydro2/20/20192/20/20192/20/2019 8:44:43 AMADONE
24 hour air test complete with no pressure loss witnessed.
FIR19-00107 INSP-Final Inspection2/19/20192/20/20192/20/2019 8:43:37 AMAPASS
Final fire sprinkler inspection for area of work complete.

Payton Phone #: ###-####
FIR19-00107 INSP-Sprinkler Rough-in2/20/20192/20/20192/20/2019 8:43:10 AMAPASS
Rough to cover inspection for overhead firte sprinkler piping in area of work complete, approved for cover.