BLD19-02339
| FIRE-Conference | 2/20/2020 | 2/20/2020 | 2/20/2020 10:39:44 AM | A | DONE |
|
|
Temporary standpipe has been placed and is in service.
|
FIR19-00804
| INSP-Sprinkler Rough-in | 2/20/2020 | 2/20/2020 | 2/20/2020 10:38:25 AM | P | DONE |
|
|
Temporary standpipe has been installed, located on the east side of building with temp stairs. Temp standpipe is in service.
Mike Phone #: ###-####
|
FIR19-00712
| INSP-Final Inspection | 2/20/2020 | 2/20/2020 | 2/20/2020 9:44:52 AM | P | PART |
|
|
Partial final inspection for scope of work has been completed. Project was reviewed under the 2015 IFC and the 2016 NFPA13 system. IFC Chapter 9, section 903.4 requires monitoring of fire sprinkler systems, this project does not meet any of the exceptions listed under 903.4. Fire sprinkler monitoring will be required due to the scope of work, a seperate FIR permit is required for any and all modifications to a fire alarm system.
Phone #: ###-#### Inspection requested via web by Sam Ball
|
FIR19-00489
| INSP-Sprinkler Rough-in | 2/19/2020 | 2/20/2020 | 2/20/2020 9:00:15 AM | A | PART |
|
|
Partial rough to cover inspection for overhead fire sprinkler piping complete, notated city approved drawings with red ink areas approved for cover.
Cole Bierman is the contact. Thanks for all you do! Phone #: ###-#### Inspection requested via web by Stan Beus
|
FIR19-00148
| INSP-Sprinkler Rough-in/Hydro | 2/19/2020 | 2/20/2020 | 2/20/2020 8:16:37 AM | A | PASS |
|
|
Hydrostatic test for underground supply complete, no pressure loss observed.
Tony Cetani is the contact. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
|
FIR20-00101
| INSP-Sprinkler Rough-in | 2/19/2020 | 2/20/2020 | 2/20/2020 8:15:55 AM | A | PASS |
|
|
Rough to cover inspection for overhead fire sprinkler piping in area of work complete, area of work approved for cover.
Tom Phone #: ###-####
|
FIR19-00489
| INSP-Sprinkler Rough-in | 2/19/2020 | 2/20/2020 | 2/19/2020 2:09:57 PM | P | CANC |
|
|
Cole Bierman is the contact. Thanks for all you do! Phone #: ###-#### >> Inspection requested via web by Stan Beus Inspection cancelled from web by: Stan Beus
|