BLD18-04312
| FIRE-Final Inspection | 2/21/2019 | 2/21/2019 | 2/21/2019 4:40:56 PM | P | PASS |
|
|
Previously noted items have been corrected, final life fire safety inspection complete.
Anthony Phone #: ###-####
|
FIR17-00508
| INSP-Final Inspection | 2/21/2019 | 2/21/2019 | 2/21/2019 4:40:08 PM | P | PART |
|
|
Finalm fire alarm inspection for TCO Phase 1 complete.
|
FIR17-00508
| INSP-Alarm Testing | 2/21/2019 | 2/21/2019 | 2/21/2019 4:39:27 PM | A | PART |
|
|
Alarm testing for TCO phase 1 complete.
Phone #: ###-#### Inspection requested via web by Gary Gambino
|
FIR19-00085
| INSP-Sprinkler Rough-in | 2/20/2019 | 2/21/2019 | 2/21/2019 3:15:15 PM | P | PART |
|
|
Rough to cover inspection for overhead fire sprinkler piping located above hardlids complete, notated city approved drawings with red ink areas approved for cover.
Ken Orahood is point of contact. Please call 30 minutes before inspection. Thank you. Phone #: ###-#### Inspection requested via web by Teri Cruickshank
|
FIR18-00673
| INSP-Sprinkler Rough-in | 2/20/2019 | 2/21/2019 | 2/21/2019 1:23:51 PM | P | PASS |
|
|
Rough to cover inspection for reamining pipe in main entry hallway complete, approved for cover.
hallway // Todd Phone #: ###-####
|
FIR18-00267
| INSP-Sprinkler Rough-in/Hydro | 2/20/2019 | 2/21/2019 | 2/21/2019 10:45:48 AM | A | PART |
|
|
Hydrostatic yesy for pump room, west standpipe and level 1 witnessed, no pressure loss observed.
Justin Phone #: ###-####
|