Inspections for the day of: Tuesday, February 25, 2020.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD18-01831 FIRE-Conference2/24/20202/25/20202/25/2020 3:28:35 PMPDONE
Fire conference complete.

Meet to pre-walk parking garage. Discuss TCO items, overall general items as we progress to final walks. Call Adam In advance. ###-####. Thanks, AKJ Phone #: ###-#### Inspection requested via web by Adam Johnson
FIR20-00117 INSP-Final Inspection2/24/20202/25/20202/25/2020 2:24:56 PMPPASS
Final fire alarm inspection for scope of work complete.

The ROC was emailed to Lee. Phone #: ###-#### Inspection requested via web by Jason Heath
FIR19-00614 INSP-Sprinkler Rough-in/Hydro2/24/20202/25/20202/25/2020 11:57:36 AMPCANC
Contact Tanner Loomis ###-#### 30 min prior to UG Hydro Insp start please.

Thank YOU Phone #: ###-#### >> Inspection requested via web by Teri Cruickshank Inspection cancelled from web by: Teri Cruickshank
BLD19-02706 FIRE-Final Inspection2/24/20202/25/20202/25/2020 10:41:14 AMACANC
FIR permit for fire alarms needs to be completed, see notes entered under FIR19-00948, after as-builts are received, reviewed and permit is back into issued status then the fire alarm permit can be finaled as well as life safety. Per conversation with point of contact, this request is cancelled and will be scheduled when FIR permit for fire alarms is complete.

Bill Phone #: ###-####
BLD19-01289 FIRE-Final Inspection2/25/20202/25/20202/25/2020 8:18:14 AMPPASS
Final life fire safety inspection for area of work complete.

Tom Phone #: ###-####
BLD18-04299 FIRE-Final Inspection2/25/20202/25/20202/25/2020 8:11:54 AMPPASS
Fire alarm issue has been resolved, final life fire safety inspection for area of work complete, signatures provided on permit sign off card.

Tom Phone #: ###-####
BLD18-04300 FIRE-Final Inspection2/25/20202/25/20202/25/2020 8:11:24 AMPPASS
Fire alarm issue has been resolved, final life fire safety inspection for area of work complete, signatures provided on permit sign off card.

Tom Phone #: ###-####
FIR19-00887 INSP-Final Inspection2/25/20202/25/20202/25/2020 8:10:13 AMPFAIL
Plastic sheeting is resting on top of sprinkler head. Insulation is resting on top of sprinkler head. Insulation hanging down around head below deflector. Plastic sheeting along west wall needs to be secured to the deck, plastic sheeting along west wall is hanging down preventing proper coverage for uprights.

Phone #: ###-#### Inspection requested via web by jeremiah robison
FIR19-00809 INSP-Sprinkler Rough-in2/25/20202/25/20202/25/2020 7:57:50 AMPFAIL
Multiple upright heads have been painted, per NFPA13 section 6.2.6.2, sprinklers shall only be painted by the sprinkler manufacturer. Quick response and standard response heads are in the same compartment area, per NFPA13 section 8.3.3 standard response and quick response shall not be in the same compartment.

give me a call before heading down Phone #: ###-#### Inspection requested via web by jeremiah robison
FIR19-00273 INSP-Final Inspection2/21/20202/25/20202/25/2020 7:14:30 AMAPASS
Previously noted items have been corrected, final fire alarm inspection for area of work complete.

Needs to be done at 7am. Phone #: ###-#### Inspection requested via web by James Williams
FIR18-00966 INSP-Final Inspection2/21/20202/25/20202/25/2020 7:13:35 AMAPASS
Previously noted items have been corrected, final fire alarm inspection for area of work complete.

Needs to be done at 7am. Phone #: ###-#### Inspection requested via web by James Williams
FIR19-00560 INSP-Final Inspection2/21/20202/25/20202/25/2020 7:12:24 AMAPASS
Final fire alarm inspection for scope of work is complete.

Needs to be done at 7am Phone #: ###-#### Inspection requested via web by James Williams
FIR20-00118 INSP-Final Inspection2/24/20202/25/20202/24/2020 10:46:55 AMACANC
Call before thanks,Jim Phone #: ###-#### >> Inspection requested via web by Jim Shilton Inspection cancelled from web by: Jim Shilton