FIR19-00096
| INSP-Sprinkler Rough-in | 2/27/2019 | 2/27/2019 | 2/27/2019 5:14:04 PM | P | PART |
|
|
Rough to cover inspection for overhead fire sprinkler piping located above hardlids complete, hardlids approved for cover.
Please give a heads up 30 min. if possible Phone #: ###-#### Inspection requested via web by jeremiah robison
|
FIR18-00610
| INSP-Sprinkler Rough-in | 2/26/2019 | 2/27/2019 | 2/27/2019 5:14:04 PM | A | PART |
|
|
Rough to cover inspection for overhead fire sprinkler piping on level 1 stairwell landings complete, approved for cover.
Cover inpection for first floor stairways only Cordinate with Mike Oswald ###-#### Phone #: ###-#### Inspection requested via web by Christophe Wilson
|
BLD18-02700
| FIRE-Final Inspection | 2/26/2019 | 2/27/2019 | 2/27/2019 12:53:31 PM | P | FAIL |
|
|
Dry system did not meet time requirements for valve trip.
Shane Phone #: ###-####
|
FIR19-00012
| INSP-Final Inspection | 2/26/2019 | 2/27/2019 | 2/27/2019 12:53:31 PM | P | FAIL |
|
|
Dry system did not meet time requirements for valve trip test.
Trip test Phone #: ###-#### Inspection requested via web by jeremiah robison
|
FIR19-00108
| INSP-Sprinkler Rough-in/Hydro | 2/26/2019 | 2/27/2019 | 2/27/2019 12:53:30 PM | A | DONE |
|
|
Hydrostatic test has been witnessed in areas where fire was located, no pressure loss observed.
Please call Tom with time frame. Because the system is existing we will pumping this up in small increments. We expect to be at 200 by 9 am. Phone #: ###-#### Inspection requested via web by Jeff Packham
|
FIR18-00564
| INSP-Sprinkler Rough-in | 2/26/2019 | 2/27/2019 | 2/27/2019 8:44:26 AM | A | PART |
|
|
Rough to cover inspection for overhead fire sprinkler piping/tenting/insulation complete in units 106, 108, 110, 202 and 204, approved for cover.
johnathon Phone #: ###-####
|
BLD18-04113
| FIRE-Final Inspection | 2/26/2019 | 2/27/2019 | 2/27/2019 8:41:06 AM | A | PASS |
|
|
Fire sprinkler inspection is complete, fire alarm inspection is complete, fire extinguisher is placed with a current inspection tag. Final life fire safety inspection for area of work complete.
Dan Phone #: ###-####
|