Inspections for the day of: Friday, February 28, 2020.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR19-00933 INSP-Sprinkler Rough-in2/27/20202/28/20202/28/2020 3:24:31 PMPFAIL
Notated city approved drawings with red ink area where upright heads are overspaced,inspection stopped after notation.

Rough in for first floor. Phone #: ###-#### Inspection requested via web by Sam Ball
BLD18-04075 FIRE-Final Inspection2/27/20202/28/20202/28/2020 3:23:24 PMPPASS
No fire sprinklers, no fire alarms, fire extinguiahers are placed with current inspection tags. Final life fire safety inspection for area of work complete, signature provided on permit sign off card.

electrical inspection is set for pm Phone #: ###-#### Inspection requested via web by chad stradley
BLD20-00509 FIRE-Final Inspection2/27/20202/28/20202/28/2020 12:37:27 PMPFAIL
Provide annual inspection on fire extinguisher as discussed. Note number 11 on the review comments requires signage on main entry reading "Door to remain unlocked while building is occupied".

Cory Phone #: ###-####
BLD19-03157 FIRE-Final Inspection2/27/20202/28/20202/28/2020 11:09:54 AMAPASS
Previously noted items have been corrected, spoke with Michael Hanson about round type door hardware on the east door as well as exit signage removal. Based on occupant load one exit is required, door hardware on east door will remain. Exit sigange has been removed as well due to not being required. Final life fire safety inspection is complete, signature provided on permit sign off card.

Santiago Phone #: ###-####
FIR19-00770 INSP-Final Inspection2/27/20202/28/20202/28/2020 10:37:25 AMAFAIL
Premit is under review as of these notes, final inspection cannot be performed until permit is back into issued status. According to SUEZ, water meter is a 5/8 water meter, not 1 inch as show on city approved documents.

Jon Beazer is the contact for this final inspection. Thank you for your help. Have a good day. Phone #: ###-#### Inspection requested via web by Stan Beus
BLD19-00822 FIRE-Conference2/28/20202/28/20202/28/2020 10:35:45 AMADONE
Need to verify coverings around screen, could not verify at time of conference. Sprinkler heads will need to be added if obstructions are installed above screen.
BLD19-00822 FIRE-Final Inspection2/27/20202/28/20202/28/2020 10:33:00 AMACANC
Request turned into a conference, this request is cancelled.

tyler Phone #: ###-####
FIR19-00468 INSP-Sprinkler Rough-in/Hydro2/27/20202/28/20202/28/2020 10:32:10 AMADONE
Hydrostatic test for overhead fire sprinkler piping on levels 1 and 2 witnessed, no pressure loss observed.

ROY IS OUR FOREMAN Phone #: ###-#### Inspection requested via web by Brad Bettencourt