Inspections for the day of: Thursday, February 7, 2019.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR19-00045 INSP-Sprinkler Rough-in2/7/20192/7/20192/7/2019 4:12:55 PMPPASS
Rough to cover inspection for undergorund supply complete, approved for cover.

Call Jim Page to verify he witness pipe installation back in 2018. The Shilo contact is Brian Collins. Thanks for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
FIR19-00032 INSP-Sprinkler Rough-in2/7/20192/7/20192/7/2019 4:12:39 PMPPASS
Rough to cover inspection for undergorund supply complete, approved for cover.

Call Jim Page to verify he witnessed pipe installation back in 2018. Shilo contact is Brian Collins. Thank you for everything you do! Phone #: ###-#### Inspection requested via web by Stan Beus
FIR19-00046 INSP-Sprinkler Rough-in2/7/20192/7/20192/7/2019 4:12:22 PMPPASS
Rough to cover inspection for undergorund supply complete, approved for cover.


Call Jim Page to verify he witnesses pipe installation back in 2018. The Shilo contact is Brian Collins. Thank you! Phone #: ###-#### Inspection requested via web by Stan Beus
FIR18-00699 INSP-Sprinkler Rough-in2/7/20192/7/20192/7/2019 4:12:04 PMPPASS
Rough to cover inspection for undergorund supply complete, approved for cover.

Call Jim Page to verify he witnessed pipe installation back in 2018. Shilo contact is Brian Collins. Thank you! Phone #: ###-#### Inspection requested via web by Stan Beus
FIR18-00939 INSP-Final Inspection2/6/20192/7/20192/7/2019 3:08:33 PMPFAIL
Fire alarm install does not match city approved drawings, re-submit drawings showing the current location of fire panel.

Buck Phone #: ###-####
FIR18-00679 INSP-Final Inspection2/6/20192/7/20192/7/2019 3:08:33 PMPPASS
Final fire sprinkler inspection for area of work complete.

Adam Phone #: ###-####
BLD18-01731 FIRE-Final Inspection2/6/20192/7/20192/7/2019 12:25:04 PMAPASS
No fire sprinklers, no fire alarm, fire extinguishers will be placed in discussed location and have current inspection tags. Final life fire safety inspection for area of work complete.

Will Phone #: ###-####
FIR18-00167 INSP-Final Inspection2/6/20192/7/20192/7/2019 11:58:47 AMAFAIL
Shielded wire not used on the install, per installation requirements shielded wire is required. Provide as builts showing that the AES is wired directly through to the panel and not through the DSC.





call for acess about 30 mins -Bill Phone #: ###-####
FIR19-00020 INSP-Sprinkler Rough-in2/6/20192/7/20192/7/2019 11:56:53 AMAPART
Rough to cover inspection for overehad fire sprinkler piping above hardlids complete, hardlids approved for cover.

Rough to cover Phone #: ###-#### Inspection requested via web by jeremiah robison
FIR18-00906 INSP-Sprinkler Rough-in2/6/20192/7/20192/7/2019 9:54:48 AMAPASS
All tenting in place at time of inspection, overhead fire sprinkler piping approved for cover.

Tenting Inspection Phone #: ###-#### Inspection requested via web by Anthony Minichiello
FIR18-00613 INSP-Final Inspection2/7/20192/7/20192/7/2019 9:27:06 AMPPASS
Plans mods have been approved, final fire alarm inspection for area of work complete.

Phone #: ###-#### Inspection requested via web by david davis
FIR18-00949 INSP-Final Inspection2/6/20192/7/20192/7/2019 9:26:30 AMAPASS
Final fire alarm inspection for scope of work complete.

Please call 1/2 hour before arriving. Thanks Phone #: ###-#### Inspection requested via web by david davis