Inspections for the day of: Friday, March 1, 2019.
Number of inspections: 22
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD19-00582 FIRE-Final Inspection3/1/20193/1/20193/1/2019 4:14:44 PMPFAIL
Service or replace exit signs and emergency lighting that is inoperable as discussed. Provide annual inspections for fire extinguishers, last inspection for extinguishers was 2016. Fire sprinkler system has a current inspection tag. Preaction fire sprinkler system riser is still in place but has been disconnected and removed from service, fire sprinkler piping on the preaction system has been converted to a wet system but valve trim is still in place. Change pendant fire sprinkler that is to close to wall to a vertical sidewall to be code compliant.

call ahead // Nick Phone #: ###-####
BLD17-04425 FIRE-Final Inspection2/28/20193/1/20193/1/2019 3:26:21 PMACANC
Rescheduled per conversation with point of contact.

Brandon Phone #: ###-####
BLD17-04413 FIRE-Final Inspection2/28/20193/1/20193/1/2019 3:26:06 PMACANC
Rescheduled per conversation with point of contact.

Brandon Phone #: ###-####
FIR19-00113 INSP-Sprinkler Rough-in3/1/20193/1/20193/1/2019 3:22:38 PMPPASS
Rough in inspection for scope of work complete.

tom Phone #: ###-####
BLD17-04483 FIRE-Final Inspection2/28/20193/1/20193/1/2019 2:33:00 PMAFAIL
Provide emergency exit discharge illuminatoin as stated in note number 7 of the building permit fire code review comments. Northeast exit door swings the wrong direction, swing is not with the path of travel, city approved drawings show door swinging with the exit path of travel.

7###-#### Kai
FIR19-00108 INSP-Final Inspection3/1/20193/1/20193/1/2019 2:03:11 PMPPASS
Final fire sprinkler inspection for scope of work complete.

Tom Small Phone #: ###-#### Inspection requested via web by Nathan Stenquist
FIR18-00908 INSP-Sprinkler Rough-in2/28/20193/1/20193/1/2019 2:02:38 PMPPASS
Rough to cover inspection for overhead fire sprinkler piping above drop in ceiling complete, approved for cover.

Please Call Roy Nelsen for contact. Phone #: ###-#### Inspection requested via web by Daniel Buccino
FIR18-00930 INSP-Sprinkler Rough-in/Hydro2/28/20193/1/20193/1/2019 2:01:50 PMPDONE
Hydrostatic test for canopy dry system witnessed, no pressure loss observed.

zack Phone #: ###-####
BLD19-00466 FIRE-Final Inspection2/28/20193/1/20193/1/2019 1:10:02 PMAPASS
No fire sprinkler modifications, no fire alarm modifications, fire extinguisher is placed with a current inspection tag. Final life fire safety inspection for area of work complete.

Lina Phone #: ###-####
BLD18-02512 FIRE-Final Inspection2/28/20193/1/20193/1/2019 12:02:32 PMAFAIL
Fire alamrs did not pass inspection, no life fire safety inspection was performed. Fire alarms must be inspected and passed before life fire safety inspection can be performed.

Pete Phone #: ###-####
BLD18-01753 FIRE-Final Inspection2/28/20193/1/20193/1/2019 12:01:15 PMAFAIL
Permit shows being under review at time of this request, no inspection was performed.
Fire alarms and fire sprinkler did not pass inspection.
Tom Phone #: ###-####
FIR18-00852 INSP-Final Inspection2/28/20193/1/20193/1/2019 12:00:04 PMPFAIL
Inspection for rough in was failed, reference notes provided under rough in inspection.

Phone #: ###-#### Inspection requested via web by jeremiah robison
FIR18-00852 INSP-Sprinkler Rough-in/Hydro2/28/20193/1/20193/1/2019 11:59:02 AMAFAIL
Add head in closet on 5 as discussed. City approved drawings do not show stair opening between 3 and 4, no head under stairs, could not verify space under landing, appears to be a combustible concealed space. Close spaced sprinkler heads may be required between levels.

Rough to cover Phone #: ###-#### Inspection requested via web by jeremiah robison
FIR18-00538 FIR-Aging Inspection3/1/20193/1/20193/1/2019 11:56:06 AMPPASS
Final inspection for underground supply complete.

can you final this yet?
FIR18-00825 INSP-Final Inspection2/28/20193/1/20193/1/2019 11:55:23 AMAFAIL
Drawings provided did not ahow notification in tenant space, provide correct city approved drawings.

Contact is Dirk. Phone #: ###-#### Inspection requested via web by Morgan Ahten
FIR18-00714 INSP-Final Inspection2/28/20193/1/20193/1/2019 11:54:28 AMAFAIL
Notated city approved drawings areas that need corrected, no alarms were activated due to deficiencies.

Contact is Dirk Phone #: ###-#### Inspection requested via web by Morgan Ahten
FIR18-00214 INSP-Final Inspection2/28/20193/1/20193/1/2019 11:51:56 AMAFAIL
Notated city approved drawings areas that need corrected, no alarms were activated due to deficiencies.

Contact is Dirk. Phone #: ###-#### Inspection requested via web by Morgan Ahten
FIR18-00213 INSP-Final Inspection2/28/20193/1/20193/1/2019 11:51:28 AMAFAIL
Notated city approved drawings areas that need corrected, no alarms were activated due to deficiencies.

Contact is Dirk. Phone #: ###-#### Inspection requested via web by Morgan Ahten
BLD18-00945 FIRE-Final Inspection2/28/20193/1/20193/1/2019 10:32:41 AMAFAIL
Fire alarm permit (FIR18-00644) associated with this project has not been inspected or finaled, fire alarm inspection needs to be completed and finaled before life fire safety inspection can be perfromed.ron Phone #: ###-####
BLD18-00887 FIRE-Final Inspection2/28/20193/1/20193/1/2019 10:30:16 AMAPASS
Final life fire safety inspection complete.

Request for Fire, life, Safety in conjunction with final sprinkler, alarm test, as scheduled by Larson Fire, Webster Alarm .
Best access usually in alley. Thank you. Phone #: ###-#### Inspection requested via web by Gary Band
FIR18-00686 INSP-Final Inspection2/28/20193/1/20193/1/2019 10:29:41 AMAPASS
Final fire sprinkler inspection complete.

Ron Phone #: ###-####
FIR18-00717 INSP-Final Inspection2/28/20193/1/20193/1/2019 10:29:04 AMAPASS
Final fire alarm inspection to include as-builts complete.

Buck Phone #: ###-####