Inspections for the day of: Tuesday, March 12, 2019.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD18-03600 FIRE-Final Inspection3/12/20193/12/20193/12/2019 2:05:26 PMPCANC
Fire alarms and hood suppression system inspection did not happen, this request is cancelled and will need to be rescheduled to coincide with fire alarm and hood suppression inspection.

call 10 mins ahead- Tyler Phone #: ###-####
FIR19-00037 INSP-Final Inspection3/11/20193/12/20193/12/2019 2:04:20 PMPCANC
Cancelled per point of contact.

Contact is Dirk. Phone #: ###-#### Inspection requested via web by Morgan Ahten
FIR19-00178 INSP-Final Inspection3/11/20193/12/20193/12/2019 2:03:57 PMPCANC
Cancelled per point of contact.

Final inspection for a Buckeye BFR-10 fire system. Phone #: ###-#### Inspection requested via web by Don Kartchner
FIR19-00020 INSP-Final Inspection3/11/20193/12/20193/12/2019 2:03:26 PMAPASS
Final fire sprinkler inspection for area of work complete.

Phone #: ###-#### Inspection requested via web by jeremiah robison
FIR17-00612 INSP-Final Inspection3/11/20193/12/20193/12/2019 1:42:36 PMPFAIL
Air compressor is not hard-wired in and is not on a dedicated circuit. Dry system needs to have a listed air maintenance device per 2016 NFPA 13, section 7.2.6.6.

Jeff Chaney is the contact for this final inspection. Thank you for your help. Have a nice day. Phone #: ###-#### Inspection requested via web by Stan Beus
FIR19-00098 INSP-Final Inspection3/12/20193/12/20193/12/2019 1:42:21 PMPNR
Dry systems are not ready to test, deficiencies on the fire sprinkler system needs to be corrected before fire alarm final.



Call prior to going Phone #: 2089546009 >> Inspection requested via mobile web by Kenny Leslie
FIR18-00824 INSP-Sprinkler Rough-in3/12/20193/12/20193/12/2019 11:26:50 AMAPART
Rough in inspection for overhead fire sprinkler piping complete, piping between conditioned spaces approved for cover. Tenting not completed at time of inspection, cover is n ot approved in tenting required areas.
FIR18-00824 INSP-Sprinkler Rough-in/Hydro3/12/20193/12/20193/12/2019 11:24:53 AMPDONE
Hydrostatic test for overhead fire sprinkler piping witnessed, no pressure loss observed.

Call Anthony before heading out Phone #: ###-#### Inspection requested via web by Anthony Minichiello
FIR18-00564 INSP-Sprinkler Rough-in3/12/20193/12/20193/12/2019 10:54:47 AMPPART
Rough to cover iospection for overhead fire sprinkler piping/tenting in units 102 and 112 complete, approved for cover.

Jonathan Phone #: ###-####
BLD19-00671 FIRE-Final Inspection3/11/20193/12/20193/12/2019 10:42:07 AMAFAIL
Provide annual inspection for fire extinguishers. Remove cabinet that reduces hallway width to 24 inches on mezzanine exit to stairs. Provide sticker on main entry reading "Door to remain unlocked while building is occupied". Provide addressing for suite.

Millie Phone #: ###-####
FIR18-00510 INSP-Sprinkler Rough-in3/11/20193/12/20193/12/2019 10:18:44 AMAPART
Rough to cover inspection for overhead fire sprinkler piping on 4 complete, level 4 approved for cover. Rough in inspection for level 5 complete, cover is not approved until tenting is installed and inspected, no cover is approved for level 5.

Rough-in for 4th and 5th floors Phone #: ###-#### Inspection requested via web by Sam Ball