BLD18-03600
| FIRE-Final Inspection | 3/12/2019 | 3/12/2019 | 3/12/2019 2:05:26 PM | P | CANC |
|
|
Fire alarms and hood suppression system inspection did not happen, this request is cancelled and will need to be rescheduled to coincide with fire alarm and hood suppression inspection.
call 10 mins ahead- Tyler Phone #: ###-####
|
FIR19-00037
| INSP-Final Inspection | 3/11/2019 | 3/12/2019 | 3/12/2019 2:04:20 PM | P | CANC |
|
|
Cancelled per point of contact.
Contact is Dirk. Phone #: ###-#### Inspection requested via web by Morgan Ahten
|
FIR19-00178
| INSP-Final Inspection | 3/11/2019 | 3/12/2019 | 3/12/2019 2:03:57 PM | P | CANC |
|
|
Cancelled per point of contact.
Final inspection for a Buckeye BFR-10 fire system. Phone #: ###-#### Inspection requested via web by Don Kartchner
|
FIR19-00020
| INSP-Final Inspection | 3/11/2019 | 3/12/2019 | 3/12/2019 2:03:26 PM | A | PASS |
|
|
Final fire sprinkler inspection for area of work complete.
Phone #: ###-#### Inspection requested via web by jeremiah robison
|
FIR17-00612
| INSP-Final Inspection | 3/11/2019 | 3/12/2019 | 3/12/2019 1:42:36 PM | P | FAIL |
|
|
Air compressor is not hard-wired in and is not on a dedicated circuit. Dry system needs to have a listed air maintenance device per 2016 NFPA 13, section 7.2.6.6.
Jeff Chaney is the contact for this final inspection. Thank you for your help. Have a nice day. Phone #: ###-#### Inspection requested via web by Stan Beus
|
FIR19-00098
| INSP-Final Inspection | 3/12/2019 | 3/12/2019 | 3/12/2019 1:42:21 PM | P | NR |
|
|
Dry systems are not ready to test, deficiencies on the fire sprinkler system needs to be corrected before fire alarm final.
Call prior to going Phone #: 2089546009 >> Inspection requested via mobile web by Kenny Leslie
|
FIR18-00824
| INSP-Sprinkler Rough-in | 3/12/2019 | 3/12/2019 | 3/12/2019 11:26:50 AM | A | PART |
|
|
Rough in inspection for overhead fire sprinkler piping complete, piping between conditioned spaces approved for cover. Tenting not completed at time of inspection, cover is n ot approved in tenting required areas.
|
FIR18-00824
| INSP-Sprinkler Rough-in/Hydro | 3/12/2019 | 3/12/2019 | 3/12/2019 11:24:53 AM | P | DONE |
|
|
Hydrostatic test for overhead fire sprinkler piping witnessed, no pressure loss observed.
Call Anthony before heading out Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
FIR18-00564
| INSP-Sprinkler Rough-in | 3/12/2019 | 3/12/2019 | 3/12/2019 10:54:47 AM | P | PART |
|
|
Rough to cover iospection for overhead fire sprinkler piping/tenting in units 102 and 112 complete, approved for cover.
Jonathan Phone #: ###-####
|
BLD19-00671
| FIRE-Final Inspection | 3/11/2019 | 3/12/2019 | 3/12/2019 10:42:07 AM | A | FAIL |
|
|
Provide annual inspection for fire extinguishers. Remove cabinet that reduces hallway width to 24 inches on mezzanine exit to stairs. Provide sticker on main entry reading "Door to remain unlocked while building is occupied". Provide addressing for suite.
Millie Phone #: ###-####
|
FIR18-00510
| INSP-Sprinkler Rough-in | 3/11/2019 | 3/12/2019 | 3/12/2019 10:18:44 AM | A | PART |
|
|
Rough to cover inspection for overhead fire sprinkler piping on 4 complete, level 4 approved for cover. Rough in inspection for level 5 complete, cover is not approved until tenting is installed and inspected, no cover is approved for level 5.
Rough-in for 4th and 5th floors Phone #: ###-#### Inspection requested via web by Sam Ball
|