Inspections for the day of: Thursday, March 14, 2019.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR19-00007 INSP-Sprinkler Rough-in3/13/20193/14/20193/14/2019 3:04:53 PMPPART
Rough in inspection for overhead fire sprinkler piping complete. Tenting was not installedf at time of inspection, cover is not approved until tenting is insected and passed.

Tenting at same time as rough-hydro. Phone #: ###-#### Inspection requested via web by Anthony Minichiello
FIR19-00007 INSP-Sprinkler Rough-in/Hydro3/13/20193/14/20193/14/2019 3:03:45 PMPDONE
Hydrostatic test for overhead fire sprinkler piping witnessed, no pressure loss observed.

Rough-hydro, call Anthony before heading out. Phone #: ###-#### Inspection requested via web by Anthony Minichiello
FIR18-00644 INSP-Final Inspection3/14/20193/14/20193/14/2019 2:44:08 PMPPART
Fire alarm audible device now meets the required NFPA 72 sound level requirements in the new kitchen area..

Final is for Kitchen Only. Contact is Dirk. Phone #: ###-#### Inspection requested via web by Morgan Ahten
BLD18-03381 FIRE-Final Inspection3/14/20193/14/20193/14/2019 1:59:09 PMPFAIL
Mag lock access control needs to be integrated with the fire alarm system for door release under general water flow alarm. Ceiling fan on main floor needs to be integrated with the fire alarm panel to shut down on general water flow alarm per manufacture instructions. Provide emergency egress lighting for exit discharge as shown on city approved drawings. Verfiy CFM of newly installed HVAC unit, if unit moves more than 2000CFM then an in-duct smoke detector will be required for unit shutdown. Modifications to the fire alarm system requires a permit.

Greg Phone #: ###-####
FIR18-00235 INSP-Final Inspection3/14/20193/14/20193/14/2019 1:02:19 PMPFAIL
Put panel into trouble, trouble signal was recieved at central station, sent a general alarm and trouble restored at central station. Issue needs to be resloved and panel needs to be tested with real events and not shorting contacts.

Jacob Phone #: ###-####
FIR18-00541 INSP-Sprinkler Rough-in/Hydro3/13/20193/14/20193/14/2019 12:32:36 PMADONE
Hydrostatic test for overhead fire sprinkler piping witnessed, no pressure loss observed.

Tom Phone #: ###-####
BLD18-02948 FIRE-Final Inspection3/14/20193/14/20193/14/2019 11:30:07 AMPPASS
Final life fire safety inspection for area of work complete.

kelly Phone #: ###-####
FIR18-00267 INSP-Sprinkler Rough-in3/13/20193/14/20193/14/2019 11:27:06 AMPPART
Rough to cover inspection for the remaining overhead fire sprinkler piping on level 3 complete, all of level 3 approved for cover. Overhead fire sprinkler piping above hardlids next to sky bridge inspected, piping above hardlids in inspected areas approved for cover.

Justin Phone #: ###-####
FIR18-00267 INSP-Sprinkler Rough-in/Hydro3/13/20193/14/20193/14/2019 11:24:12 AMPDONE
Hydrostatic test for three dry systems witnessed, no pressure loss observed.

Justin Phone #: ###-####
FIR19-00067 INSP-Sprinkler Rough-in3/14/20193/14/20193/14/2019 10:26:37 AMPPASS
Rough to cover inspection for undergorund supply complete, underground approved for cover.

Bryan Collins is the contact. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
FIR18-00565 INSP-Sprinkler Rough-in/Hydro3/13/20193/14/20193/14/2019 10:25:55 AMADONE
Hydrostatic test for overhead fire sprinkler piping witnessed, no pressure loss observed.

Johnathon Phone #: ###-####
FIR18-00564 INSP-Supply line flush3/13/20193/14/20193/14/2019 10:24:52 AMADONE
Underground main line flush complete.

Johnathon Phone #: ###-####