Inspections for the day of: Thursday, March 15, 2018.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR17-00474 INSP-Conference3/15/20183/15/20183/15/2018 2:08:33 PMPDONE
Discussed location for FDC, FDC will be installed on the eastern side of the north wall next to emergrncy exit door instead of the east wall.
FIR17-00474 INSP-Sprinkler Rough-in3/15/20183/15/20183/15/2018 2:07:07 PMPCANC
Request is for a conference, this request is cancelled.
FIR17-00760 INSP-Sprinkler Rough-in3/15/20183/15/20183/15/2018 2:06:24 PMPPASS
Rough to cover inspection for overhead fire sprinkler piping in area of work complete, area of work approved for cover.
FIR17-00733 INSP-Final Inspection3/14/20183/15/20183/15/2018 1:10:08 PMAFAIL
Flow switches on wet system fire sprinkler risers worked correctly. Audio visual notification did not sync correctly, audio visual devices will need to be re-inspected.
FIR18-00182 INSP-Sprinkler Rough-in3/14/20183/15/20183/15/2018 12:53:35 PMPPART
Rough to cover inspection for overhead fire sprinkler piping located above the hardlid complete, hardlid approved for cover.
FIR17-00647 INSP-Final Inspection3/15/20183/15/20183/15/2018 12:23:42 PMPPASS
Final fire sprinkler inspection complete.
FIR18-00004 INSP-Final Inspection3/14/20183/15/20183/15/2018 10:35:46 AMAPASS
Final fire alarm inspection complete.
BLD18-00593 FIRE-Final Inspection3/14/20183/15/20183/15/2018 9:11:39 AMAPART
Partial final inspection for life fire safety inspection complete, fire extinguishers are in place, no fire sprinklers and no fire alarms, kitchen hood fire suppression system has been finaled with the requirement of cooking appliances being installed per the layout of appliances provided by the commercial hood suppression contractor. Life fire safety cannot be finaled until appliances are in place.
BLD17-03588 FIRE-Final Inspection3/14/20183/15/20183/15/2018 8:53:42 AMAPASS
Fire sprinkler inspection complete, fire alarm inspection complete, fire extinguishers are in place with current inspection tags. Final life fire safety inspection complete.
FIR17-00647 INSP-Final Inspection3/14/20183/15/20183/15/2018 8:37:49 AMAFAIL
Fire sprinkler heads in room 133 are lees than 6 feet apart, a minimum of 6 feet between heads is required.
FIR18-00182 INSP-Sprinkler Rough-in3/14/20183/15/20183/14/2018 5:06:51 PMACANC
Phone #: ###-#### >> Inspection requested via web by Sam Ball Inspection cancelled from web by: Sam Ball