FIR17-00474
| INSP-Conference | 3/15/2018 | 3/15/2018 | 3/15/2018 2:08:33 PM | P | DONE |
|
|
Discussed location for FDC, FDC will be installed on the eastern side of the north wall next to emergrncy exit door instead of the east wall.
|
FIR17-00474
| INSP-Sprinkler Rough-in | 3/15/2018 | 3/15/2018 | 3/15/2018 2:07:07 PM | P | CANC |
|
|
Request is for a conference, this request is cancelled.
|
FIR17-00760
| INSP-Sprinkler Rough-in | 3/15/2018 | 3/15/2018 | 3/15/2018 2:06:24 PM | P | PASS |
|
|
Rough to cover inspection for overhead fire sprinkler piping in area of work complete, area of work approved for cover.
|
FIR17-00733
| INSP-Final Inspection | 3/14/2018 | 3/15/2018 | 3/15/2018 1:10:08 PM | A | FAIL |
|
|
Flow switches on wet system fire sprinkler risers worked correctly. Audio visual notification did not sync correctly, audio visual devices will need to be re-inspected.
|
FIR18-00182
| INSP-Sprinkler Rough-in | 3/14/2018 | 3/15/2018 | 3/15/2018 12:53:35 PM | P | PART |
|
|
Rough to cover inspection for overhead fire sprinkler piping located above the hardlid complete, hardlid approved for cover.
|
FIR17-00647
| INSP-Final Inspection | 3/15/2018 | 3/15/2018 | 3/15/2018 12:23:42 PM | P | PASS |
|
|
Final fire sprinkler inspection complete.
|
FIR18-00004
| INSP-Final Inspection | 3/14/2018 | 3/15/2018 | 3/15/2018 10:35:46 AM | A | PASS |
|
|
Final fire alarm inspection complete.
|
BLD18-00593
| FIRE-Final Inspection | 3/14/2018 | 3/15/2018 | 3/15/2018 9:11:39 AM | A | PART |
|
|
Partial final inspection for life fire safety inspection complete, fire extinguishers are in place, no fire sprinklers and no fire alarms, kitchen hood fire suppression system has been finaled with the requirement of cooking appliances being installed per the layout of appliances provided by the commercial hood suppression contractor. Life fire safety cannot be finaled until appliances are in place.
|
BLD17-03588
| FIRE-Final Inspection | 3/14/2018 | 3/15/2018 | 3/15/2018 8:53:42 AM | A | PASS |
|
|
Fire sprinkler inspection complete, fire alarm inspection complete, fire extinguishers are in place with current inspection tags. Final life fire safety inspection complete.
|
FIR17-00647
| INSP-Final Inspection | 3/14/2018 | 3/15/2018 | 3/15/2018 8:37:49 AM | A | FAIL |
|
|
Fire sprinkler heads in room 133 are lees than 6 feet apart, a minimum of 6 feet between heads is required.
|
FIR18-00182
| INSP-Sprinkler Rough-in | 3/14/2018 | 3/15/2018 | 3/14/2018 5:06:51 PM | A | CANC |
|
|
Phone #: ###-#### >> Inspection requested via web by Sam Ball Inspection cancelled from web by: Sam Ball
|