FIR17-00612
| INSP-Sprinkler Rough-in | 3/15/2018 | 3/16/2018 | 3/16/2018 2:25:36 PM | P | PART |
|
|
Rough to cover inspection for west side of system 2 complete, west side of system 2 approved for cover.
|
FIR18-00132
| INSP-Sprinkler Rough-in | 3/16/2018 | 3/16/2018 | 3/16/2018 2:24:56 PM | P | PASS |
|
|
Rough to cover inspection for underground supply complete, approved for cover.
|
FIR18-00016
| INSP-Final Inspection | 3/16/2018 | 3/16/2018 | 3/16/2018 2:24:22 PM | P | FAIL |
|
|
Could not perform inspection due to access issues, inspection will need to be rescheduled.
|
FIR18-00079
| INSP-Final Inspection | 3/15/2018 | 3/16/2018 | 3/16/2018 10:40:33 AM | A | PART |
|
|
Final fire sprinkler inspection for scope of work complete. A walk in freezer is located inside of the cooler, walk in freezer does not have fire sprinklers installed, freezer may possibly be removed, FIR permit for fire sprinklers cannot be finaled until freezer has sprinklers installed or until the freezer is removed.
|
FIR18-00079
| INSP-Sprinkler Rough-in | 3/15/2018 | 3/16/2018 | 3/16/2018 10:37:25 AM | A | PASS |
|
|
Rough in inspection for overhead fire sprinkler piping in scope of work complete.
|
FIR17-00746
| INSP-Final Inspection | 3/16/2018 | 3/16/2018 | 3/16/2018 10:03:02 AM | P | PASS |
|
|
Final fire alarm inspection complete.
|
FIR18-00142
| INSP-Final Inspection | 3/15/2018 | 3/16/2018 | 3/16/2018 10:02:33 AM | A | FAIL |
|
|
Tamper switchs and flow switch worked correctly, FDC identification plate needs installed on FDC connection, overhead doors need fire sprinkler protection installed underneath.
|
BLD18-00124
| FIRE-Final Inspection | 3/15/2018 | 3/16/2018 | 3/16/2018 9:31:58 AM | A | PASS |
|
|
No fire sprinkler modifications, no fire alarm modifications, fire extinguisher is in place with a current inspection tag. Final life fire safety inspection complete.
|
FIR18-00135
| INSP-Sprinkler Rough-in | 3/15/2018 | 3/16/2018 | 3/16/2018 8:50:13 AM | A | PASS |
|
|
Rough to cover inspection for overhead fire sprinkler piping in area of work complete, approved for cover.
|
FIR17-00317
| INSP-Sprinkler Rough-in | 3/15/2018 | 3/16/2018 | 3/16/2018 8:27:56 AM | A | PART |
|
|
Rough to cover inspection for overhead fire sprinkler piping located above hardlids on the east and south side of parking area complete, north side common area hardlids are complete, areas mentioned/inspected approved for cover. RTS-O sensors will need to be installed in the area around space heaters above parking garage hardlid to monitor temperature in case of heater failure, area above parking garage hardlids needs to be maintained at 40 degrees or higher at all times.
|
FIR18-00044
| INSP-Final Inspection | 3/15/2018 | 3/16/2018 | 3/16/2018 8:23:25 AM | A | PASS |
|
|
Final fire alarm inspection for area of work complete.
|