Inspections for the day of: Friday, March 16, 2018.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR17-00612 INSP-Sprinkler Rough-in3/15/20183/16/20183/16/2018 2:25:36 PMPPART
Rough to cover inspection for west side of system 2 complete, west side of system 2 approved for cover.
FIR18-00132 INSP-Sprinkler Rough-in3/16/20183/16/20183/16/2018 2:24:56 PMPPASS
Rough to cover inspection for underground supply complete, approved for cover.
FIR18-00016 INSP-Final Inspection3/16/20183/16/20183/16/2018 2:24:22 PMPFAIL
Could not perform inspection due to access issues, inspection will need to be rescheduled.
FIR18-00079 INSP-Final Inspection3/15/20183/16/20183/16/2018 10:40:33 AMAPART
Final fire sprinkler inspection for scope of work complete. A walk in freezer is located inside of the cooler, walk in freezer does not have fire sprinklers installed, freezer may possibly be removed, FIR permit for fire sprinklers cannot be finaled until freezer has sprinklers installed or until the freezer is removed.
FIR18-00079 INSP-Sprinkler Rough-in3/15/20183/16/20183/16/2018 10:37:25 AMAPASS
Rough in inspection for overhead fire sprinkler piping in scope of work complete.
FIR17-00746 INSP-Final Inspection3/16/20183/16/20183/16/2018 10:03:02 AMPPASS
Final fire alarm inspection complete.
FIR18-00142 INSP-Final Inspection3/15/20183/16/20183/16/2018 10:02:33 AMAFAIL
Tamper switchs and flow switch worked correctly, FDC identification plate needs installed on FDC connection, overhead doors need fire sprinkler protection installed underneath.
BLD18-00124 FIRE-Final Inspection3/15/20183/16/20183/16/2018 9:31:58 AMAPASS
No fire sprinkler modifications, no fire alarm modifications, fire extinguisher is in place with a current inspection tag. Final life fire safety inspection complete.
FIR18-00135 INSP-Sprinkler Rough-in3/15/20183/16/20183/16/2018 8:50:13 AMAPASS
Rough to cover inspection for overhead fire sprinkler piping in area of work complete, approved for cover.
FIR17-00317 INSP-Sprinkler Rough-in3/15/20183/16/20183/16/2018 8:27:56 AMAPART
Rough to cover inspection for overhead fire sprinkler piping located above hardlids on the east and south side of parking area complete, north side common area hardlids are complete, areas mentioned/inspected approved for cover. RTS-O sensors will need to be installed in the area around space heaters above parking garage hardlid to monitor temperature in case of heater failure, area above parking garage hardlids needs to be maintained at 40 degrees or higher at all times.
FIR18-00044 INSP-Final Inspection3/15/20183/16/20183/16/2018 8:23:25 AMAPASS
Final fire alarm inspection for area of work complete.