Inspections for the day of: Tuesday, March 17, 2020.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR19-00516 INSP-Sprinkler Rough-in3/16/20203/17/20203/17/2020 1:04:51 PMPPART
Rough to cover inspection for overhead fire sprinkler piping installed in floor joist cavity on levels 2 and 3 complete, piping located in floor joist cavity on levels 2 and 3 approved for cover, a follow up cover inspection will be required for piping above lowered ceilings.

Tony Cetani is the contact. The inspections are for the 2nd and 3rd floor. The inspector asks that it''ll be in the PM. Thanks! (: Phone #: ###-#### Inspection requested via web by Stan Beus
BLD19-04226 FIRE-Final Inspection3/17/20203/17/20203/17/2020 12:26:26 PMPCANC
Life fire safety inspection completed on 07JAN2020. No point of contact provided, this request is cancelled.
FIR19-00489 INSP-Sprinkler Rough-in3/17/20203/17/20203/17/2020 12:25:32 PMPPART
Partial rough to cover inspection for overhead fire sprinkler piping complete, notated city approved drawings with red ink areas approved for cover.

Aron Foster is the contact. Thanks! Have a great day Phone #: ###-#### Inspection requested via web by Stan Beus
BLD19-02810 FIRE-Final Inspection3/16/20203/17/20203/17/2020 9:31:42 AMAPASS
Final life fire safety inspection for area of work complete, signature provided on permit sign off card. As stated in project description, no occupancy allowed under this permit.

For Cert. of Completion only
Project has added 1 exit device, 1 egress light of which there were none previously. Phone #: ###-#### Inspection requested via web by mark nearman
FIR20-00109 INSP-Sprinkler Rough-in3/16/20203/17/20203/17/2020 8:59:13 AMPFAIL
Install does not match city approved drawings, plans were noted in a couple of areas but not all areas, re-submit will be required.

Jonathan Phone #: ###-####
BLD18-01083 FIRE-Final Inspection3/16/20203/17/20203/17/2020 8:28:49 AMAPASS
Previously noted items have been corrected, final life fire safety inspection is complete, signature card not available at time of inspection.

Mike Phone #: ###-####
FIR19-00800 INSP-Sprinkler Rough-in3/16/20203/17/20203/16/2020 3:34:01 PMPCANC
Tony Cetani is the contact. The Inspection will also be for the third floor. Thanks for all that you do! (: Phone #: ###-#### >> Inspection requested via web by Stan Beus Inspection cancelled from web by: Stan Beus