Inspections for the day of: Wednesday, March 18, 2020.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD19-04538 FIRE-Final Inspection3/18/20203/18/20203/18/2020 4:51:05 PMPCANC
Project related fire alarm permit needs to be finaled before life fire safety can be signed off, fire alarm inspection is schedule for 19MAR2020 per fire alarm vendor. This request is cancelled.

Phone #: ###-#### Inspection requested via web by Todd Kurns
BLD19-04544 FIRE-Final Inspection3/18/20203/18/20203/18/2020 4:49:40 PMPFAIL
Fire alarm modifications are required for space, new wall edition caused oversapcing issue with fire alarm, a seperate permit is required for fire alarm modifications.

Phone #: ###-#### Inspection requested via web by Todd Kurns
FIR20-00018 INSP-Final Inspection3/18/20203/18/20203/18/2020 1:50:31 PMPPASS
Final fire sprinkler inspection is complete.

jon Phone #: ###-####
BLD17-03010 FIRE-Final Inspection3/18/20203/18/20203/18/2020 1:15:26 PMPFAIL
Fire riser room is not a rated room as required by Boise Municipal Code, Chapter 7 Fire Prevention Code section 903.1.2. Provide building permit fire review comments for project, documents are required to be onsite, per conversation with point of contact they are not onsite. Install addressing that is compliant with 2016 IFC section 505, current addressing does not meet the requirements of section 505. Provide corner lot addressing as defined in the BMC Chapter 7 section 505.3. Provide fire extinguishers with current inspection tags for each unit, fire extingiushers can be mounted under the sink. Correct the addressing with the monitoring company.

Tim Phone #: ###-####
BLD17-03009 FIRE-Final Inspection3/18/20203/18/20203/18/2020 1:15:08 PMPFAIL
Fire riser room is not a rated room as required by Boise Municipal Code, Chapter 7 Fire Prevention Code section 903.1.2. Provide building permit fire review comments for project, documents are required to be onsite, per conversation with point of contact they are not onsite. Install addressing that is compliant with 2016 IFC section 505, current addressing does not meet the requirements of section 505. Provide corner lot addressing as defined in the BMC Chapter 7 section 505.3. Provide fire extinguishers with current inspection tags for each unit, fire extingiushers can be mounted under the sink. Correct the addressing with the monitoring company.

Tim Phone #: ###-####
FIR18-00891 INSP-Final Inspection3/17/20203/18/20203/18/2020 10:19:33 AMPPASS
Final underground supply inspection is complete.

Robert Chambers is the contact. Thanks Phone #: ###-#### Inspection requested via web by Stan Beus
FIR18-00889 INSP-Final Inspection3/17/20203/18/20203/18/2020 10:19:12 AMPPASS
Final underground supply inspection is complete.

Robert Chambers is the contact. Thanks (: Phone #: ###-#### Inspection requested via web by Stan Beus
FIR19-00280 INSP-Final Inspection3/17/20203/18/20203/18/2020 10:17:57 AMAPASS
Final fire sprinkler inspection is complete.

Please call Adam with time frame. Phone #: ###-#### Inspection requested via web by Jeff Packham
FIR19-00280 INSP-Sprinkler Rough-in/Hydro3/17/20203/18/20203/18/2020 10:17:25 AMADONE
Hydrostatic test witnessed at city pressure, no pressure loss observed.

Please call Adam with time frame. Phone #: ###-#### Inspection requested via web by Jeff Packham
FIR20-00093 INSP-Final Inspection3/17/20203/18/20203/18/2020 9:35:56 AMAPASS
Final inspection for scope of work is complete.

Phone #: ###-#### Inspection requested via web by Don Kartchner
FIR19-00705 INSP-Final Inspection3/17/20203/18/20203/18/2020 9:35:28 AMAPART
Fire alarm inspection for area of work complete, permit is submitted for as-builts to notated minor changes. System is installed per NFPA 72, after as-builts are approved permit can be finaled.

please call 1/2 hour prior. Thanks Phone #: ###-#### Inspection requested via web by Rick Groom
FIR20-00164 INSP-Sprinkler Rough-in3/17/20203/18/20203/18/2020 9:34:16 AMAPASS
Rough to cover inspection for scope of work complete, cover is approved.

Randy Knutson is the contact Phone #: ###-#### Inspection requested via web by Stan Beus