BLD19-04538
| FIRE-Final Inspection | 3/18/2020 | 3/18/2020 | 3/18/2020 4:51:05 PM | P | CANC |
|
|
Project related fire alarm permit needs to be finaled before life fire safety can be signed off, fire alarm inspection is schedule for 19MAR2020 per fire alarm vendor. This request is cancelled.
Phone #: ###-#### Inspection requested via web by Todd Kurns
|
BLD19-04544
| FIRE-Final Inspection | 3/18/2020 | 3/18/2020 | 3/18/2020 4:49:40 PM | P | FAIL |
|
|
Fire alarm modifications are required for space, new wall edition caused oversapcing issue with fire alarm, a seperate permit is required for fire alarm modifications.
Phone #: ###-#### Inspection requested via web by Todd Kurns
|
FIR20-00018
| INSP-Final Inspection | 3/18/2020 | 3/18/2020 | 3/18/2020 1:50:31 PM | P | PASS |
|
|
Final fire sprinkler inspection is complete.
jon Phone #: ###-####
|
BLD17-03010
| FIRE-Final Inspection | 3/18/2020 | 3/18/2020 | 3/18/2020 1:15:26 PM | P | FAIL |
|
|
Fire riser room is not a rated room as required by Boise Municipal Code, Chapter 7 Fire Prevention Code section 903.1.2. Provide building permit fire review comments for project, documents are required to be onsite, per conversation with point of contact they are not onsite. Install addressing that is compliant with 2016 IFC section 505, current addressing does not meet the requirements of section 505. Provide corner lot addressing as defined in the BMC Chapter 7 section 505.3. Provide fire extinguishers with current inspection tags for each unit, fire extingiushers can be mounted under the sink. Correct the addressing with the monitoring company.
Tim Phone #: ###-####
|
BLD17-03009
| FIRE-Final Inspection | 3/18/2020 | 3/18/2020 | 3/18/2020 1:15:08 PM | P | FAIL |
|
|
Fire riser room is not a rated room as required by Boise Municipal Code, Chapter 7 Fire Prevention Code section 903.1.2. Provide building permit fire review comments for project, documents are required to be onsite, per conversation with point of contact they are not onsite. Install addressing that is compliant with 2016 IFC section 505, current addressing does not meet the requirements of section 505. Provide corner lot addressing as defined in the BMC Chapter 7 section 505.3. Provide fire extinguishers with current inspection tags for each unit, fire extingiushers can be mounted under the sink. Correct the addressing with the monitoring company.
Tim Phone #: ###-####
|
FIR18-00891
| INSP-Final Inspection | 3/17/2020 | 3/18/2020 | 3/18/2020 10:19:33 AM | P | PASS |
|
|
Final underground supply inspection is complete.
Robert Chambers is the contact. Thanks Phone #: ###-#### Inspection requested via web by Stan Beus
|
FIR18-00889
| INSP-Final Inspection | 3/17/2020 | 3/18/2020 | 3/18/2020 10:19:12 AM | P | PASS |
|
|
Final underground supply inspection is complete.
Robert Chambers is the contact. Thanks (: Phone #: ###-#### Inspection requested via web by Stan Beus
|
FIR19-00280
| INSP-Final Inspection | 3/17/2020 | 3/18/2020 | 3/18/2020 10:17:57 AM | A | PASS |
|
|
Final fire sprinkler inspection is complete.
Please call Adam with time frame. Phone #: ###-#### Inspection requested via web by Jeff Packham
|
FIR19-00280
| INSP-Sprinkler Rough-in/Hydro | 3/17/2020 | 3/18/2020 | 3/18/2020 10:17:25 AM | A | DONE |
|
|
Hydrostatic test witnessed at city pressure, no pressure loss observed.
Please call Adam with time frame. Phone #: ###-#### Inspection requested via web by Jeff Packham
|
FIR20-00093
| INSP-Final Inspection | 3/17/2020 | 3/18/2020 | 3/18/2020 9:35:56 AM | A | PASS |
|
|
Final inspection for scope of work is complete.
Phone #: ###-#### Inspection requested via web by Don Kartchner
|
FIR19-00705
| INSP-Final Inspection | 3/17/2020 | 3/18/2020 | 3/18/2020 9:35:28 AM | A | PART |
|
|
Fire alarm inspection for area of work complete, permit is submitted for as-builts to notated minor changes. System is installed per NFPA 72, after as-builts are approved permit can be finaled.
please call 1/2 hour prior. Thanks Phone #: ###-#### Inspection requested via web by Rick Groom
|
FIR20-00164
| INSP-Sprinkler Rough-in | 3/17/2020 | 3/18/2020 | 3/18/2020 9:34:16 AM | A | PASS |
|
|
Rough to cover inspection for scope of work complete, cover is approved.
Randy Knutson is the contact Phone #: ###-#### Inspection requested via web by Stan Beus
|