FIR19-00751
| INSP-Final Inspection | 3/19/2020 | 3/19/2020 | 3/19/2020 4:28:02 PM | P | PART |
|
|
Final fire sprinkler inspection for TCO phase 1 complete.
|
FIR19-00751
| INSP-Sprinkler Rough-in | 3/19/2020 | 3/19/2020 | 3/19/2020 4:27:14 PM | P | CANC |
|
|
Inspection was for TCO phase 1 final inspection, this request is cancelled.
Rick Phone #: ###-####
|
BLD19-04538
| FIRE-Final Inspection | 3/18/2020 | 3/19/2020 | 3/19/2020 2:36:55 PM | P | PASS |
|
|
Fire sprinkler inspection is complete, fire alarm inspection is complete, fire extinguishers are placed with current inspection tags. Final life fire safety inspection for area of work is complete, no signature card available at time of inspection.
Jim,
I have two fire extinguishers to hang. If I''m not there, set them where u would like to see them and I will hang them.
Thanks,
Todd Phone #: ###-#### Inspection requested via web by Todd Kurns
|
FIR20-00021
| INSP-Final Inspection | 3/18/2020 | 3/19/2020 | 3/19/2020 2:35:30 PM | P | PASS |
|
|
Final fire alarm inspection for area of work is complete.
We would like to have the inspection done at 1:00 pm if possible. Please call Nate at ###-#### with inspection time. Phone #: ###-#### Inspection requested via web by Lori Brungardt
|
FIR19-00855
| INSP-Final Inspection | 3/18/2020 | 3/19/2020 | 3/19/2020 12:27:28 PM | A | FAIL |
|
|
Room labeled closet off of level 2 bonus room has washer and dryer hook-ups added, per 2016 NFPA13D section 8.3.8 requires sprinkler protection in areas containing washer/dryers, a cover inspection will be required for tenting verification.
Call James before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
FIR19-00845
| INSP-Final Inspection | 3/19/2020 | 3/19/2020 | 3/19/2020 12:26:17 PM | A | FAIL |
|
|
Texted point of contact at 11:06AM with no response, attempted to call point of contact at 11:30AM with no answer, could not leave a message because voicemail was full. Final fire sprinkler inspection needs to be coordinated with the alarm vendor, this request will need to be rescheduled, procceeded to next inspection. Due to the second fail a reinspection fee has been added to the permit.
Raul is the contact Phone #: ###-#### Inspection requested via web by Chris Green
|
BLD19-01594
| FIRE-Final Inspection | 3/19/2020 | 3/19/2020 | 3/19/2020 12:21:41 PM | P | FAIL |
|
|
Associated FIR permits for fire alarm and fire sprinkler are not finaled, FIR permits must be finaled before life fire safety inspection can be performed.
Bo Phone #: ###-####
|
FIR20-00065
| INSP-Sprinkler Rough-in | 3/19/2020 | 3/19/2020 | 3/19/2020 10:16:15 AM | P | FAIL |
|
|
Level 1 kitchen and hallway, hallway head does not extend past the corner of wall as shown on city approved drawings, due to head not being past the wall the kitchen heads in 2 units are overspaced, inspection stopped.
Overhead rough ; tenting, call James before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
FIR20-00066
| INSP-Sprinkler Rough-in | 3/19/2020 | 3/19/2020 | 3/19/2020 10:14:43 AM | P | FAIL |
|
|
Open 1 1/2 outlet and 1 inch outlet open above finish ceiling, inspection stopped.
Overhead rough ; tenting, call James before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
BLD19-04908
| FIRE-Final Inspection | 3/16/2020 | 3/19/2020 | 3/19/2020 9:05:54 AM | A | PASS |
|
|
Fire sprinkler inspection is complete, fire alarm inspection is complete, fire extinguisher will be placed in discussed location and has a current inspection tag. Final life fire safety inspection for area of work complete, signatures provided on permit sign off card.
Doug Phone #: ###-####
|
FIR20-00059
| INSP-Final Inspection | 3/17/2020 | 3/19/2020 | 3/19/2020 9:04:21 AM | A | PASS |
|
|
Final fire alarm inspection for area of work complete.
please call 1/2hour prior. Thanks Phone #: ###-#### Inspection requested via web by Rick Groom
|
BLD17-03009
| FIRE-Final Inspection | 3/18/2020 | 3/19/2020 | 3/19/2020 8:21:16 AM | A | PASS |
|
|
Previously noted items have been corrected, fire sprinkler inspection is complete, fire alarm inspection is complete, fire extinguishers are placed with current inspection tags. Final life fire safety inspection complete, signature card not available at time of inspection.
Tim Phone #: ###-####
|
BLD17-03010
| FIRE-Final Inspection | 3/18/2020 | 3/19/2020 | 3/19/2020 8:20:49 AM | A | PASS |
|
|
Previously noted items have been corrected, fire sprinkler inspection is complete, fire alarm inspection is complete, fire extinguishers are placed with current inspection tags. Final life fire safety inspection complete, signature card not available at time of inspection.
Tim Phone #: ###-####
|