Inspections for the day of: Thursday, March 21, 2019.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR18-00815 INSP-Final Inspection3/20/20193/21/20193/21/2019 3:06:07 PMPFAIL
Pull station in riser room mounted to low. Provide city approved drawings and small documents, no city approved drawings on site. Provide document cabinet at fire panel. Provide map showing initiating devices. Only item tested is the commercial hood interface, hood suppression system reports to panel.

Partial Final for cafeteria and commons. Contact is Dan. Phone #: ###-#### Inspection requested via web by Morgan Ahten
FIR19-00150 INSP-Final Inspection3/19/20193/21/20193/21/2019 3:06:06 PMPPASS
Final hood suppression system inspection complete.

Brittany Phone #: ###-####
FIR19-00018 INSP-Final Inspection3/19/20193/21/20193/21/2019 1:28:16 PMPFAIL
Escutcheon does cover entire hole from sprinkler penetration in numerous areas. Exposed CPVC from backflow to riser needs to be changed, cannot have exposed CPVC. Provide 911 signage on fire bell. Irrigation shutdown not wired correctly.

Call before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
FIR18-00804 INSP-Sprinkler Rough-in/Hydro3/21/20193/21/20193/21/2019 12:44:37 PMPPART
Rough in inspection for wings A & B complete.

This Rough-in/hydro is for wings A ; B. The contact is Richard Clark. Thank your for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
FIR18-00235 INSP-Final Inspection3/20/20193/21/20193/21/2019 11:41:43 AMAFAIL
Valve on fire sprinkler system reports out as a trouible, when fire alarm panel is in trouble, each subsequent trouble does not report out until panel is reset.

Bill Phone #: ###-####
FIR18-00510 INSP-Conference3/20/20193/21/20193/21/2019 10:13:38 AMADONE
Fire conference complete. Installing contractor and designer had a discussion with Tim Frost over the small soffit areas in corridors, based on the information provided heads will not be required in the small soffits above the suite entries in the corridor, corridor protection (provided the sprinkler heads are installed center of corridor) is sufficient.

Questions on 2 nd floor Phone #: ###-#### Inspection requested via web by Sam Ball
FIR19-00089 INSP-Final Inspection3/18/20193/21/20193/21/2019 10:09:43 AMAFAIL
Provide notitification in quiet rooms, no notification in quiet rooms at time of inspection.

Phone #: ###-#### Inspection requested via web by Brian Richard