FIR18-00815
| INSP-Final Inspection | 3/20/2019 | 3/21/2019 | 3/21/2019 3:06:07 PM | P | FAIL |
|
|
Pull station in riser room mounted to low. Provide city approved drawings and small documents, no city approved drawings on site. Provide document cabinet at fire panel. Provide map showing initiating devices. Only item tested is the commercial hood interface, hood suppression system reports to panel.
Partial Final for cafeteria and commons. Contact is Dan. Phone #: ###-#### Inspection requested via web by Morgan Ahten
|
FIR19-00150
| INSP-Final Inspection | 3/19/2019 | 3/21/2019 | 3/21/2019 3:06:06 PM | P | PASS |
|
|
Final hood suppression system inspection complete.
Brittany Phone #: ###-####
|
FIR19-00018
| INSP-Final Inspection | 3/19/2019 | 3/21/2019 | 3/21/2019 1:28:16 PM | P | FAIL |
|
|
Escutcheon does cover entire hole from sprinkler penetration in numerous areas. Exposed CPVC from backflow to riser needs to be changed, cannot have exposed CPVC. Provide 911 signage on fire bell. Irrigation shutdown not wired correctly.
Call before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
FIR18-00804
| INSP-Sprinkler Rough-in/Hydro | 3/21/2019 | 3/21/2019 | 3/21/2019 12:44:37 PM | P | PART |
|
|
Rough in inspection for wings A & B complete.
This Rough-in/hydro is for wings A ; B. The contact is Richard Clark. Thank your for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
|
FIR18-00235
| INSP-Final Inspection | 3/20/2019 | 3/21/2019 | 3/21/2019 11:41:43 AM | A | FAIL |
|
|
Valve on fire sprinkler system reports out as a trouible, when fire alarm panel is in trouble, each subsequent trouble does not report out until panel is reset.
Bill Phone #: ###-####
|
FIR18-00510
| INSP-Conference | 3/20/2019 | 3/21/2019 | 3/21/2019 10:13:38 AM | A | DONE |
|
|
Fire conference complete. Installing contractor and designer had a discussion with Tim Frost over the small soffit areas in corridors, based on the information provided heads will not be required in the small soffits above the suite entries in the corridor, corridor protection (provided the sprinkler heads are installed center of corridor) is sufficient.
Questions on 2 nd floor Phone #: ###-#### Inspection requested via web by Sam Ball
|
FIR19-00089
| INSP-Final Inspection | 3/18/2019 | 3/21/2019 | 3/21/2019 10:09:43 AM | A | FAIL |
|
|
Provide notitification in quiet rooms, no notification in quiet rooms at time of inspection.
Phone #: ###-#### Inspection requested via web by Brian Richard
|