BLD19-00675
| FIRE-Final Inspection | 3/21/2019 | 3/25/2019 | 3/25/2019 1:23:12 PM | A | PASS |
|
|
No fire sprinklers, no fire alarms, fire exitnguisher is placed with a current inspection tag. Final life fire safety inspection complete.
Lesley Phone #: ###-####
|
BLD18-01629
| FIRE-Final Inspection | 3/25/2019 | 3/25/2019 | 3/25/2019 12:59:15 PM | P | CANC |
|
|
Cancelled per conversation with point of contact. Need FIR permits for fire alarm and fire sprinkler work per notes entered on 12FEB 2019.
Laurin Phone #: ###-####
|
FIR18-00644
| INSP-Final Inspection | 3/22/2019 | 3/25/2019 | 3/25/2019 12:39:34 PM | P | FAIL |
|
|
Two speaker strobes in gym area are blocked by ducting. Need to test in-ducts for HVAC unit shutdown. Wire hanging out of communicator to fire panel.
Contact is Dirk. Phone #: ###-#### Inspection requested via web by Morgan Ahten
|
FIR19-00141
| INSP-Sprinkler Rough-in | 3/25/2019 | 3/25/2019 | 3/25/2019 12:07:04 PM | P | PART |
|
|
Rough to cover inspection for overhead firte sprinkler piping above two restroom hardlids in area of work complete, restroom hardlids approved for cover.
2 hard kids. Phone #: ###-#### Inspection requested via web by Sam Ball
|
FIR18-00633
| INSP-Sprinkler Rough-in/Hydro | 3/22/2019 | 3/25/2019 | 3/25/2019 10:58:24 AM | P | FAIL |
|
|
Prints show no more than 1 head off of 1 inch, dry sidewalls on level 1 have more than 1 head off of 1 inch, does not match city approved drawings. Add surge clips next to drops or provide longer rods to prevent surge.
Kenny Caldwell is the contact. He''d like this to be a partial rough-in/hydro for the 1st floor. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
|
FIR19-00171
| INSP-Conference | 3/22/2019 | 3/25/2019 | 3/25/2019 9:43:45 AM | A | DONE |
|
|
Fire conference complete.
Phone #: 2085733237 >> Inspection requested via mobile web by Scott Wilson
|
FIR18-00510
| INSP-Sprinkler Rough-in | 3/25/2019 | 3/25/2019 | 3/25/2019 9:26:58 AM | P | CANC |
|
|
5th floor tenting. Phone #: ###-#### >> Inspection requested via web by Sam Ball Inspection cancelled from web by: Sam Ball
|
FIR18-00678
| INSP-Final Inspection | 3/22/2019 | 3/25/2019 | 3/25/2019 8:50:10 AM | A | CANC |
|
|
Robert Phone #: ###-####
|
BLD19-00092
| FIRE-Final Inspection | 3/25/2019 | 3/25/2019 | 3/25/2019 8:43:45 AM | A | PASS |
|
|
Fire sprinkler inspection complete, fire alarm inspection complete, fire exitnguisher is placed with a current inspection tag. Final life fire safety inspection for area of work complete.
Tom Phone #: ###-####
|
FIR19-00097
| INSP-Final Inspection | 3/22/2019 | 3/25/2019 | 3/25/2019 8:12:14 AM | A | PASS |
|
|
Final fire sprinkler inspection complete.
Phone #: ###-#### Inspection requested via web by Sam Ball
|
FIR19-00128
| INSP-Final Inspection | 3/22/2019 | 3/25/2019 | 3/25/2019 8:11:41 AM | A | PASS |
|
|
Final fire alarm inspection complete.
Need to final alarms Phone #: ###-#### Inspection requested via web by Sam Ball
|