FIR18-00804
| INSP-Alarm Testing | 3/25/2019 | 3/26/2019 | 3/26/2019 4:31:42 PM | P | FAIL |
|
|
Too much water in piping during trip test, time was not met on system A, took 1 minute and 56 seconds for water to reach inspectors test.
Richard Clark is the contact. He requests a Trip Test for wings A ; B after school. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
|
FIR19-00159
| INSP-Sprinkler Rough-in | 3/26/2019 | 3/26/2019 | 3/26/2019 2:27:18 PM | P | PART |
|
|
Rough in inspection for north warehouse system complete.
|
FIR19-00159
| INSP-Sprinkler Rough-in/Hydro | 3/26/2019 | 3/26/2019 | 3/26/2019 2:26:07 PM | P | PART |
|
|
Hydrostatic test for north warehouse system witnessed, no pressure loss observed.
This will be hydro and rough in for north warehouse system. Please call Troy Nelson with time frame. Phone #: ###-#### Inspection requested via web by Jeff Packham
|
BLD18-02909
| BLD-Final | 3/25/2019 | 3/26/2019 | 3/26/2019 1:56:44 PM | P | NR |
|
|
301 added call before going out .
|
FIR18-00541
| INSP-Sprinkler Rough-in | 3/26/2019 | 3/26/2019 | 3/26/2019 1:15:30 PM | P | PASS |
|
|
Rough to cover inspection for overehad fire sprinkler in hallway next to gym complete, approved for cover.
Curt Phone #: ###-####
|
FIR18-00545
| INSP-Sprinkler Rough-in/Hydro | 3/26/2019 | 3/26/2019 | 3/26/2019 1:14:49 PM | P | DONE |
|
|
Hydrstatic test for underground supply witnessed, no pressure loss observed.
Gerardo Arce is the contact. This inspection is for a Hydro only. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
|
FIR18-00608
| INSP-Sprinkler Rough-in/Hydro | 3/26/2019 | 3/26/2019 | 3/26/2019 1:14:19 PM | P | DONE |
|
|
Hydrstatic test for underground supply witnessed, no pressure loss observed.
Gerardo Arce is the contact. This inspection is for a Hydro only. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
|
FIR18-00829
| INSP-Sprinkler Rough-in | 3/26/2019 | 3/26/2019 | 3/26/2019 1:13:42 PM | P | PASS |
|
|
Rough to cover inspection for overhead fire sprinkler piping/tenting complete, approved for cover.
Gerardo Arce is the contact. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
|
FIR18-00519
| INSP-Sprinkler Rough-in/Hydro | 3/26/2019 | 3/26/2019 | 3/26/2019 1:12:12 PM | P | DONE |
|
|
Hydrstatic test for underground supply witnessed, no pressure loss observed.
Gerardo Arce is the contact. This inspection is for a Hydro only. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
|
FIR18-00562
| INSP-Sprinkler Rough-in/Hydro | 3/26/2019 | 3/26/2019 | 3/26/2019 1:11:43 PM | P | DONE |
|
|
Hydrstatic test for underground supply witnessed, no pressure loss observed.
Gerardo Arce is the contact. This inspection is for a Hydro only. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
|
FIR18-00530
| INSP-Final Inspection | 3/26/2019 | 3/26/2019 | 3/26/2019 1:09:47 PM | P | NR |
|
|
Fire sprinkler system not ready to test.
As late as possible Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price
|
FIR18-00510
| INSP-Conference | 3/22/2019 | 3/26/2019 | 3/26/2019 12:47:18 PM | P | CANC |
|
|
Rescheduled per conversation with point of contact.
Look at concealed spaces Phone #: ###-#### Inspection requested via web by Sam Ball
|
FIR18-00943
| INSP-Sprinkler Rough-in | 3/25/2019 | 3/26/2019 | 3/26/2019 11:00:54 AM | P | PASS |
|
|
Rough to cover/tenting inspection for overhead fire sprinkler piping complete, approved for cover.
Tenting at same time as rough/hydro. Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
FIR18-00943
| INSP-Sprinkler Rough-in/Hydro | 3/25/2019 | 3/26/2019 | 3/26/2019 10:58:54 AM | P | PART |
|
|
Hydrostatic test for overhead fire sprinkler piping witnessed, no pressure loss observed.
Call James before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
FIR19-00047
| INSP-Sprinkler Rough-in | 3/25/2019 | 3/26/2019 | 3/26/2019 10:19:43 AM | A | PASS |
|
|
Rough to cover inspection for overehad fire sprinkler piping in area of work complete, area of work approved for cover.
Todd Ketterling is the contact. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
|
FIR18-00633
| INSP-Sprinkler Rough-in/Hydro | 3/25/2019 | 3/26/2019 | 3/26/2019 9:54:36 AM | A | PART |
|
|
Previously noted items in rooms on level 1, southeast wing have been corrected, southeast rooms approved for cover, total of 10.
This rough-in/hydro is for the 1st floor east side. The contact is Kenny Caldwell. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
|
FIR19-00004
| INSP-Sprinkler Rough-in | 3/25/2019 | 3/26/2019 | 3/26/2019 9:17:09 AM | A | PASS |
|
|
All tenting in place at time of inspection, overehad fire sprinkler piping approved for cover, approval sticker is placed by riser.
Tenting Inspection - Call James if there are any issues. Thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
FIR19-00129
| INSP-Final Inspection | 3/25/2019 | 3/26/2019 | 3/26/2019 8:57:02 AM | A | PASS |
|
|
Final fire sprinkler inspection for area of work complete.
Mike Martin is the contact. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
|
FIR18-00632
| INSP-Final Inspection | 3/20/2019 | 3/26/2019 | 3/26/2019 8:27:17 AM | P | CANC |
|
|
Cancelled per conversation with point of contact, will be rescheduled for a later date.
Colton Cox is the contact. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
|